type of terminal unit. This improves the control of the air | ROOM |
temperature in the building. |
|
BOILER INDOOR DESIGN TEMPERATURE | The room is the desired room temperature for the building |
and provides a parallel shift of the heating curve. The room | |
| temperature desired by the occupants is often different from |
The indoor design temperature is the room temperature that | the design indoor temperature. If the room temperature is |
was used in the original heat loss calculations for the build- | not correct, adjusting the ROOM setting increases or |
ing. This setting establishes the beginning of the character- | decreases the amount of heat available to the building. A |
ized heating curve, see Figure 15 below. | ROOM setting is available for both the occupied (day) and |
| unoccupied (night) periods. |
BOIL DSGN |
BOIL IND |
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil,
FIG. 15
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air tempera- ture that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply tempera- ture rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
BOILER DESIGN TEMPERATURE
The design supply temperature is the supply water temper- ature required to heat the building when the outdoor air tem- perature is as cold as the outdoor design temperature.
WARM WEATHER SHUTDOWN
When the outdoor air temperature rises above the WWSD setting, the control turns on the WWSD pointer in the dis- play. When the control is in Warm Weather Shut Down, the boiler demand pointer is displayed if there is a boiler demand. However, the control does not operate the heating system to satisfy this demand. The control does respond to a DHW or set point demand and operates as described in sections E & F.
10