Lochinvar F0600187510 service manual Installation, Combustion Air Options

Page 8

Commercial Pool Heaters

INSTALLATION Continued

For convenience and flexibility, you can direct the combustion air inlet from either the back or right side of the pool heater. To arrange the combustion air inlet for side entry, follow the steps below.

1.Remove the metal panel from the pool heater’s side wall (see Figure 4).

2.Remove screws from the air filter/bracket assembly.

3.Move the filter/bracket assembly from the rear of the pool heater to the side opening (see Figure 5).

4.Attach the filter/bracket assembly to the pool heater’s side using the pre-drilled screw holes.

5.Attach the metal panel to the rear combustion air opening to seal it off.

Figure 4 – Metal Panel Covering Side Combustion Air Inlet

Figure 5 – Moving Air Filter/Bracket Assembly from Rear of Pool Heater to Side

Combustion Air Options

This pool heater has four combustion air options.

1.Outside Combustion Air, No Ducts

You can direct outside combustion air to this pool heater using either one or two permanent openings.

One Opening

The opening must have a minimum free area of one square inch per 3000 Btu input (7cm2 per kW). You must locate this opening within 12" (30cm) of the top of the enclosure.

Figure 6 – Outside Combustion Air - Single Opening

Two Openings

The combustion air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5cm2 per kW). You must locate this opening within 12" (30cm) of the bottom of the enclosure.

The ventilation air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5cm2 per kW). You must locate this opening within 12" (30cm) of the top of the enclosure.

Figure 7 – Outside Combustion Air - Two Openings

8

Image 8
Contents GAS Heaters for Commercial Pool Applications Do not try to light any applianceCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsCFK3302 CFK3303CFK3304 Combustion Air FilterInstallation Combustion Air OptionsOutside Combustion Air, Using Ducts Exhaust FansVertical Vent Termination Clearances and Location General InformationVenting Support Sidewall Vent Termination Clearances and Location Table BSidewall Air Inlet Combustion Air Inlet PipingLength of Air Inlet Pipe Vertical Rooftop Air Inlet Combined Air Inlet PointsNegative Draft Vent System OptionsConventional Negative Draft Venting Flue Outlet Piping Common Venting SystemsInspection of a Masonry Chimney Masonry Chimney InstallationsVertical DirectAire Venting Sidewall Venting Vent KitsVenting of Flue Products Sidewall Venting Without Fan Sidewall FanSidewall Venting Termination Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Combustion Air Inlet Piping Horizontal DV Venting TerminationFlue Pipe Materials Connecting the Air Inlet Pipe to the Pool Heater Length of Air Inlet PipeAir Inlet Piping Materials Sealing Type-B Doublewall Vent Pipe or Galvanized Vent PipeCombined Combustion Air Inlet Points Vertical Rooftop Air InletOutdoor Installation Venting Vertical Combustion Air Inlet ClearancesHorizontal Combustion Air Inlet Clearances Outdoor Vent/Air Inlet LocationCombustion Air Fan Adjustment for startup 3-Way Valve Cover InstallationGas Pressure Test Outdoor Vent Cap KitGas Train and Controls Connecting Gas Piping to the Pool HeaterGas Piping Combination Gas Valves Venting of Combination Gas ValvesChecking Gas Supply Pressure TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment To adjust to the proper manifold gas pressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Automatic Chlorinator and Chemical Feeders Water Flow SwitchRelief Valve Way Automatic Bypass Valve Wiring Pump Purge Delay OptionService Indicator Option Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsStarting the Filter System Pre-Start ChecklistTo Turn Off Gas To Pool Heater Operation Programming Mode Error Messages Displayed by Temperature ControllerDiagnostic Status Indication Hot Surface Igniter and Ignition Control ModuleHot Surface Ignition Control Module Ignition Module Lockout FunctionsIgnition and Control Timings Access to Internal Control PanelTABLE-N Water Chemistry TABLE-OPipe Size Requirements TABLE-QHigh Water Temperature Limit Control Circulating PumpMinimum Pump Performance Heat ExchangerFlue Gas Passageways Cleaning Procedures Appliance AreaWater Circulating Pump Burner FlamesBurner Removal and Cleaning Heat Exchanger CleaningElectrical Combustion and Ventilation AirAdjusting Differential Air Pressure Fan CleaningCombustion Air Fan Adjustment Set-Up ProcedureIgnition System Checkout Adjustment ProcedureServicing Hot Surface Igniter and Ignition Module Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.