Lochinvar F0600187510 service manual Combustion Air Fan Adjustment for startup, Gas Pressure Test

Page 26

Commercial Pool Heaters

INSTALLATION Continued

TABLE H

Outdoor Vent Cap Kits

Input

Outdoor Vent Kit*

Btu/hr

 

 

 

500,000

ODK3075

 

 

650,000

ODK3076

 

 

750,000

ODK3076

 

 

990,000

ODK3077

 

 

1,260,000

ODK3078

 

 

1,440,000

ODK3079

 

 

1,800,000

ODK3080

 

 

2,070,000

ODK3080

 

 

* These kits include an outdoor vent cap and gasket.

Flue gas condensate can freeze on exterior walls or on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition. Some discoloration to exterior building or pool heater surfaces can be expected. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.

The Outdoor Vent Cap Kit

The optional outdoor vent cap kit is available from the pool heater manufacturer. The outdoor cap part numbers are listed by input size. See TABLE–H for kit numbers.

Install the outdoor vent cap on the rear of the pool heater, see Figure 27.

The air filter bracket will need to be rotated as shown in Figure 27 to allow proper access to the filters with the outdoor vent cap in place.

The 3-Way Valve Cover Installation

The 3-way bypass valve requires a cover for outdoor use. This cover is provided with the outdoor vent kits listed in Table-H. See page 31 for 3-way valve cover installation instructions.

Combustion Air Fan Adjustment (for startup)

For startup, the combustion air fan shutter may require adjustment. Should the combustion air fan shutter need adjusting refer to the Adjusting Differential Air Pressure instructions located under the Cleaning and Maintenance section on page 49 of this manual.

Note: The manifold gas pressure can affect the differential air pressure. Once the combustion air fan shutter has been adjusted, confirm manifold gas pressure as described in the Gas Manifold Pressure Adjustment section on page 30 of this manual.

Figure 27 – Outdoor Vent Cap Installed on Rear of Pool Heater

CONNECTING TO GAS SUPPLY

Only supply gas type specified on the pool heater’s rating plate. This pool heater is orificed for operation up to 2000 feet altitude. If installing above 2000 feet elevation, consult the pool heater manufacturer.

INLET PRESSURE: Measure inlet pressure at the inlet pressure tap located upstream of the combination gas valve(s).

See TABLE–I for maximum and minimum inlet pressures. Do not exceed the maximum. Minimum inlet pressure is for the purposes of input adjustment.

TABLE-I

Inlet Pressure

 

Maximum

Minimum

 

 

 

Natural Gas

10.5" w.c.

4.5" w.c.

 

 

 

LP Gas

13" w.c.

8" w.c.

 

 

 

MANIFOLD PRESSURE: Measure manifold pressure at the pressure tap on the downstream side of the combination gas valves. The gas regulator on the pool heater’s combination gas valves is preset at the factory to supply proper manifold pressure for normal operation. See TABLE–L, page 31 for net manifold pressure settings.

If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment, page 30. Do not increase regulator pressure beyond specified pressure setting.

Gas Pressure Test

1.Disconnect the unit from the gas supply piping system during any piping system pressure testing greater than 1/2 PSIG (3.5kPa)

2.Isolate the pool heater from the gas supply piping system by closing a manual shutoff valve during any piping system pressure testing that is equal to or less than 1/2 PSIG (3.5kPa).

3.Test all gas connections for gas leaks before placing the pool heater in operation.

26

Image 26
Contents GAS Heaters for Commercial Pool Applications Do not try to light any applianceCommercial Pool Heaters General Product Information Commercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsCFK3304 CFK3302CFK3303 Combustion Air FilterInstallation Combustion Air OptionsOutside Combustion Air, Using Ducts Exhaust FansVertical Vent Termination Clearances and Location General InformationVenting Support Sidewall Vent Termination Clearances and Location Table BSidewall Air Inlet Combustion Air Inlet PipingLength of Air Inlet Pipe Vertical Rooftop Air Inlet Combined Air Inlet PointsNegative Draft Vent System OptionsConventional Negative Draft Venting Flue Outlet Piping Common Venting SystemsInspection of a Masonry Chimney Masonry Chimney InstallationsVertical DirectAire Venting Sidewall Venting Vent KitsVenting of Flue Products Sidewall Venting Without Fan Sidewall FanSidewall Venting Termination Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Combustion Air Inlet Piping Horizontal DV Venting TerminationFlue Pipe Materials Air Inlet Piping Materials Connecting the Air Inlet Pipe to the Pool HeaterLength of Air Inlet Pipe Sealing Type-B Doublewall Vent Pipe or Galvanized Vent PipeCombined Combustion Air Inlet Points Vertical Rooftop Air InletHorizontal Combustion Air Inlet Clearances Outdoor Installation VentingVertical Combustion Air Inlet Clearances Outdoor Vent/Air Inlet LocationGas Pressure Test Combustion Air Fan Adjustment for startup3-Way Valve Cover Installation Outdoor Vent Cap KitGas Train and Controls Connecting Gas Piping to the Pool HeaterGas Piping Checking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment To adjust to the proper manifold gas pressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Automatic Chlorinator and Chemical Feeders Water Flow SwitchRelief Valve Way Automatic Bypass Valve Wiring Pump Purge Delay OptionService Indicator Option Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsStarting the Filter System Pre-Start ChecklistTo Turn Off Gas To Pool Heater Operation Programming Mode Error Messages Displayed by Temperature ControllerHot Surface Ignition Control Module Diagnostic Status IndicationHot Surface Igniter and Ignition Control Module Ignition Module Lockout FunctionsIgnition and Control Timings Access to Internal Control PanelTABLE-N Water Chemistry TABLE-OPipe Size Requirements TABLE-QMinimum Pump Performance High Water Temperature Limit ControlCirculating Pump Heat ExchangerWater Circulating Pump Flue Gas Passageways Cleaning ProceduresAppliance Area Burner FlamesElectrical Burner Removal and CleaningHeat Exchanger Cleaning Combustion and Ventilation AirCombustion Air Fan Adjustment Adjusting Differential Air PressureFan Cleaning Set-Up ProcedureIgnition System Checkout Adjustment ProcedureServicing Hot Surface Igniter and Ignition Module Sequence of Operation Glossary Igniter WARM-UP and Proving Wiring BOX Connections Main Unit Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.