Lochinvar TST2313, MP2, INS7141, INS7162 installation instructions Rotate / OFF

Page 23

The Alarm / C.A. DIP switch selects whether a combustion air damper or alarm device is to be connected to the C.A. / Alarm terminals (12 and 13) (FIG. 45).

ROTATE / OFF

FIG. 45

The Rotate / Off DIP switch selects whether or not the con- trol is to provide Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate, the stages will be rotat- ed accordingly. If the switch is set to Off, the firing sequence is fixed starting with the lowest stage to the highest stage (FIG. 46).

FIXED LAST / OFF

FIG. 46

The Fixed Last / Off DIP switch selects whether or not the last boiler is to be included in the rotation sequence. If the DIP switch is set to Fixed Last, the last boiler is always the last to fire (FIG. 47). This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate.

FIXED LEAD / OFF

The Fixed Lead / Off DIP switch selects whether or not the first boiler is to be included in the rotation sequence. If the DIP switch is set to Fixed Lead, the first boiler is always the first to fire (FIG. 48). This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate.

FIRST ON / LAST OFF OR FIRST ON / FIRST OFF

FIG. 48

The First On / Last Off or First On / First Off DIP switch selects whether the first boiler is the first to stage on and the last to stage off or the first to stage on and the first to stage off. This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate and the Fixed Lead / Off DIP switch is set to Fixed Lead (FIG. 49).

OFF / EXERCISE

FIG. 49

The Off / Exercise DIP switch selects whether or not the control is to exercise the primary pump and boiler pumps (FIG. 50). If the DIP switch is set to Exercise, the pumps are operated for 10 seconds after every three days of inactivity.

FIG. 47

FIG. 50

23

Image 23
Contents Additional Functions Include Installation InstructionsTable of Contents Display Set Point Boiler Reset Stand AloneSection a General Operation Domestic Hot WaterFixed Lead Rotation AlarmBoiler Alarm Combustion Air C. aMode Resetting the Rotation SequenceResetting the Running Times Section B Staging OperationLo / Lo Fire DelayLo / Hi Auto Differential Section C Pump OperationMed Fixed DifferentialBoiler Pump Purge Section D Boiler Reset OperationType of terminal unit. This improves the control of the air High Mass Radiant DHW Demand Section E Domestic HOT Water OPERA- TionDHW Mode 4 DHW in Primary / Secondary with Priority Section F SET Point Operation Section G External Input Operation Setp Mode 1 Setpoint in ParallelDc or 4 20 mA Dc or 0 20 mADHW Demand Ac PowerGeneral Boiler DemandPrimary Pump Contact Prim P1 Combustion Air / Alarm Contact C.A./AlarmSet Point Demand External Input 0 10 V dcBoiler Supply Sensor UnOccupied SwitchRelay 9 / DHW Boiler Return SensorExternal Input Primary Pump Prim P1 Combustion Air or Alarm C.A. / AlarmGeneral Cleaning the ControlRotate / OFF Page Page Page Boiler Maximum Stage DelayDHW Mode Boiler MinimumThis item is only available when DHW Mode is set to OFF Testing the Control Error Messages Is not a safety limit control Technical DataTypical Boiler Installation Typical Boiler Installation Typical DWH Priority Heating Package System