Application Data

LOCATION

Of the many factors that can affect the acoustical char- acteristics of a rooftop installation, one of the most im- portant is the unit location. Ideally, the rooftop unit should be installed away from sound-sensitive areas, such as conference rooms, auditoriums and executive offices. Possible locations could be above storage areas, hall- ways, mechanical or utility rooms, or bathrooms.

The eco2 air conditioning units are designed for out- door installation. When selecting a site for installation, be guided by the following conditions:

Unit must be installed on a level surface.

For the outdoor location of the unit, select a place having a minimum sun exposure and an adequate supply of fresh air for the condenser.

Also avoid locations beneath windows or between structures.

Optional condenser coil protection should be used for seashore locations or other harsh environments.

The unit should be installed on a roof that is struc- turally strong enough to support the weight of the unit with a minimum of deflection. Extreme caution should be taken when the unit is mounted on a wood structured roof. It is recommended that the unit(s) be installed not more than 15 feet from a main sup- port beam to provide proper structural support and to minimize the transmission of sound and vibra- tion. Ideally, the center of gravity should be located over a structural support or building column.

Location of unit(s) should also be away from build- ing flue stacks or exhaust ventilators to prevent pos- sible reintroduction of contaminated air through the outside air intakes.

Be sure the supporting structures will not obstruct the duct, gas or wiring connections.

Proper service clearance space of 6-feet around the perimeter of the unit and 12-feet to any adja- cent units is required to eliminate cross contami- nation of exhaust and outdoor air, and for mainte- nance tasks such as coil pull and cleaning. No ob- structions should be above the condensing unit section.

RIGGING

Proper rigging and handling of the equipment is man- datory during unloading and setting it into position to retain warranty status.

Spreader bars must be used to prevent damage to the unit casing. All lifting lugs must be used when lifting the rooftop unit.

Care must be taken to keep the unit in the upright posi- tion during rigging and to prevent damage to the water- tight seams in the unit casing. Avoid unnecessary jar- ring or rough handling.

Ground Level Locations

It is important that the units be installed on a substan- tial base that will not settle, causing strain on the refrig- erant lines and sheet metal and resulting in possible leaks. A one-piece concrete slab with footers extended below the frost line is highly recommended. Addition- ally, the slab should not be tied to the main building foundation as noises may be transmitted into the build- ing structure.

For ground level installations, precautions should be taken to protect the unit from tampering by, or injury to, unauthorized persons. Erecting a fence around the unit is another common practice.

ECONOMIZER

The economizer section is used for ventilation of the conditioned space to maintain indoor air quality, and also to reduce energy consumption by using outdoor air cooling in lieu of mechanical cooling. If outdoor air is appropriate for cooling, but not sufficient for the cool- ing demand, mechanical cooling will stage on as nec- essary until the cooling load is met.

Comparative enthalpy operation is the most accurate and efficient means of economizer operation. The OptiLogicTM control monitors the return and outside air energy con- tent, and selects the lower of the two for operation.

VAV SUPPLY AIR PRESSURE CONTROL

Traditional packaged rooftop systems use inlet guide vanes (IGVs) for duct static pressure control. These con- trol supply duct pressure by modulating dampers (intro- ducing losses and inefficiencies) on the intlet of the fan, open and closed. Variable frequency drives (VFDs) of- fer superior fan speed control and quieter, energy effi- cient operation.

IGV inefficiency can be compared to the operation of a car. Modulating air flow with an IGV is like pressing on the gas to drive the car, but modulating the speed of the car by simultaneously pressing on the brake. VFD modu- lation is speed modulation by using just the gas pedal.

YORK INTERNATIONAL

9

Image 9
Contents 407C Optimized Through 65 Tons Packaged Rooftop Air Conditioning UnitsTable of Contents Basic Model Number NomenclatureFEATURES/BENEFITS IntroductionEcological and Economical Design Serviceability Install with Ease and SafetyReliable Scroll Compressor Technology Introduction Physical Data Physical DataPhysical Data Cont’d Location Application DataRigging EconomizerHarsh Environments Condenser and Evaporator Coil Protection Building Exhaust SystemsRoof Curb Acoustical Considerations Selection ProcedureGiven Select UnitCooling Performance Data 50 TON Model Cooling Performance Data 50 Ton ModelCooling Performance Data 50 TON Model CONT’D Cooling Performance Data 55 TON Model Cooling Performance Data 55 Ton ModelCooling Performance Data 55 TON Model CONT’D Cooling Performance Data 60 TON Model Cooling Performance Data 60 Ton ModelCooling Performance Data 60 TON Model CONT’D Cooling Performance Data 65 TON Model Cooling Performance Data 65 Ton ModelCooling Performance Data 65 TON Model CONT’D Fan Performance 50 Through 65 TON Supply FAN Data50 Through 65 TON Supply FAN Data CONT’D 50 Through 65 TON Exhaust FAN Data Component Static Pressure Drops Inches of Water Column Filters Economizer Economizer Dampers Rigid Filter Manual or Electrical Data Electrical Service SizingLoad Definitions CompressorsHigh Efficiency Supply and Exhaust FAN Motor ODP or TefcPremium Efficiency Condenser FAN Motors / EachControls Unoccupied / Occupied SwitchingControl Sequences for ALL Units GeneralExhaust Control Sequences Ventilation Control SequencesSmoke Purge Sequences LOW Ambient OperationCooling Operation VAV Specific SequencesCV Specific Sequences Stand Alone ControlCooling Operation Thermostat Control Stage 1 Y1 CallSINGLE-POINT Power Supply Wiring Power WiringSINGLE-POINT Power Supply Wiring with NON-FUSED Disconnect SINGLE-POINT Power Supply Wiring With NON-FUSED DisconnectDUAL-POINT Power Supply Wiring DUAL-POINT Power Supply WiringField Control Wiring Field Control WiringGeneral Arrangement DrawingBottom Supply Bottom Return General Arrangement Drawing Left or Right Rear Return SupplyCurb Layout Drawing Curb Layout DrawingConstruction Guide SpecificationsSupply AIR System Bearings and DrivesAIR Filtering System Power SupplyAIR Inlet System Refrigeration SystemAccessories and Options ControlsEconomizers Evaporator Coil Protection Relief SystemCondenser Coil Protection Suction and Discharge Pressure Transducers moniYork International York International Proud Sponsor Olympic Team