Resetting the Rotation Sequence
To reset the rotation sequence, set the Rotate / Off DIP switch to the Off setting for 5 seconds and then return the DIP switch to the Rotate setting.
RUNNING TIMES
The control displays the accumulated running time of each boiler in the VIEW menu. When using a
Resetting the Running Times
To reset the running time for each boiler, select the appro- priate running time in the VIEW menu. Next, press the up and down arrow buttons simultaneously until CLR is dis- played.
EXERCISING
The control has a
Note: The exercising function does not work if power to the control or pumps is disconnected.
RELOADING FACTORY DEFAULTS
To reload the factory defaults, power down the control for 10 seconds. Power up the control while simultaneously hold- ing the Menu and down arrow buttons. The control will now display the E01 error message. To clear this error message, follow the procedure in the Error Messages section of this manual.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the con- trol is allowed to use as a boiler target temperature. During mild conditions, if the control calculates a boiler target tem- perature that is below the BOIL MIN setting, the boiler tar- get temperature is adjusted to at least the BOIL MIN setting. During this condition, if the boiler(s) is operating, the mini- mum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target tem- perature. Set the BOIL MIN setting to the boiler manufac- turer's recommended temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the BOIL MAX setting, and the boil- er temperature is near the boiler maximum temperature, the maximum segment will be displayed in the LCD while either the boiler target temperature or the boiler supply tempera- ture is being viewed. At no time does the control operate the boiler(s) above 248°F (120°C).
SECTION B: STAGING OPERATION
SECTION B1: STAGING
Mode
The control is capable of staging single stage, two stage, three stage or four stage on / off heat sources. In certain modes of operation the control is capable of controlling the individual boiler pumps. The control has 8 modes of opera- tion based on the type of staging and pump operation that is desired. The following describes the modes of operation:
Mode 1: 9 Single Stage Boilers and a primary pump.
Mode 2: 4 Single Stage Boilers with individual boiler pumps and a primary pump.
Mode 3: 4 Lo/Hi boilers and a primary pump.
Mode 4: 3 Lo/Hi boilers with individual boiler pumps and a primary pump.
Mode 5: 3 Three Stage Boilers and a primary pump.
Mode 6: 2 Three Stage Boilers with individual boiler pumps and a primary pump.
Mode 7: 2 Four Stage Boilers and a primary pump.
Mode 8: 1 Four Stage Boiler with a boiler pump and a pri- mary pump.