Lochinvar INS7162, MP2, INS7141 Type of terminal unit. This improves the control of the air

Page 10

type of terminal unit. This improves the control of the air

ROOM

temperature in the building.

 

BOILER INDOOR DESIGN TEMPERATURE

The room is the desired room temperature for the building

and provides a parallel shift of the heating curve. The room

 

temperature desired by the occupants is often different from

The indoor design temperature is the room temperature that

the design indoor temperature. If the room temperature is

was used in the original heat loss calculations for the build-

not correct, adjusting the ROOM setting increases or

ing. This setting establishes the beginning of the character-

decreases the amount of heat available to the building. A

ized heating curve, see Figure 15 below.

ROOM setting is available for both the occupied (day) and

 

unoccupied (night) periods.

BOIL DSGN

BOIL IND

TERMINAL UNITS

The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a termi- nal unit is selected, the control automatically loads the design supply temperature, maximum supply temperature, and minimum supply temperature (FIG. 16). The factory defaults are listed in Figure 16. These factory defaults can be changed to better match the installed system. If a facto- ry default has been changed, refer to section A to reload the factory defaults.

FIG. 15

OUTDOOR DESIGN TEMPERATURE

The outdoor design temperature is the outdoor air tempera- ture that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply tempera- ture rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.

BOILER DESIGN TEMPERATURE

The design supply temperature is the supply water temper- ature required to heat the building when the outdoor air tem- perature is as cold as the outdoor design temperature.

WARM WEATHER SHUTDOWN

When the outdoor air temperature rises above the WWSD setting, the control turns on the WWSD pointer in the dis- play. When the control is in Warm Weather Shut Down, the boiler demand pointer is displayed if there is a boiler demand. However, the control does not operate the heating system to satisfy this demand. The control does respond to a DHW or set point demand and operates as described in sections E & F.

10

Image 10
Contents Installation Instructions Additional Functions IncludeTable of Contents Display Domestic Hot Water Boiler Reset Stand AloneSection a General Operation Set PointCombustion Air C. a AlarmBoiler Alarm Fixed Lead RotationSection B Staging Operation Resetting the Rotation SequenceResetting the Running Times ModeLo / Hi Fire DelayLo / Lo Fixed Differential Section C Pump OperationMed Auto DifferentialSection D Boiler Reset Operation Boiler Pump PurgeType of terminal unit. This improves the control of the air High Mass Radiant Section E Domestic HOT Water OPERA- Tion DHW DemandDHW Mode 4 DHW in Primary / Secondary with Priority Section F SET Point Operation Setp Mode 1 Setpoint in Parallel Section G External Input OperationDc or 0 20 mA Dc or 4 20 mABoiler Demand Ac PowerGeneral DHW DemandExternal Input 0 10 V dc Combustion Air / Alarm Contact C.A./AlarmSet Point Demand Primary Pump Contact Prim P1Boiler Return Sensor UnOccupied SwitchRelay 9 / DHW Boiler Supply SensorExternal Input Combustion Air or Alarm C.A. / Alarm Primary Pump Prim P1Cleaning the Control GeneralRotate / OFF Page Page Page Boiler Minimum Stage DelayDHW Mode Boiler MaximumThis item is only available when DHW Mode is set to OFF Testing the Control Error Messages Technical Data Is not a safety limit controlTypical Boiler Installation Typical Boiler Installation Typical DWH Priority Heating Package System