Lochinvar F0600187510 service manual General Information, Venting Support

Page 10

Commercial Pool Heaters

INSTALLATION Continued

VENTING

General Information

You must supply adequate combustion and ventilation air to this pool heater. You must provide minimum clearances for the vent terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment” of the above-mentioned standards.

IMPORTANT: Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also check for corrosion or deterioration. If you find any problems, correct them at once.

Venting Support

Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot (21mm/m) on all horizontal runs from the pool heater to the vertical flue run or to the vent terminal on sidewall venting installations.

Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the venting system must not rest on the pool heater. Provide adequate support of the venting system. Follow all local and applicable codes. Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.

Vertical Vent Termination Clearances and Location

The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination.

The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.

A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.

You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.

Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.

Figure 10 – Vent Termination from Peaked Roof - 10' or Less From Ridge

IMPORTANT: Vent terminations are not shown in Figures 10, 11, 12, and 13. Make sure all vertical vents are installed with vent terminations recommended by the vent manufacturer.

Figure 11 – Vent Termination from Peaked Roof More Than 10' From Ridge

10

Image 10
Contents GAS Heaters for Commercial Pool Applications Do not try to light any applianceCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsCFK3304 CFK3302CFK3303 Combustion Air FilterInstallation Combustion Air OptionsOutside Combustion Air, Using Ducts Exhaust FansVenting Support General InformationVertical Vent Termination Clearances and Location Sidewall Vent Termination Clearances and Location Table BLength of Air Inlet Pipe Combustion Air Inlet PipingSidewall Air Inlet Vertical Rooftop Air Inlet Combined Air Inlet PointsConventional Negative Draft Venting Vent System OptionsNegative Draft Flue Outlet Piping Common Venting SystemsVertical DirectAire Venting Masonry Chimney InstallationsInspection of a Masonry Chimney Venting of Flue Products Vent KitsSidewall Venting Sidewall Venting Termination Sidewall FanSidewall Venting Without Fan Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Flue Pipe Materials Horizontal DV Venting TerminationCombustion Air Inlet Piping Air Inlet Piping Materials Connecting the Air Inlet Pipe to the Pool HeaterLength of Air Inlet Pipe Sealing Type-B Doublewall Vent Pipe or Galvanized Vent PipeCombined Combustion Air Inlet Points Vertical Rooftop Air InletHorizontal Combustion Air Inlet Clearances Outdoor Installation VentingVertical Combustion Air Inlet Clearances Outdoor Vent/Air Inlet LocationGas Pressure Test Combustion Air Fan Adjustment for startup3-Way Valve Cover Installation Outdoor Vent Cap KitGas Piping Connecting Gas Piping to the Pool HeaterGas Train and Controls Checking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment To adjust to the proper manifold gas pressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Relief Valve Water Flow SwitchAutomatic Chlorinator and Chemical Feeders Service Indicator Option Pump Purge Delay OptionWay Automatic Bypass Valve Wiring Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsTo Turn Off Gas To Pool Heater Pre-Start ChecklistStarting the Filter System Operation Programming Mode Error Messages Displayed by Temperature ControllerHot Surface Ignition Control Module Diagnostic Status IndicationHot Surface Igniter and Ignition Control Module Ignition Module Lockout FunctionsTABLE-N Access to Internal Control PanelIgnition and Control Timings Water Chemistry TABLE-OPipe Size Requirements TABLE-QMinimum Pump Performance High Water Temperature Limit ControlCirculating Pump Heat ExchangerWater Circulating Pump Flue Gas Passageways Cleaning ProceduresAppliance Area Burner FlamesElectrical Burner Removal and CleaningHeat Exchanger Cleaning Combustion and Ventilation AirCombustion Air Fan Adjustment Adjusting Differential Air PressureFan Cleaning Set-Up ProcedureServicing Hot Surface Igniter and Ignition Module Adjustment ProcedureIgnition System Checkout Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.