INTERMITTENT BLOWER

177820-YIM-A-0506

INTERMITTENT BLOWER

With the room thermostat fan switch set to “AUTO” and the system switch set to either the “AUTO” or “HEAT” settings, the blower is energized whenever a cooling or heating operation is requested. The blower is ener- gized after any specified delay associated with the operation.

When energized, the indoor blower has a minimum run time of 30 seconds. Additionally, the indoor blower has a delay of 10 seconds between operations.

NO OUTDOOR AIR OPTIONS

When the thermostat calls for cooling, the low-voltage control circuit from “R” to “Y1” and “G” is completed. The compressor and condenser fan motor are ener- gized. After completing the specified fan on delay for cooling, the UCB will energize the blower motor.

Once the thermostat has been satisfied, it will de-ener- gize Y1. If the compressor has satisfied its minimum run time, the compressor and condenser fan de-ener- gize. Otherwise, the unit operates the cooling system until the minimum run time for the compressor has been completed. After the compressor de-energizes, the blower is stopped following the elapse of the fan off delay for cooling.

To be available, a compressor must not be locked-out due to a high or low-pressure switch or freezestat trip and the anti-short cycle delay (ASCD) must have elapsed.

ECONOMIZER WITH SINGLE ENTHALPY SENSOR -

When the room thermostat calls for cooling, the low voltage control circuit from “R” to “G” and “Y1” is com- pleted. The UCB energizes the blower motor (if the fan switch on the room thermostat is set in the “AUTO” position) and drives the economizer dampers from fully closed to their minimum position. If the enthalpy of the outdoor air is below the setpoint of the enthalpy con- troller (previously determined), “Y1” energizes the economizer. The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor. If the outdoor air enthalpy is above the setpoint, “Y1” energizes the compressor and condenser fan motor only.

Once the thermostat has been satisfied, it will de-ener- gize “Y1”. If the compressor has satisfied its minimum run time, the compressor and condenser fan are de-

energized. Otherwise, the unit operates the cooling system until the minimum run times for the compressor has been completed. After the compressor de-ener- gizes, the blower is stopped following the elapse of the fan off delay for cooling, and the economizer damper goes to the closed position. If the unit is in continues fan operation the economizer damper goes to the min. position.

ECONOMIZER WITH DUAL ENTHALPY SENSORS -

The operation with the dual enthalpy sensors is identi- cal to the single sensor except that a second enthalpy sensor is mounted in the return air. This return air sen- sor allows the economizer to choose between outdoor air and return air, whichever has the lowest enthalpy value, to provide maximum operating efficiency.

ECONOMIZER (SINGLE OR DUAL) WITH POWER EXHAUST -

This system operates as specified above with one addition. The power exhaust motor is energized 45 seconds after the actuator position exceeds the exhaust fan setpoint on the economizer control. When the power exhaust is operating, the second stage of mechanical cooling will not operate. As always, the “R” to “G” connection provides minimum position but does not provide power exhaust operation.

MOTORIZED OUTDOOR AIR DAMPERS -

This system operation is the same as the units with no outdoor air options with one exception. When the “R” to “G” circuit is complete, the motorized damper drives open to a position set by the thumbwheel on the damper motor. When the “R” to “G” circuit is opened, the damper spring returns fully closed.

COOLING OPERATION ERRORS

Each cooling system is monitored for operation outside of the intended parameters. Errors are handled as described below. All system errors override minimum run times for compressors.

HIGH-PRESSURE LIMIT SWITCH

During cooling operation, if a high-pressure limit switch opens, the UCB will de-energize the compressor, ini- tiate the ASCD (Anti-short cycle delay), and, stop the condenser fan. If the call for cooling is still present at the conclusion of the ASCD, the UCB will re-energize the compressor.

28

Unitary Products Group

Image 28
Contents BCH INSTALLATION MANUALCONTENTS SUNLINE SINGLE PACKAGE HEAT PUMPSEQUENCE OF OPERATIONS OVERVIEW TABLE OF CONTENTSCOOLING SEQUENCE OF OPERATION LIST OF FIGURES LIST OF TABLESSAFETY CONSIDERATIONS GENERALINSPECTION REFERENCEINSTALLATION INSTALLATION SAFETY INFORMATIONPRODUCT NOMENCLATURE LIMITATIONSTABLE 1 UNIT APPLICATION DATA BCH LOCATIONRIGGING AND HANDLING CLEARANCESDUCTWORK CONDENSATE DRAINFIGURE 1 - RECOMMENDED DRAIN PIPING COMPRESSORS FIGURE 2 - COMPRESSOR RESTRAINING BRACKETSERVICE ACCESS FILTERSTYPICAL POWER WIRING TYPICAL CONTROL WIRINGFIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRING COOLING / HEATING 24 VOLT THERMOSTATPOWER AND CONTROL WIRING TABLE 2 CONTROL WIRE SIZESOPTIONS/ACCESSORIES THERMOSTATTABLE 3 ELECTRIC HEATER CFM LIMITATIONS ECONOMIZER/MOTORIZED DAMPER AND RAIN HOODFIGURE 4 - ENTHALPY SETPOINT ADJUSTMENT FIGURE 5 - HONEYWELL ECONOMIZER CONTROL W7212MINIMUM POSITION ADJUSTMENT ENTHALPY SET POINT ADJUSTMENTTABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTION TABLE 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTIONFIGURE 6 - FOUR AND SIX POINT LOADING TABLE 4 CENTER OF GRAVITY ALL MODELSTABLE 8 OPERATING WEIGHTS LBS TABLE 7 PHYSICAL DATACOMPRESSORS Unitary Products Group None Unitary Products Group TABLE 11 ELECTRIC HEAT CORRECTION FACTORS TABLE 12 VOLTAGE LIMITATIONS1POWER SUPPLY NOMINAL VOLTAGEDETAIL “A” FIGURE 8 - UNIT WITH ECONOMIZER RAINHOODDETAIL “B” FIGURE 10 - UNIT DIMENSIONS REAR VIEW FIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATIONTABLE 13 UTILITIES ENTRY TABLE 14 MINIMUM CLEARANCESUnitary Products Group Page Unitary Products Group 177820-YIM-A-0506 TABLE 19 BELT DRIVE BLOWER MOTOR AND DRIVE DATAUnitary Products Group FIGURE 12 - BELT ADJUSTMENT TABLE 20 STATIC RESISTANCESPHASING 5.Afteradjusting,re-tightennutsAOPERATION FIGURE 13 - PRESSURE DROP ACROSS COILSEQUENCE OF OPERATIONS OVERVIEW COOLING SEQUENCE OF OPERATIONCOOLING OPERATION ERRORS ECONOMIZER SINGLE OR DUAL WITH POWER EXHAUSTHIGH-PRESSURELIMIT SWITCH INTERMITTENT BLOWERSAFETY CONTROLS COMPRESSOR PROTECTIONLOW-PRESSURELIMIT SWITCH FREEZESTATSAFETY CONTROLS TABLE 21 ELECTRIC HEAT LIMIT CONTROL SETTING START-UPCOOLINGHEAT ANTICIPATOR SETPOINTS TABLE 22 ELECTRIC HEAT ANTICIPATOR SETPOINTSTROUBLESHOOTING COOLING TROUBLESHOOTING GUIDEOPERATING INSTRUCTIONS POST START CHECK LISTa.24 volts at the thermostat Y1 terminal 177820-YIM-A-0506Unitary Products Group MAINTENANCE NORMAL MAINTENANCEUNIT FLASH CODES TABLE 23 UNIT CONTROL BOARD FLASH CODESMOTORS OUTDOOR COIL177820-YIM-A-0506 Unitary Products GroupUnitary 5005Norman Products