Controls (continued)
Stand Alone Control
If the unit is not configured for Thermostat or Zone Sen- sor operation, the unit will operate in Stand Alone Mode.
In Stand Alone Mode, the OptiLogic™ Controller will monitor only the Occupied/Unoccupied state. When the unit is commanded into the Occupied Mode of opera- tion, the OptiLogic™ Controller will start the Supply Fan. If the unit is equipped with an Economizer, the Control- ler will check to see if Outside Air conditions are suit- able for Economizing. The controller will then use Out- side Air (when available and suitable) and/or stage com- pressors up and down, as required, to maintain the VAV Low SAT Setpoint.
CV SPECIFIC SEQUENCES
Cooling Operation
Thermostat Control
If a
Stage 1 (“Y1”) Call
If Y1 is called and the unit is equipped with an econo- mizer, the control will check to see if the Outside Air is suitable for economizing. If conditions are suitable for economizing, the control will control the economizer and stage up compressors, as required, to maintain a high
SAT setpoint. If conditions are not suitable for econo- mizing or not equipped with an economizer, the control will stage up 50% of the compressors. This shall be maintained until Stage 1 is deactivated or Stage 2 is called.
Stage 2 (“Y2”) Call
If Y2 is called and the unit is equipped with an econo- mizer, the control will check to see if the Outside Air is suitable for economizing. If conditions are suitable for economizing, the control will control the economizer and stage up compressors, as required, to maintain a LOW SAT setpoint. If conditions are not suitable for econo- mizing or not equipped with an economizer, the control will stage up 100% of the compressors. This shall be maintained until Stage 2 is deactivated.
Zone Sensor Control
If a zone sensor controls the unit, the OptiLogic™ con- troller shall maintain all zone temperature setpoints. These setpoints are user selectable at the OptiLogic™ User Interface.
When a zone sensor is used for control, the OptiLogic™ unit controller will monitor the temperature within the space and control the unit accordingly. A