Power Wiring
SINGLE-POINT POWER SUPPLY WIRING
Field Power Supply
Electrical / Controls Box
Power Side
1L1 1L2 1L3 | GND |
TB1
Line 1
Line 2
Line 3
Earth
Ground
Control Side
Wiring Terminal
Block
LD06414
NOTES:
1.All field wiring must be provided through a
2.All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3.Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4.Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5.Use copper conductors only.
6.On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section 100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device.
FIG. 2 – SINGLE-POINT POWER SUPPLY WIRING