TABLE 7: PHYSICAL DATA

177820-YIM-A-0506

TABLE 7: PHYSICAL DATA

 

MODELS

 

BCH

 

 

036

048

060

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

Fan Motor HP (Direct Drive)

1/2

3/4

1

BLOWER

 

 

 

 

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

1 1/2

 

 

 

 

 

 

EVAPORATOR

Rows Deep

4

3

3

 

 

 

 

Fins Per Inch

16

15

15

COIL

 

 

 

 

Face Area (Sq. Ft.)

4.3

5.1

5.1

 

 

 

 

 

 

CONDENSER

Propeller Dia. (in.)

22

22

24

 

 

 

 

Fan Motor Hp

1/3

1/2

1/2

FANS

 

 

 

 

Nom. CFM

4300

4200

4500

 

 

 

 

 

 

CONDENSER

Rows Deep

1

1

1

 

 

 

 

Fins Per Inch

20

20

20

COILS

 

 

 

 

Face Area (Sq. Ft.)

17.1

17.1

17.1

 

 

 

 

 

 

COMPRESSOR

Reciprocating Type

1

1

1

(Qty. Per Unit)

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

FILTERS

 

 

 

 

Total Face Area (sq. ft.)

6.6

6.6

6.6

 

 

 

 

 

 

CHARGE

Refrigerant 22

7/12

9/2

8/4

(lbs./oz.)

 

 

 

 

TABLE 8: OPERATING WEIGHTS (LBS.)

 

MODEL SIZE

 

 

3 TON

4 TON

5 TON

BASIC UNIT

 

BCH

628

668

693

 

Economizer

 

50

 

 

 

 

 

 

 

Motorized Damper

 

26

 

 

 

 

 

 

 

 

OPTIONS

 

 

5 - 7 kW

 

18

 

 

 

 

 

 

 

Electric Heater

 

10 - 15 kW

 

23

 

OR

 

 

 

 

 

 

 

 

 

 

 

20 - 30 kW

 

28

 

ACCY.

 

 

 

 

 

 

 

 

 

 

 

 

Roof Curb

 

 

92

 

 

 

 

 

 

 

Barometric Relief / Fixed Air Damper

 

10

 

 

 

 

 

 

 

Belt-Drive Blower

 

5

 

14

Unitary Products Group

Image 14
Contents CONTENTS BCHINSTALLATION MANUAL SUNLINE SINGLE PACKAGE HEAT PUMPCOOLING SEQUENCE OF OPERATION TABLE OF CONTENTSSEQUENCE OF OPERATIONS OVERVIEW LIST OF FIGURES LIST OF TABLESINSPECTION SAFETY CONSIDERATIONSGENERAL REFERENCEPRODUCT NOMENCLATURE INSTALLATIONINSTALLATION SAFETY INFORMATION LIMITATIONSRIGGING AND HANDLING TABLE 1 UNIT APPLICATION DATA BCHLOCATION CLEARANCESFIGURE 1 - RECOMMENDED DRAIN PIPING COMPRESSORS DUCTWORKCONDENSATE DRAIN FIGURE 2 - COMPRESSOR RESTRAINING BRACKETSERVICE ACCESS FILTERSFIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRING TYPICAL POWER WIRINGTYPICAL CONTROL WIRING COOLING / HEATING 24 VOLT THERMOSTATOPTIONS/ACCESSORIES POWER AND CONTROL WIRINGTABLE 2 CONTROL WIRE SIZES THERMOSTATTABLE 3 ELECTRIC HEATER CFM LIMITATIONS ECONOMIZER/MOTORIZED DAMPER AND RAIN HOODMINIMUM POSITION ADJUSTMENT FIGURE 4 - ENTHALPY SETPOINT ADJUSTMENTFIGURE 5 - HONEYWELL ECONOMIZER CONTROL W7212 ENTHALPY SET POINT ADJUSTMENTFIGURE 6 - FOUR AND SIX POINT LOADING TABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTIONTABLE 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTION TABLE 4 CENTER OF GRAVITY ALL MODELSTABLE 8 OPERATING WEIGHTS LBS TABLE 7 PHYSICAL DATACOMPRESSORS Unitary Products Group None Unitary Products Group POWER SUPPLY TABLE 11 ELECTRIC HEAT CORRECTION FACTORSTABLE 12 VOLTAGE LIMITATIONS1 NOMINAL VOLTAGEDETAIL “B” FIGURE 8 - UNIT WITH ECONOMIZER RAINHOODDETAIL “A” TABLE 13 UTILITIES ENTRY FIGURE 10 - UNIT DIMENSIONS REAR VIEWFIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 14 MINIMUM CLEARANCESUnitary Products Group Page Unitary Products Group Unitary Products Group TABLE 19 BELT DRIVE BLOWER MOTOR AND DRIVE DATA177820-YIM-A-0506 PHASING FIGURE 12 - BELT ADJUSTMENTTABLE 20 STATIC RESISTANCES 5.Afteradjusting,re-tightennutsASEQUENCE OF OPERATIONS OVERVIEW OPERATIONFIGURE 13 - PRESSURE DROP ACROSS COIL COOLING SEQUENCE OF OPERATIONHIGH-PRESSURELIMIT SWITCH COOLING OPERATION ERRORSECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST INTERMITTENT BLOWERLOW-PRESSURELIMIT SWITCH SAFETY CONTROLSCOMPRESSOR PROTECTION FREEZESTATSAFETY CONTROLS HEAT ANTICIPATOR SETPOINTS TABLE 21 ELECTRIC HEAT LIMIT CONTROL SETTINGSTART-UPCOOLING TABLE 22 ELECTRIC HEAT ANTICIPATOR SETPOINTSOPERATING INSTRUCTIONS TROUBLESHOOTINGCOOLING TROUBLESHOOTING GUIDE POST START CHECK LISTUnitary Products Group 177820-YIM-A-0506a.24 volts at the thermostat Y1 terminal UNIT FLASH CODES MAINTENANCENORMAL MAINTENANCE TABLE 23 UNIT CONTROL BOARD FLASH CODES177820-YIM-A-0506 MOTORSOUTDOOR COIL Unitary Products GroupNorman Unitary5005 Products