HP 6621A, 6623A, 6624A manual Unr +Cc, Asts?

Page 74

Figure 5-3. Functional Relationship of Status Registers

The supply has one serial poll register which services all outputs and provides the user with other power supply status- related information as discussed on page 75.

Status Register. Each output channel of the power supply maintains its present status in an 8-bit register. This status register reports the status of the output channel whenever it is queried. A "1" in any of the bit positions indicates that the condition is true. As long as the condition continues to be true, the bit will remain set. Assignments for the bits are shown in Table 5-5.

Decoding of the reading is based on the weighted number placed on each bit of the 8-bit status registers. For example, bit position 5 in the register has a bit weight of 32 (see Table 5-5). Each bit is assigned to a particular condition and the corresponding bit weight is used to identify that condition. When set, bit 5 indicates that the associated output is in the unregulated state. If this is the only bit that is set, the number 32 will be returned when the output's status register is queried.

Table 5-5. Bit Alignment for the Status, A Status, Fault, and Mask Register

Bit Position

7

6

5

4

3

2

1

0

Bit Weight

128

64

32

16

8

4

2

1

Meaning

CP

OC

UNR

OT

OV

-CC

+CC

CV

Where

 

 

 

 

 

 

 

 

CV = Constant Voltage Mode

+CC = Positive Constant Current Mode - CC = Negative Current Limit Mode

OV = Overvoltage Protection circuit tripped

OT = Over Temperature Protection circuit tripped UNR = Unregulated Mode

OC = Over Current Protection tripped CP = Coupled parameter (See Note)

Note: When the range is automatically switched as discussed on page70, the CP bit is set. It is cleared when you send a voltage or current value that causes no range change.

To query an output channel for its status, you must specify the output channel. For example, to find out the status at output

2 send the following query and address the supply to talk:

STS? 2

Accumulated Status Register. Each output channel of the power supply also maintains a cumulative status in its accumulated status (astatus) register. This register records every status condition the power supply output entered since it was last queried. When queried, it returns a decimal number which is decoded as shown below. The astatus register is reset to the present value of the status register after it is queried. The bits are assigned as in Table 5-5. Here is an example to help you decode the decimal number (from 0 to 255) returned when the astatus register is queried. If the output channel was in overvoltage since the last reading of the astatus register and that channel is presently operating in constant voltage mode, the reading you will get when you query the register will be 9. To decode this we use table 5-5.

9 =

8

+

1

 

OV

+

CV

For example, to query the astatus register of output 2, send the following query and address the supply to talk.

ASTS? 2

74 Remote Operation

Image 74
Contents Operating Manual HP Part NoCertification Safety Summary Safety Summary Symbol DescriptionDeclaration of Conformity EMCAppendix C--Command Summary Installation ProceduresAppendix A--Calibration Procedure Appendix D--Error MessagesTable Of Contents Remote Operation Local OperationCalibration Command SummaryError Messages Programming With The Series 200/300 ComputerPage Introduction Safety ConsiderationsGeneral Information Instrument and Manual IdentificationOutput Combinations Available Model AccessoriesDescription HP-IB Board Basic OperationOutput Low Range Values High Range Values Output Boards Definitions SpecificationsQualifying Conditions Output Response Characteristics Specifications Source EffectSupplemental Characteristics Outputs Low High Voltage Temperature CoefficientAC Input Power and Current Outputs Low High Voltage Programming ResolutionReadback Resolution Command Processing Time see FigureOutput Impedance Safety Agency ComplianceDimensions all models Low Voltage High Voltage 80 W Low VoltageGeneral Information General Information General Information General Information Location and Cooling InstallationInitial Inspection Input Power Requirements Line FuseLine Fuses 100/120 2110-0342 220/240 2110-0055Power Cord Line Voltage ConversionHP-IB Interface Connector Page Turning On Your Supply Front Panel Controls and IndicatorsGetting Started LCL key HP-IB Status AnnunciatorsAlphanumeric LCD Power Supply StatusAnnunciators System Control KeysOutput Control Keys Normal Self Test Indications Line SwitchNumeric Entry Keys Checking Out Your Supply Using Local Control Sample Self-Test Failure DisplayCurrent Test Voltage TestOvervoltage Test OCP Introduction To Remote OperationIset Enter Enter/Output StatementsReading the HP-IB Address Sending a Remote CommandOutput AddrDisp a Often Used CommandsGetting Data From The Supply Disp a Returning the Supply to Local Mode Output Connections and Operating Information Output RangesRange Selection Protection FeaturesOperating Quadrants Typical Output Range Characteristics Connecting the Load Page Cross Section Meters Area in mm2 Wire Bundled 10 a 20 aFeet Positive and Negative Voltages Remote Voltage SensingMultiple Loads Remote Voltage Sensing Remote Sense ConnectionsProgramming Response Time with an Output Capacitor Output Type FormulaOutput Noise Considerations Open Sense LeadsOvervoltage Trigger Connections External Trigger CircuitEquivalent Internal OV Trigger Circuit Parallel Operation Power Supply Protection ConsiderationsBattery Charging Maximum Allowable Voltage Setting CV OperationCC Operation Remote SensingSeries Operation 13. Series Connections with Local Sensing CV OperationSpecifications for Series Operation 14. Series Connections with Remote SensingPage Page Interface Function Remote OperationHP-IB Operation HP-IB Address Selection Numeric Data Power-On Service Request PONProgramming Syntax Sheet 1 of 2. Syntax Forms for Power Supply Commands Sheet 2 of 2. Syntax Forms for Power Supply Commands Iset Fault ?Vset OvsetPage Power Supply Commands Initial ConditionsVoltage Programming Current ProgrammingRange Switching OVSET? Output On/OffOvervoltage OV Protection Overcurrent Protection OCP Multiple Output Storage & RecallClear Command Status ReportingUNR +CC ASTS?Unmask 2,XXX FAULT?UNMASK? Bit Assignment of the Serial Poll RegisterService Request Generation SRQ? PON ?Display On/Off Reprogramming DelayRQS Bit Other Queries Response Code Front PanelExplanation TEST? Responses Code ExplanationPage Local Control Of Output Functions Local ModeLocal Operation GeneralSetting Voltage Setting CurrentResetting Overcurrent Protection Setting Overvoltage ProtectionResetting Overvoltage Protection Displaying the Contents of the Fault RegisterLocal Control Of System Functions Setting the Reprogramming DelaySetting the Supplys HP-IB Address ConditionSTO Enter Displaying Error MessagesAddr Enter RCL EnterPage Calibration Procedures Test Equipment and Setup RequiredFigure A-1. Calibration Setup General Calibration Procedure Are not stored. Exercise care when moving the leads Clear Voltmeter Output Buffer Calibration Program10 ! Calibration Example PauseFnend Input ANY More Outputs to CALIBRATE? Y or N,X$Disp END of Calibration Program Page Page Voltage and Current Programming Programming With a Series 200/300 ComputerPath Names Voltage and Current Programming With Variables Voltage and Current ReadbackService Request and Serial Poll Programming Power Supply RegistersPrint OUTPUT1 is in CV Mode END if Present StatusPrint Overvoltage on Output #1 Enable IntrOFF Intr Print Overvoltage on Output #2Error Detection Programming Outputs Connected In Parallel Stored Operating StatesInput Enter Voltage LIMIT,V Input Enter Operating VOLTAGE,V1Programming Outputs Connected In Series Input Enter the Desired Current Limit POINT,ICommand Description Command SummaryTable C-1. Command Summary Table C-l. Command Summary PON? ROM?Previously Table D-l. Power-On Self Test Error Message Error Codes and MessagesPower-On Self Test Messages Error Responses Test ResponsesTable D-2. Error Responses Error Code Message Explanation ERR? query ERR keyTable D-3. TEST? Responses Response Code Explanation TEST? queryPage Manual Backdating Make Changes6621A Generally Applicable AnnotationsII. CE92 Product Specific Annotations 6623AFar East Or contactEurope Latin America

6624A, 6621A, 6623A specifications

The HP 6623A, 6621A, and 6624A are precision DC power supplies widely recognized for their reliability and performance in various laboratory and industrial applications. These models are part of HP's 662X series, designed to cater to the needs of engineers, researchers, and technicians who require accurate power sources for their testing and development activities.

The main features of the HP 6623A, 6621A, and 6624A include their high stability, low ripple, and excellent load regulation, ensuring that the output voltage and current remain stable during testing. The power supplies provide multiple output channels, allowing users to power multiple devices simultaneously. The flexibility in setting voltage and current levels makes these models ideal for a wide range of applications, including semiconductor testing, device characterization, and system integration.

One of the standout technologies in the HP 662X series is the use of smart design techniques that minimize noise and enhance output performance. These power supplies incorporate advanced feedback mechanisms to maintain steady output, even under varying load conditions. Additionally, they feature programmable outputs, which means users can adjust the output levels through a connected computer or control system, streamlining the testing process and improving efficiency.

The HP 6623A model offers three independent outputs, with total power capabilities of 40 watts. It includes a 0-20V output, which can deliver up to 2A of current, along with two additional outputs that are adjustable. The 6621A provides a single output option, delivering a maximum of 20V and 2A, making it well-suited for simple applications where a single power source is required. In contrast, the HP 6624A stands out with its four independent output channels, providing a total of 60 watts, making it the most versatile of the three models.

Characteristics of these power supplies include user-friendly interfaces, allowing for easy configuration and monitoring of settings. LED indicators provide real-time feedback on voltage and current levels, enabling users to quickly assess the performance of their tests. Moreover, built-in protection features safeguard both the power supply and the connected devices from overvoltage and overcurrent conditions.

Overall, the HP 6623A, 6621A, and 6624A power supplies embody advanced engineering and design, making them invaluable tools for professionals looking for high-quality, reliable power sources for their electronic testing needs.