York BCH 036 Static Resistances, Phasing, Belt Adjustment, Afteradjusting,re-tightennutsA

Page 26
TABLE 20: STATIC RESISTANCES
Scroll compressors require proper rotation to operate correctly. Do not change the internal wiring to make the blower, condenser fans, or compressor rotate correctly. Change the incoming power to the main terminal block to obtain proper rotation.
SUPPLY AIR BLOWERS
These blowers have either 3-speed direct drive motors, or single speed motors equipped with a belt drive. Belt drive units have a variable pitch motor pulley that allows the blower speed to be adjusted.
CHECKING SUPPLY AIR CFM
The RPM of the supply air blower will depend on the required CFM, the unit accessories or options and the static resistances of both the supply and the return air duct systems. With this information, the motor speed tap (direct drive) or the motor pulley number of turns open (belt drive) can be determined from the Blower Performance Data Tables.
26

177820-YIM-A-0506

TABLE 20: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

 

1800

 

2000

2200

2400

2600

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1, 2

0.07

0.08

0.09

0.11

 

0.13

 

0.15

0.17

0.20

0.23

ELECTRIC

5-15KW

0.04

0.05

0.06

0.07

 

0.08

 

0.10

0.12

0.14

0.16

HEATERS1

 

 

 

 

 

 

 

 

 

 

 

 

20-30KW

0.06

0.07

0.08

0.09

 

0.11

 

0.13

0.15

0.17

0.20

BOTTOM DUCT CONNECTIONS1

0.06

0.07

0.08

0.09

 

0.10

 

0.11

0.12

0.14

0.16

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

PHASING

PROCEDUREFORADJUSTINGBELTTENSION:

 

Check for proper compressor rotation. If the blower or

 

1

Loosennu

(A)(topandbottom).

 

compressors rotate in the wrong direction at start-up,

2

Adjustthet

 

byturningbolt(B).

 

the electrical connection to the unit is misphased.

3

Neverloosennuts(C)fromeachother.

 

4.Usebelttensioncheckertoapplyaperpendicularforcetobeonebeltatthe

Change the incoming line connection phasing to obtain

 

midpointofthespanasshown.Thedeflectionforceshouldbeapplied

 

untilaspecificdeflectiondistanceof4mm(5/32")is

.Todetermine

proper rotation. (Scroll compressors operate in only

 

thedeflection

fromnormalposition,useastraight

dgefrom

 

sheavetosheavedistanascereferenceline.herecommendedobtainedflectionforce

one direction. If the scroll is drawing low amperage,

 

isasfollows:

 

DEFLFORCE

 

has similar suction and discharge pressures, or pro-

 

 

 

 

ducing a high noise level, the scroll is misphased).

 

 

 

 

(A) (C)**Never(B)Loosen Tnsionnewbeltsatthemax.deflectionbetweenforcerecomendminandeforthebelt sdeflectionoperati.Check.forceAnyrethevalues-tenioningbelt.tensionshouldatleastfalltwotimestheduring.thfirstmax24.hoursof

5.Afteradjusting,re-tightennuts(A).

FIGURE 12 - BELT ADJUSTMENT

Note the following:

1. The supply air CFM must be within the limitations shown in the Unit Application Data Table 1.

2. Pulleys can be adjusted in half turn increments.

3. The tension on the belt should be adjusted as shown in the Belt Adjustment Figure 12.

Unitary Products Group

Image 26
Contents CONTENTS BCHINSTALLATION MANUAL SUNLINE SINGLE PACKAGE HEAT PUMPCOOLING SEQUENCE OF OPERATION TABLE OF CONTENTSSEQUENCE OF OPERATIONS OVERVIEW LIST OF FIGURES LIST OF TABLESINSPECTION SAFETY CONSIDERATIONSGENERAL REFERENCEPRODUCT NOMENCLATURE INSTALLATIONINSTALLATION SAFETY INFORMATION LIMITATIONSRIGGING AND HANDLING TABLE 1 UNIT APPLICATION DATA BCHLOCATION CLEARANCESFIGURE 1 - RECOMMENDED DRAIN PIPING COMPRESSORS DUCTWORKCONDENSATE DRAIN FIGURE 2 - COMPRESSOR RESTRAINING BRACKETSERVICE ACCESS FILTERSFIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRING TYPICAL POWER WIRINGTYPICAL CONTROL WIRING COOLING / HEATING 24 VOLT THERMOSTATOPTIONS/ACCESSORIES POWER AND CONTROL WIRINGTABLE 2 CONTROL WIRE SIZES THERMOSTATTABLE 3 ELECTRIC HEATER CFM LIMITATIONS ECONOMIZER/MOTORIZED DAMPER AND RAIN HOODMINIMUM POSITION ADJUSTMENT FIGURE 4 - ENTHALPY SETPOINT ADJUSTMENTFIGURE 5 - HONEYWELL ECONOMIZER CONTROL W7212 ENTHALPY SET POINT ADJUSTMENTFIGURE 6 - FOUR AND SIX POINT LOADING TABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTIONTABLE 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTION TABLE 4 CENTER OF GRAVITY ALL MODELSTABLE 8 OPERATING WEIGHTS LBS TABLE 7 PHYSICAL DATACOMPRESSORS Unitary Products Group None Unitary Products Group POWER SUPPLY TABLE 11 ELECTRIC HEAT CORRECTION FACTORSTABLE 12 VOLTAGE LIMITATIONS1 NOMINAL VOLTAGEDETAIL “B” FIGURE 8 - UNIT WITH ECONOMIZER RAINHOODDETAIL “A” TABLE 13 UTILITIES ENTRY FIGURE 10 - UNIT DIMENSIONS REAR VIEWFIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 14 MINIMUM CLEARANCESUnitary Products Group Page Unitary Products Group Unitary Products Group TABLE 19 BELT DRIVE BLOWER MOTOR AND DRIVE DATA177820-YIM-A-0506 PHASING FIGURE 12 - BELT ADJUSTMENTTABLE 20 STATIC RESISTANCES 5.Afteradjusting,re-tightennutsASEQUENCE OF OPERATIONS OVERVIEW OPERATIONFIGURE 13 - PRESSURE DROP ACROSS COIL COOLING SEQUENCE OF OPERATIONHIGH-PRESSURELIMIT SWITCH COOLING OPERATION ERRORSECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST INTERMITTENT BLOWERLOW-PRESSURELIMIT SWITCH SAFETY CONTROLSCOMPRESSOR PROTECTION FREEZESTATSAFETY CONTROLS HEAT ANTICIPATOR SETPOINTS TABLE 21 ELECTRIC HEAT LIMIT CONTROL SETTINGSTART-UPCOOLING TABLE 22 ELECTRIC HEAT ANTICIPATOR SETPOINTSOPERATING INSTRUCTIONS TROUBLESHOOTINGCOOLING TROUBLESHOOTING GUIDE POST START CHECK LISTUnitary Products Group 177820-YIM-A-0506a.24 volts at the thermostat Y1 terminal UNIT FLASH CODES MAINTENANCENORMAL MAINTENANCE TABLE 23 UNIT CONTROL BOARD FLASH CODES177820-YIM-A-0506 MOTORSOUTDOOR COIL Unitary Products GroupNorman Unitary5005 Products