Lochinvar TST2313, MP2, INS7141, INS7162 Technical Data, Is not a safety limit control

Page 31

FIG. 59

The control is no longer able to read the boiler return sen- sor due to an open circuit (FIG. 59). The control will contin- ue to operate normally. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.

If the boiler return sensor was deliberately removed from the control, remove power from the control and repower the control to clear the error message.

FIG. 60

The control has detected no increase in the supply water temperature within the BOIL Alarm time setting. Check to see if the boilers are operating properly using the Test but- ton. To reset the alarm, press and hold the up and down arrow buttons for 5 seconds while in the VIEW menu.

TECHNICAL DATA

MP2 NINE STAGE BOILER & DHW / SET POINT

Control

- Microprocessor PID control; This

 

is not a safety (limit) control.

Packaged Weight - - 3.3 lb. (1500 g), Enclosure A, blue modified PPO plastic

Power Supply

- 115 V (ac) + 10% 50/60 Hz

 

600

Va

Relay Capacity

- 230 V (ac) 5 A 1/3 hp pilot duty

 

230

VA

Demands

 

 

 

 

 

 

 

 

- 20 to 260 V (ac) 2 VA

 

 

 

Sensors Included

 

 

 

 

- NTC thermistor, 10 k

 

@ 77°F

 

 

 

 

 

 

 

 

 

 

 

(25°C + 0.2°C) B=3892

 

 

 

Nine StageoilerB

& DHW /oinSetp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal wiring muste batedr

at

least

 

Do not applyowerp

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9 10 11

12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

H2026B

Com BoilBoilOutUnO

BoilCom Setp

 

 

Prim

 

 

 

Sup Ret +

Sw

Dem Dem DH

N

L

P1

1 1 2 2 3 3 4 4 5 5 6 6 7 7

8

8 DHW

 

FIG. 61

The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromag- netic noise. Conversely, this Class B digital apparatus com- plies with Part 15 of the FCC Rules and meets all require- ments of the Canadian Interference - Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is deter- mined by turning the control off and on, the user is encour- aged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connect- ed.

￿CAUTION

The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bush- ings and jumper wires.

Dimensions

- 6-5/8" H x 7-9/16" W x 2-13/16" D

 

(170 x 193 x 72 mm)

Approvals

- CSA C US, meets ICES & FCC

 

regulations for EMI/RFI

Ambient Conditions

- Indoor use only, 30 to 120°F (0 to

 

50°C), <95% RH non-condensing

31

Image 31
Contents Additional Functions Include Installation InstructionsTable of Contents Display Set Point Boiler Reset Stand AloneSection a General Operation Domestic Hot WaterFixed Lead Rotation AlarmBoiler Alarm Combustion Air C. aMode Resetting the Rotation SequenceResetting the Running Times Section B Staging OperationLo / Hi Fire DelayLo / Lo Auto Differential Section C Pump OperationMed Fixed DifferentialBoiler Pump Purge Section D Boiler Reset OperationType of terminal unit. This improves the control of the air High Mass Radiant DHW Demand Section E Domestic HOT Water OPERA- TionDHW Mode 4 DHW in Primary / Secondary with Priority Section F SET Point Operation Section G External Input Operation Setp Mode 1 Setpoint in ParallelDc or 4 20 mA Dc or 0 20 mADHW Demand Ac PowerGeneral Boiler DemandPrimary Pump Contact Prim P1 Combustion Air / Alarm Contact C.A./AlarmSet Point Demand External Input 0 10 V dcBoiler Supply Sensor UnOccupied SwitchRelay 9 / DHW Boiler Return SensorExternal Input Primary Pump Prim P1 Combustion Air or Alarm C.A. / AlarmGeneral Cleaning the ControlRotate / OFF Page Page Page Boiler Maximum Stage DelayDHW Mode Boiler MinimumThis item is only available when DHW Mode is set to OFF Testing the Control Error Messages Is not a safety limit control Technical DataTypical Boiler Installation Typical Boiler Installation Typical DWH Priority Heating Package System