Lochinvar F0600187510 service manual Heater is Within 15 Feet of Pool Piping

Page 33

Installation and Service Manual

MODEL NO.

BYPASS PIPE SIZE

CP (N,L) 501 - 751

2” MINIMUM

 

 

CP (N,L) 991 - 2071

2 1/2” MINIMUM

AUTOMATIC

BYPASS VALVE

FACTORY POOL

RETURN SENSOR

LOCATION

PVC MINIMUM

(SEE TABLE)

RECOMMENDED

ISOLATION VALVE

FROM FILTER

 

 

VALVE

20' MAXIMUM

COPPER OR CPVC

110° LIMIT

(SEE TABLE)

3'

 

 

 

MINIMUM

TO POOL

ALTERNATE POOL

RETURN SENSOR

LOCATION

Figure 34 - Heater is Within 15 Feet of Pool Piping

MODEL NO.

BYPASS PIPE SIZE

CP (N,L) 501 - 751

2” MINIMUM

 

 

CP (N,L) 991 - 2071

2 1/2” MINIMUM

 

 

20' MAXIMUM

COPPER OR CPVC

(SEE TABLE)

FACTORY POOL

RETURN SENSOR

LOCATION

AUTOMATIC

BYPASS VALVE

PVC (SEE TABLE)

RECOMMENDED

ISOLATION VALVE

FROM FILTER

12"

OR FOUR PIPE

DIAMETERS

MAXIMUM

VALVE

110° LIMIT

3'

MINIMUM

TO POOL

ALTERNATE POOL

RETURN SENSOR

LOCATION

Figure 35 - Heater is Beyond 15 Feet of Pool Piping

33

Image 33
Contents Do not try to light any appliance GAS Heaters for Commercial Pool ApplicationsCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Base for Combustible Floors Clearances from Combustible ConstructionCFK3303 CFK3302CFK3304 Combustion Air FilterCombustion Air Options InstallationExhaust Fans Outside Combustion Air, Using DuctsGeneral Information Venting SupportVertical Vent Termination Clearances and Location Table B Sidewall Vent Termination Clearances and LocationCombustion Air Inlet Piping Length of Air Inlet PipeSidewall Air Inlet Combined Air Inlet Points Vertical Rooftop Air InletVent System Options Conventional Negative Draft VentingNegative Draft Common Venting Systems Flue Outlet PipingMasonry Chimney Installations Vertical DirectAire VentingInspection of a Masonry Chimney Vent Kits Venting of Flue ProductsSidewall Venting Sidewall Fan Sidewall Venting TerminationSidewall Venting Without Fan Masonry Chimney Installation TABLE-E Horizontal DirectAire VentingDirect Venting Horizontal DV Venting Termination Flue Pipe MaterialsCombustion Air Inlet Piping Length of Air Inlet Pipe Connecting the Air Inlet Pipe to the Pool HeaterAir Inlet Piping Materials Sealing Type-B Doublewall Vent Pipe or Galvanized Vent PipeVertical Rooftop Air Inlet Combined Combustion Air Inlet PointsVertical Combustion Air Inlet Clearances Outdoor Installation VentingHorizontal Combustion Air Inlet Clearances Outdoor Vent/Air Inlet Location3-Way Valve Cover Installation Combustion Air Fan Adjustment for startupGas Pressure Test Outdoor Vent Cap KitConnecting Gas Piping to the Pool Heater Gas PipingGas Train and Controls Venting of Combination Gas Valves Combination Gas ValvesChecking Gas Supply Pressure TABLE-JTable K Multiple Unit Installations Gas Supply Pipe SizingTo adjust to the proper manifold gas pressure Gas Manifold Pressure AdjustmentPumped Automatic Bypass Auxiliary Mixed Water Limit ControlWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Water Flow Switch Relief ValveAutomatic Chlorinator and Chemical Feeders Pump Purge Delay Option Service Indicator OptionWay Automatic Bypass Valve Wiring TABLE-M Terminal Strip Connection OptionsLighting Instructions OperationPre-Start Checklist To Turn Off Gas To Pool HeaterStarting the Filter System Operation Error Messages Displayed by Temperature Controller Programming ModeHot Surface Igniter and Ignition Control Module Diagnostic Status IndicationHot Surface Ignition Control Module Ignition Module Lockout FunctionsAccess to Internal Control Panel TABLE-NIgnition and Control Timings TABLE-O Water ChemistryTABLE-Q Pipe Size RequirementsCirculating Pump High Water Temperature Limit ControlMinimum Pump Performance Heat ExchangerAppliance Area Flue Gas Passageways Cleaning ProceduresWater Circulating Pump Burner FlamesHeat Exchanger Cleaning Burner Removal and CleaningElectrical Combustion and Ventilation AirFan Cleaning Adjusting Differential Air PressureCombustion Air Fan Adjustment Set-Up ProcedureAdjustment Procedure Servicing Hot Surface Igniter and Ignition ModuleIgnition System Checkout Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.