Lochinvar F0600187510 service manual Vertical DirectAire Venting, Masonry Chimney Installations

Page 16

Commercial Pool Heaters

INSTALLATION Continued

Masonry Chimney Installations

A masonry chimney must be properly sized for the installation of a high efficiency gas-fired pool heater. Venting of a high efficiency pool heater into a cold or oversized masonry chimney can result in operational and safety problems. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency pool heater may not be able to sufficiently heat the masonry structure of the chimney to generate proper draft. This will result in condensing of flue products, damage to the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space. Carefully inspect all chimney systems before installation.

Inspection of a Masonry Chimney

A masonry chimney must be carefully inspected to determine its suitability for the venting of flue products. A clay-tile-lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined with a properly-sized and approved chimney liner system. An unlined masonry chimney must not be used to vent flue products from this high-efficiency pool heater. An unlined chimney must be relined with an approved chimney liner system when a new pool heater is being attached to it. Metallic liner systems (Type-B doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.

Vertical Vent Termination Clearances and Location Follow all vertical venting termination information for clearances and location under Vertical Vent Termination Clearances and Location, page 10.

You can terminate the combustion air pipe either horizontally with a sidewall air inlet or vertically with a rooftop air inlet. The installed length of air inlet pipe from the pool heater to the outside air inlet cap must not exceed 50 equivalent feet (15.2m).

Figure 18 – Vertical DirectAire Installation with Sidewall Combustion Air Inlet

2. Vertical DirectAire™ Venting

IMPORTANT: Before installing a venting system, follow all venting clearances and requirements found in the Venting, General Information section, page 10.

Figure 19 – Air Inlet Cap for Sidewall Termination

The Vertical DirectAire™ vent system is the same as the Conventional Negative Draft vent system, except it pulls combustion air from the outdoors through a sidewall or vertical air inlet. Follow all requirements in Conventional Negative Draft Venting, page 14.

The Vertical DirectAire™ vent system requires you to install two vent pipes directly to the pool heater; one vertical pipe with a rooftop termination for the flue products and one pipe for combustion air. For this venting option, you must purchase the DV box adapter. The DV box attaches to the air inlet of the pool heater. The pipe for combustion air attaches to the DV box.

16

Image 16
Contents GAS Heaters for Commercial Pool Applications Do not try to light any applianceCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsCFK3302 CFK3303CFK3304 Combustion Air FilterInstallation Combustion Air OptionsOutside Combustion Air, Using Ducts Exhaust FansVenting Support General InformationVertical Vent Termination Clearances and Location Sidewall Vent Termination Clearances and Location Table BLength of Air Inlet Pipe Combustion Air Inlet PipingSidewall Air Inlet Vertical Rooftop Air Inlet Combined Air Inlet PointsConventional Negative Draft Venting Vent System OptionsNegative Draft Flue Outlet Piping Common Venting SystemsVertical DirectAire Venting Masonry Chimney InstallationsInspection of a Masonry Chimney Venting of Flue Products Vent KitsSidewall Venting Sidewall Venting Termination Sidewall FanSidewall Venting Without Fan Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Flue Pipe Materials Horizontal DV Venting TerminationCombustion Air Inlet Piping Connecting the Air Inlet Pipe to the Pool Heater Length of Air Inlet PipeAir Inlet Piping Materials Sealing Type-B Doublewall Vent Pipe or Galvanized Vent PipeCombined Combustion Air Inlet Points Vertical Rooftop Air InletOutdoor Installation Venting Vertical Combustion Air Inlet ClearancesHorizontal Combustion Air Inlet Clearances Outdoor Vent/Air Inlet LocationCombustion Air Fan Adjustment for startup 3-Way Valve Cover InstallationGas Pressure Test Outdoor Vent Cap KitGas Piping Connecting Gas Piping to the Pool HeaterGas Train and Controls Combination Gas Valves Venting of Combination Gas ValvesChecking Gas Supply Pressure TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment To adjust to the proper manifold gas pressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Relief Valve Water Flow SwitchAutomatic Chlorinator and Chemical Feeders Service Indicator Option Pump Purge Delay OptionWay Automatic Bypass Valve Wiring Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsTo Turn Off Gas To Pool Heater Pre-Start ChecklistStarting the Filter System Operation Programming Mode Error Messages Displayed by Temperature ControllerDiagnostic Status Indication Hot Surface Igniter and Ignition Control ModuleHot Surface Ignition Control Module Ignition Module Lockout FunctionsTABLE-N Access to Internal Control PanelIgnition and Control Timings Water Chemistry TABLE-OPipe Size Requirements TABLE-QHigh Water Temperature Limit Control Circulating PumpMinimum Pump Performance Heat ExchangerFlue Gas Passageways Cleaning Procedures Appliance AreaWater Circulating Pump Burner FlamesBurner Removal and Cleaning Heat Exchanger CleaningElectrical Combustion and Ventilation AirAdjusting Differential Air Pressure Fan CleaningCombustion Air Fan Adjustment Set-Up ProcedureServicing Hot Surface Igniter and Ignition Module Adjustment ProcedureIgnition System Checkout Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.