York R-407C manual Physical Data

Page 7

Physical Data

 

 

FORM 100.50-EG1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 1 – PHYSICAL DATA

 

 

 

 

 

 

 

 

 

 

 

MODEL SIZE

50

55

60

65

GENERAL DATA

 

 

 

 

 

Length (Inches)

336

336

336

336

Width (Inches)

92

92

92

92

Height (Inches)

82

82

82

82

Operating Weights (Lbs.) (base unit, no options)

 

 

 

 

 

Cooling Only (Rigging & Refrigerant)

8,080

8,290

8,530

8,740

Rigging Weights (Lbs.) (base unit, no options)

 

 

 

 

 

Cooling Only

8,010

8,210

8,440

8,640

Option Weights (Lbs.)

 

 

 

 

 

Power Exhaust (Blower, motor, fan skid & mod damper)

647

647

647

647

Power Exhaust (Blower, motor, fan skid, VFD & baro damper)

654

654

654

654

100% AMS (Measurement Station & Mounting)

110

110

110

110

25/75% AMS (Measurement Station & Mounting)

130

130

130

130

Min. AMS (Measurement Station & Mounting)

40

40

40

40

Barometric only

36

36

36

36

Condenser Hail Guard

32

32

32

32

Copper Condenser Coils

617

617

793

793

Copper Evaporator Coils

262

320

400

500

Roof Curb Weights (Lbs.)

 

 

 

 

 

14" Full Perimeter Roof Curb

787

787

787

787

14" Open Condenser Roof Curb

555

555

555

555

Compressor Data

 

 

 

 

 

Quantity / Size (Nominal Tons )

4/13

4/13

4/15

 

4/15

Type

Scroll

Scroll

Scroll

 

Scroll

 

 

 

 

 

 

Capacity Steps (%)

25, 50, 75, 100

25, 50, 75, 100

25, 50, 75, 100

 

25, 50, 75, 100

Supply Fan and Drive

 

 

 

 

 

Quantity

1

1

1

1

Type

FC

FC

FC

 

FC

Size

25-22

25-22

25-22

25-22

Motor Size Range (min. to max. HP)

7.5-40

7.5-40

7.5-40

7.5-40

Air Flow Range (min. to max. cfm)

10000-22500

12000-24000

14000-27000

14000-27000

Static Pressure Range (min. to max. ESP)

0-4"

0-4"

0-4"

0-4"

Exhaust Fan

 

 

 

 

 

Quantity

2

2

2

2

Type

FC

FC

FC

 

FC

Size

15-15

15-15

15-15

15-15

Motor Size Range (min. to max. HP)

5-20

5-20

5-20

5-20

Air Flow Range (min. to max. cfm)

0-20000

0-20000

0-20000

0-20000

Static Pressure Range (min. to max. ESP)

0-1"

0-1"

0-1"

0-1"

Evaporator Coil

 

 

 

 

 

Size (square feet)

48.8

48.8

48.8

48.8

Number of rows/fins per inch

3/8

4/8

4/12

5/10

Tube Diameter/Surface

1/2"/enhanced

1/2"/enhanced

1/2"/enhanced

 

1/2"/enhanced

Condenser Coil (Aluminum Fins)

 

 

 

 

 

Size (square feet)

121.3

121.3

121.3

121.3

Number of rows/fins per inch

3/14

3/14

3/18

3/18

Tube Diameter

3/8"

3/8"

3/8"

3/8"

Condenser Coil (Copper Fins – Opt)

 

 

 

 

 

Size (square feet)

121.3

121.3

121.3

121.3

Number of rows/fins per inch

3/14

3/14

3/18

3/18

Tube Diameter

3/8"

3/8"

3/8"

3/8"

YORK INTERNATIONAL

7

Image 7
Contents 407C Optimized Through 65 Tons Packaged Rooftop Air Conditioning UnitsTable of Contents Basic Model Number NomenclatureIntroduction FEATURES/BENEFITSEcological and Economical Design Install with Ease and Safety ServiceabilityReliable Scroll Compressor Technology Introduction Physical Data Physical DataPhysical Data Cont’d Economizer Application DataLocation RiggingBuilding Exhaust Systems Harsh Environments Condenser and Evaporator Coil ProtectionRoof Curb Select Unit Selection ProcedureAcoustical Considerations GivenCooling Performance Data 50 TON Model Cooling Performance Data 50 Ton ModelCooling Performance Data 50 TON Model CONT’D Cooling Performance Data 55 TON Model Cooling Performance Data 55 Ton ModelCooling Performance Data 55 TON Model CONT’D Cooling Performance Data 60 TON Model Cooling Performance Data 60 Ton ModelCooling Performance Data 60 TON Model CONT’D Cooling Performance Data 65 TON Model Cooling Performance Data 65 Ton ModelCooling Performance Data 65 TON Model CONT’D 50 Through 65 TON Supply FAN Data Fan Performance50 Through 65 TON Supply FAN Data CONT’D 50 Through 65 TON Exhaust FAN Data Component Static Pressure Drops Inches of Water Column Filters Economizer Economizer Dampers Rigid Filter Manual or Compressors Electrical Service SizingElectrical Data Load DefinitionsCondenser FAN Motors / Each Supply and Exhaust FAN Motor ODP or TefcHigh Efficiency Premium EfficiencyGeneral Unoccupied / Occupied SwitchingControls Control Sequences for ALL UnitsExhaust Control Sequences Ventilation Control SequencesSmoke Purge Sequences LOW Ambient OperationCooling Operation VAV Specific SequencesStage 1 Y1 Call Stand Alone ControlCV Specific Sequences Cooling Operation Thermostat ControlSINGLE-POINT Power Supply Wiring Power WiringSINGLE-POINT Power Supply Wiring with NON-FUSED Disconnect SINGLE-POINT Power Supply Wiring With NON-FUSED DisconnectDUAL-POINT Power Supply Wiring DUAL-POINT Power Supply WiringField Control Wiring Field Control WiringDrawing General ArrangementBottom Supply Bottom Return General Arrangement Drawing Left or Right Rear Return SupplyCurb Layout Drawing Curb Layout DrawingBearings and Drives Guide SpecificationsConstruction Supply AIR SystemRefrigeration System Power SupplyAIR Filtering System AIR Inlet SystemControls Accessories and OptionsEconomizers Suction and Discharge Pressure Transducers moni Relief SystemEvaporator Coil Protection Condenser Coil ProtectionYork International York International Proud Sponsor Olympic Team