York R-407C manual Ventilation Control Sequences, Exhaust Control Sequences

Page 27

FORM 100.50-EG1

less than the Return Air enthalpy and the Outside Air temperature is less than the reference temperature set- ting. This method of economizing is the most accurate and provides the highest degree of energy efficiency for a packaged rooftop economizer.

VENTILATION CONTROL SEQUENCES

Minimum OA Damper Position (CV Units)

When the unit goes into the Occupied mode of opera- tion, the unit controller shall open the Outside Air Damper to a fixed minimum position. The damper shall remain at this position as long as the unit is in the occu- pied mode. The minimum position may be overridden more open by the unit controller when Outside Air con- ditions are suitable for economizing.

Minimum OA Damper Position (VAV Units)

With Variable Air Volume units, there are two Minimum OA Damper Positions, one when the unit is at full speed and the second when the unit is at approximately half speed. These two points allow the control to linearly reset the position of the OA damper in response to fan speed.

When the unit goes into the Occupied mode of opera- tion, the unit controller shall monitor the speed of the supply fan and open the Outside Air damper to a calcu- lated minimum position based on the fan speed. This minimum position shall vary as the speed of the fan changes. The damper shall remain at this calculated position as long as the unit is in the occupied mode. The minimum position may be overridden more open by the unit controller when Outside Air conditions are suitable for economizing.

Air Measurement Stations

When the unit is equipped with an air measurement station, the unit controller shall control the Outside Air damper to a measured flow rate through the Air Mea- surement Station.

When the unit goes into the Occupied mode of opera- tion, the unit controller shall control the Outside Air damper to maintain the Minimum AirFlow Setpoint through the Air Measurement Station. The unit control- ler shall control the Outside Air damper to this flow rate as long as the unit is in the Occupied mode. The Out- side Air damper may be overridden more open by the unit controller when Outside Air conditions are suitable for economizing.

Demand Ventilation

If an optional CO2 sensor is connected to the unit, the unit controller can reset the minimum OA damper position(s) or minimum flow rate based on demand.

The unit controller shall monitor the CO2 level within the building. If the CO2 level rises above the CO2 setpoint, the controller will temporarily increase the Minimum OA Damper Position or Minimum OA flow rate to increase ventilation. If the CO2 level drops below the CO2 set- point, the controller will decrease the Minimum OA Damper Position or Minimum OA flow rate to decrease ventilation.

Demand Ventilation shall remain active as long as the unit is in the Occupied mode of operation.

EXHAUST CONTROL SEQUENCES

Barometric

The optional barometric exhaust system consists of a lightweight barometric relief damper installed on the end of the unit in the Return Air section. As more outside air is introduced into the controlled zone due to Econo- mizer and Ventilation control sequences, the pressure inside the building rises. This increase in building pres- sure forces the barometric relief damper open to allow exhaust air to escape. Because this type of exhaust system is not powered, it is limited to small amounts of exhaust.

Powered Fixed Volume Exhaust Based on Outside Air Damper Position

This optional fixed volume powered exhaust system consists of a fixed speed fan that is controlled ON and OFF based on the position of the Outside Air Damper. During operation, when the Outside Air Damper opens to a selected turn-on point, the Exhaust Fan is cycled ON. The fan remains on as long as the Outside Air damper is above a selected turn-off point. If the Out- side Air Damper closes to the selected turn-off point, the Exhaust Fan is cycled OFF. The turn-on and turn- off points are user selectable from the OptiLogic™ User Interface panel.

Powered Fixed Volume Exhaust Based on Building Pressure

This optional fixed volume powered exhaust system consists of a fixed speed fan that is controlled ON and OFF based on the pressure inside the building. During

YORK INTERNATIONAL

27

Image 27
Contents 407C Optimized Through 65 Tons Packaged Rooftop Air Conditioning UnitsTable of Contents Basic Model Number NomenclatureFEATURES/BENEFITS IntroductionEcological and Economical Design Serviceability Install with Ease and SafetyReliable Scroll Compressor Technology Introduction Physical Data Physical DataPhysical Data Cont’d Economizer Application DataLocation RiggingHarsh Environments Condenser and Evaporator Coil Protection Building Exhaust SystemsRoof Curb Select Unit Selection ProcedureAcoustical Considerations GivenCooling Performance Data 50 TON Model Cooling Performance Data 50 Ton ModelCooling Performance Data 50 TON Model CONT’D Cooling Performance Data 55 TON Model Cooling Performance Data 55 Ton ModelCooling Performance Data 55 TON Model CONT’D Cooling Performance Data 60 TON Model Cooling Performance Data 60 Ton ModelCooling Performance Data 60 TON Model CONT’D Cooling Performance Data 65 TON Model Cooling Performance Data 65 Ton ModelCooling Performance Data 65 TON Model CONT’D Fan Performance 50 Through 65 TON Supply FAN Data50 Through 65 TON Supply FAN Data CONT’D 50 Through 65 TON Exhaust FAN Data Component Static Pressure Drops Inches of Water Column Filters Economizer Economizer Dampers Rigid Filter Manual or Compressors Electrical Service SizingElectrical Data Load DefinitionsCondenser FAN Motors / Each Supply and Exhaust FAN Motor ODP or TefcHigh Efficiency Premium EfficiencyGeneral Unoccupied / Occupied SwitchingControls Control Sequences for ALL UnitsExhaust Control Sequences Ventilation Control SequencesSmoke Purge Sequences LOW Ambient OperationCooling Operation VAV Specific SequencesStage 1 Y1 Call Stand Alone ControlCV Specific Sequences Cooling Operation Thermostat ControlSINGLE-POINT Power Supply Wiring Power WiringSINGLE-POINT Power Supply Wiring with NON-FUSED Disconnect SINGLE-POINT Power Supply Wiring With NON-FUSED DisconnectDUAL-POINT Power Supply Wiring DUAL-POINT Power Supply WiringField Control Wiring Field Control WiringGeneral Arrangement DrawingBottom Supply Bottom Return General Arrangement Drawing Left or Right Rear Return SupplyCurb Layout Drawing Curb Layout DrawingBearings and Drives Guide SpecificationsConstruction Supply AIR SystemRefrigeration System Power SupplyAIR Filtering System AIR Inlet SystemAccessories and Options ControlsEconomizers Suction and Discharge Pressure Transducers moni Relief SystemEvaporator Coil Protection Condenser Coil ProtectionYork International York International Proud Sponsor Olympic Team