York 048 & 060 Ductwork, Condensate Drain, Recommended Drain Piping Compressors, cut and remove

Page 7
DUCTWORK

177820-YIM-A-0506

DUCTWORK

Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Con- tractors of America (ACCA).

A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise.

The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should NOT be sized to match the dimen- sions of the duct connections on the unit.

When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor ductwork must be insulated and waterproofed.

Refer to Figures 7 and 10 for information concerning side and bottom supply and return air duct openings.

CONDENSATE DRAIN

Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the one-inch NPT female connection on the unit to an open drain.

NOTE: The condensate drain operates in a negative pressure in the cabinet. The condensate drain line MUST be trapped to provide proper drain- age. See Figure 1.

FIGURE 1 - RECOMMENDED DRAIN PIPING

COMPRESSORS

Units are shipped with compressor mountings factory- adjusted and ready for operation.

Units with scroll compressors have a shipping bracket which must be removed after the unit is set in place. See Figure 2.

Compressor

Mounting bracket

base

Remove these

screws (2)

Mounting bracket

top (remove)

Wire tie

(cut and remove)

FIGURE 2 - COMPRESSOR RESTRAINING BRACKET

Unitary Products Group

7

Image 7
Contents SUNLINE SINGLE PACKAGE HEAT PUMP BCHINSTALLATION MANUAL CONTENTSSEQUENCE OF OPERATIONS OVERVIEW TABLE OF CONTENTSCOOLING SEQUENCE OF OPERATION LIST OF TABLES LIST OF FIGURESREFERENCE SAFETY CONSIDERATIONSGENERAL INSPECTIONLIMITATIONS INSTALLATIONINSTALLATION SAFETY INFORMATION PRODUCT NOMENCLATURECLEARANCES TABLE 1 UNIT APPLICATION DATA BCHLOCATION RIGGING AND HANDLINGFIGURE 2 - COMPRESSOR RESTRAINING BRACKET DUCTWORKCONDENSATE DRAIN FIGURE 1 - RECOMMENDED DRAIN PIPING COMPRESSORSFILTERS SERVICE ACCESSCOOLING / HEATING 24 VOLT THERMOSTAT TYPICAL POWER WIRINGTYPICAL CONTROL WIRING FIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRINGTHERMOSTAT POWER AND CONTROL WIRINGTABLE 2 CONTROL WIRE SIZES OPTIONS/ACCESSORIESECONOMIZER/MOTORIZED DAMPER AND RAIN HOOD TABLE 3 ELECTRIC HEATER CFM LIMITATIONSENTHALPY SET POINT ADJUSTMENT FIGURE 4 - ENTHALPY SETPOINT ADJUSTMENTFIGURE 5 - HONEYWELL ECONOMIZER CONTROL W7212 MINIMUM POSITION ADJUSTMENTTABLE 4 CENTER OF GRAVITY ALL MODELS TABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTIONTABLE 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTION FIGURE 6 - FOUR AND SIX POINT LOADINGTABLE 7 PHYSICAL DATA TABLE 8 OPERATING WEIGHTS LBSCOMPRESSORS Unitary Products Group None Unitary Products Group NOMINAL VOLTAGE TABLE 11 ELECTRIC HEAT CORRECTION FACTORSTABLE 12 VOLTAGE LIMITATIONS1 POWER SUPPLYDETAIL “A” FIGURE 8 - UNIT WITH ECONOMIZER RAINHOODDETAIL “B” TABLE 14 MINIMUM CLEARANCES FIGURE 10 - UNIT DIMENSIONS REAR VIEWFIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 13 UTILITIES ENTRYUnitary Products Group Page Unitary Products Group 177820-YIM-A-0506 TABLE 19 BELT DRIVE BLOWER MOTOR AND DRIVE DATAUnitary Products Group 5.Afteradjusting,re-tightennutsA FIGURE 12 - BELT ADJUSTMENTTABLE 20 STATIC RESISTANCES PHASINGCOOLING SEQUENCE OF OPERATION OPERATIONFIGURE 13 - PRESSURE DROP ACROSS COIL SEQUENCE OF OPERATIONS OVERVIEWINTERMITTENT BLOWER COOLING OPERATION ERRORSECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST HIGH-PRESSURELIMIT SWITCHFREEZESTAT SAFETY CONTROLSCOMPRESSOR PROTECTION LOW-PRESSURELIMIT SWITCHSAFETY CONTROLS TABLE 22 ELECTRIC HEAT ANTICIPATOR SETPOINTS TABLE 21 ELECTRIC HEAT LIMIT CONTROL SETTINGSTART-UPCOOLING HEAT ANTICIPATOR SETPOINTSPOST START CHECK LIST TROUBLESHOOTINGCOOLING TROUBLESHOOTING GUIDE OPERATING INSTRUCTIONSa.24 volts at the thermostat Y1 terminal 177820-YIM-A-0506Unitary Products Group TABLE 23 UNIT CONTROL BOARD FLASH CODES MAINTENANCENORMAL MAINTENANCE UNIT FLASH CODESUnitary Products Group MOTORSOUTDOOR COIL 177820-YIM-A-0506Products Unitary5005 Norman