Lochinvar F0600187510 service manual Sidewall Vent Termination Clearances and Location, Table B

Page 11

Installation and Service Manual

Figure 12 – Vent Termination from Flat Roof 10' or Less from Parapet Wall

Provide a minimum clearance of 4 feet (1.2m) horizontally from electric meters, gas meters, regulators, and relief equipment. Never locate the vent cap above or below electric meters, gas meters, regulators, and relief equipment unless a 4 foot (1.2m) horizontal clearance is maintained.

Terminate the venting system at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).

Terminate the venting system at least 4 feet (1.2m) below, 4 feet (1.2m) beside, or 1 foot (30cm) above any door, window, or gravity air inlet into any building.

Locate vent termination at least 8 feet (2.4m) horizontally from any combustion air intake located above the sidewall termination cap.

￿CAUTION: Pool heaters which are shut down or will not operate may experience freezing due to convective air flow in the flue pipe, through the air inlet, or from negative pressure in the equipment room. In cold climates, operate pump continuously to help prevent freezing of pool heater water. Provide proper freeze protection. See Freeze Protection, page 7.

Figure 13 – Vent Termination from Flat Roof More Than 10' from Parapet Wall

Sidewall Vent Termination Clearances and Location

Locate the bottom of the vent terminal at least 12 inches (30cm) above grade and above normal snow levels. Locate the bottom of the vent terminal at least 7 feet (2.13m) above grade when located adjacent to public walkways. Do not terminate directly above a public walkway.

Do not terminate the venting system in a window well, stairwell, alcove, courtyard, or other recessed area. Do not terminate the venting system below grade.

Locate vent termination at least 3 feet (0.91m) from an inside corner of an L-shaped structure.

TABLE - B

Flue and Air Inlet Pipe Sizes

Input

Flue

Air Inlet

Btu / hr

Size

Size*

 

 

 

500,000

6"

6"

 

 

 

650,000

8"

8"

 

 

 

750,000

8"

8"

 

 

 

990,000

10"

10"

 

 

 

1,260,000

12"

12"

 

 

 

1,440,000

12"

12"

 

 

 

1,800,000

14"

12"

 

 

 

2,070,000

14"

12"

 

 

 

*Minimum diameter for air inlet pipe. Installer may increase diameter one pipe size for ease of installation, if needed. Refer to the National Fuel Gas Code (ANSI Z223.1) Vent Tables for additional guidance on vent sizing of fan assisted appliances.

11

Image 11
Contents Do not try to light any appliance GAS Heaters for Commercial Pool ApplicationsCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Base for Combustible Floors Clearances from Combustible ConstructionCombustion Air Filter CFK3302CFK3303 CFK3304Combustion Air Options InstallationExhaust Fans Outside Combustion Air, Using DuctsVertical Vent Termination Clearances and Location General InformationVenting Support Table B Sidewall Vent Termination Clearances and LocationSidewall Air Inlet Combustion Air Inlet PipingLength of Air Inlet Pipe Combined Air Inlet Points Vertical Rooftop Air InletNegative Draft Vent System OptionsConventional Negative Draft Venting Common Venting Systems Flue Outlet PipingInspection of a Masonry Chimney Masonry Chimney InstallationsVertical DirectAire Venting Sidewall Venting Vent KitsVenting of Flue Products Sidewall Venting Without Fan Sidewall FanSidewall Venting Termination Masonry Chimney Installation TABLE-E Horizontal DirectAire VentingDirect Venting Combustion Air Inlet Piping Horizontal DV Venting TerminationFlue Pipe Materials Sealing Type-B Doublewall Vent Pipe or Galvanized Vent Pipe Connecting the Air Inlet Pipe to the Pool HeaterLength of Air Inlet Pipe Air Inlet Piping MaterialsVertical Rooftop Air Inlet Combined Combustion Air Inlet PointsOutdoor Vent/Air Inlet Location Outdoor Installation VentingVertical Combustion Air Inlet Clearances Horizontal Combustion Air Inlet ClearancesOutdoor Vent Cap Kit Combustion Air Fan Adjustment for startup3-Way Valve Cover Installation Gas Pressure TestGas Train and Controls Connecting Gas Piping to the Pool HeaterGas Piping TABLE-J Combination Gas ValvesVenting of Combination Gas Valves Checking Gas Supply PressureTable K Multiple Unit Installations Gas Supply Pipe SizingTo adjust to the proper manifold gas pressure Gas Manifold Pressure AdjustmentPumped Automatic Bypass Auxiliary Mixed Water Limit ControlWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Automatic Chlorinator and Chemical Feeders Water Flow SwitchRelief Valve Way Automatic Bypass Valve Wiring Pump Purge Delay OptionService Indicator Option TABLE-M Terminal Strip Connection OptionsLighting Instructions OperationStarting the Filter System Pre-Start ChecklistTo Turn Off Gas To Pool Heater Operation Error Messages Displayed by Temperature Controller Programming ModeIgnition Module Lockout Functions Diagnostic Status IndicationHot Surface Igniter and Ignition Control Module Hot Surface Ignition Control ModuleIgnition and Control Timings Access to Internal Control PanelTABLE-N TABLE-O Water ChemistryTABLE-Q Pipe Size RequirementsHeat Exchanger High Water Temperature Limit ControlCirculating Pump Minimum Pump PerformanceBurner Flames Flue Gas Passageways Cleaning ProceduresAppliance Area Water Circulating PumpCombustion and Ventilation Air Burner Removal and CleaningHeat Exchanger Cleaning ElectricalSet-Up Procedure Adjusting Differential Air PressureFan Cleaning Combustion Air Fan AdjustmentIgnition System Checkout Adjustment ProcedureServicing Hot Surface Igniter and Ignition Module Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.