York 048 & 060 Start-Upcooling, Electric Heat Limit Control Setting, Heat Anticipator Setpoints

Page 31
TABLE 21: ELECTRIC HEAT LIMIT CONTROL SETTING

177820-YIM-A-0506

TABLE 21: ELECTRIC HEAT LIMIT CONTROL SETTING

VOLTAGE

kW

TEMPERATURE LIMIT SWITCH

Open Temp ºF

 

 

 

 

 

5

1

140

 

 

 

 

 

7

1,3

140

 

 

 

 

 

10

1,2,3

140

230-1-60

 

 

 

15

2,4,6

140

 

 

 

 

 

20

1,2,3,4,5

140

 

 

 

 

6

150

 

 

 

 

 

 

 

30

1,2,3,4,5,6

150

 

 

 

 

 

5

1,2,3

140

 

 

 

 

 

7

1,2,3

140

 

 

 

 

 

10

1,2,3

150

230-3-60

 

 

 

15

2,4,6

140

 

 

 

 

 

20

1,2,3,4,5,6

150

 

 

 

 

 

30

1,3,5

160

 

 

 

 

2,4,6

150

 

 

 

 

 

 

 

7

2,4,6

140

 

 

 

 

 

10

2,4,6

140

460-3-60

 

 

 

15

2,4,6

140

 

 

 

 

 

20

3

160

 

 

 

 

 

30

3

150

 

 

 

 

 

10

2,4,6

140

 

 

 

 

575-3-60

15

2,4,6

140

 

 

 

20

5

160

 

 

 

 

 

 

30

5

150

 

 

 

 

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint will give shorter “ON” cycles and may result in the low- ering of the temperature within the conditioned space. Refer to Table 22 for the required electric heat anticipa- tor setting.

TABLE 22: ELECTRIC HEAT ANTICIPATOR SETPOINTS

HEATER

VOLTAGE

SETTING, AMPS

KW

TH1

TH2

 

5

 

0.024

0.35

7

 

0.024

0.35

10

230-3-60

0.024

0.35

15

0.024

0.35

 

20

 

0.024

0.35

30

 

0.024

0.35

7

 

0.024

0.35

10

 

0.024

0.35

15

460-3-60

0.024

0.35

20

 

0.024

0.37

30

 

0.024

0.37

10

 

0.024

0.35

15

575-3-60

0.024

0.35

20

0.024

0.37

 

30

 

0.024

0.37

START-UP (COOLING)

PRESTART CHECK LIST

After installation has been completed:

1.Check the electrical supply voltage being supplied. Be sure that it is the same as listed on the unit nameplate.

2.Set the room thermostat to the off position.

3.Turn unit electrical power on.

4.Set the room thermostat fan switch to on.

5.Check indoor blower rotation.

If blower rotation is in the wrong direction. Refer to Phasing Section in general informa- tion section.

Check blower drive belt tension.

6.Check the unit supply air (CFM). See “CHECKING SUPPLY AIR CFM” on page 26.

Unitary Products Group

31

Image 31
Contents SUNLINE SINGLE PACKAGE HEAT PUMP BCHINSTALLATION MANUAL CONTENTSSEQUENCE OF OPERATIONS OVERVIEW TABLE OF CONTENTSCOOLING SEQUENCE OF OPERATION LIST OF TABLES LIST OF FIGURESREFERENCE SAFETY CONSIDERATIONSGENERAL INSPECTIONLIMITATIONS INSTALLATIONINSTALLATION SAFETY INFORMATION PRODUCT NOMENCLATURECLEARANCES TABLE 1 UNIT APPLICATION DATA BCHLOCATION RIGGING AND HANDLINGFIGURE 2 - COMPRESSOR RESTRAINING BRACKET DUCTWORKCONDENSATE DRAIN FIGURE 1 - RECOMMENDED DRAIN PIPING COMPRESSORSFILTERS SERVICE ACCESSCOOLING / HEATING 24 VOLT THERMOSTAT TYPICAL POWER WIRINGTYPICAL CONTROL WIRING FIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRINGTHERMOSTAT POWER AND CONTROL WIRINGTABLE 2 CONTROL WIRE SIZES OPTIONS/ACCESSORIESECONOMIZER/MOTORIZED DAMPER AND RAIN HOOD TABLE 3 ELECTRIC HEATER CFM LIMITATIONSENTHALPY SET POINT ADJUSTMENT FIGURE 4 - ENTHALPY SETPOINT ADJUSTMENTFIGURE 5 - HONEYWELL ECONOMIZER CONTROL W7212 MINIMUM POSITION ADJUSTMENTTABLE 4 CENTER OF GRAVITY ALL MODELS TABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTIONTABLE 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTION FIGURE 6 - FOUR AND SIX POINT LOADINGTABLE 7 PHYSICAL DATA TABLE 8 OPERATING WEIGHTS LBSCOMPRESSORS Unitary Products Group None Unitary Products Group NOMINAL VOLTAGE TABLE 11 ELECTRIC HEAT CORRECTION FACTORSTABLE 12 VOLTAGE LIMITATIONS1 POWER SUPPLYDETAIL “A” FIGURE 8 - UNIT WITH ECONOMIZER RAINHOODDETAIL “B” TABLE 14 MINIMUM CLEARANCES FIGURE 10 - UNIT DIMENSIONS REAR VIEWFIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 13 UTILITIES ENTRYUnitary Products Group Page Unitary Products Group 177820-YIM-A-0506 TABLE 19 BELT DRIVE BLOWER MOTOR AND DRIVE DATAUnitary Products Group 5.Afteradjusting,re-tightennutsA FIGURE 12 - BELT ADJUSTMENTTABLE 20 STATIC RESISTANCES PHASINGCOOLING SEQUENCE OF OPERATION OPERATIONFIGURE 13 - PRESSURE DROP ACROSS COIL SEQUENCE OF OPERATIONS OVERVIEWINTERMITTENT BLOWER COOLING OPERATION ERRORSECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST HIGH-PRESSURELIMIT SWITCHFREEZESTAT SAFETY CONTROLSCOMPRESSOR PROTECTION LOW-PRESSURELIMIT SWITCHSAFETY CONTROLS TABLE 22 ELECTRIC HEAT ANTICIPATOR SETPOINTS TABLE 21 ELECTRIC HEAT LIMIT CONTROL SETTINGSTART-UPCOOLING HEAT ANTICIPATOR SETPOINTSPOST START CHECK LIST TROUBLESHOOTINGCOOLING TROUBLESHOOTING GUIDE OPERATING INSTRUCTIONSa.24 volts at the thermostat Y1 terminal 177820-YIM-A-0506Unitary Products Group TABLE 23 UNIT CONTROL BOARD FLASH CODES MAINTENANCENORMAL MAINTENANCE UNIT FLASH CODESUnitary Products Group MOTORSOUTDOOR COIL 177820-YIM-A-0506Products Unitary5005 Norman