Lochinvar 497 - 2067 service manual Outdoor installation venting, Outdoor vent/air inlet location

Page 20

2 Venting

2. Outdoor installation venting

NOTICE

Before installing a venting system, follow

all venting clearances and requirements

 

 

found in the Venting, General Information

 

section, page 16.

 

Only install outdoor models outdoors

WARNING

and only use the vent caps supplied by

 

the appliance manufacturer. Personal

 

injury or product damage may result if

 

any other cap is used or if an outdoor

 

model is used indoors. Properly install all

 

covers, doors and jacket panels to ensure

 

proper operation and prevent a hazardous

 

condition.

Units are self-venting and can be used outdoors when installed with the optional outdoor caps. These caps mount directly to the unit and cover the flue outlet and combustion air inlet openings. No additional vent piping is required.

Combustion air supply must be free of contaminants (see Combustion and Ventilation Air, page 12). To prevent recirculation of the flue products into the combustion air inlet, follow all instructions in this section.

Outdoor vent/air inlet location

Keep venting areas free of obstructions. Keep area clean and free of combustible and flammable materials. Maintain a minimum clearance of 3'' (76mm) to combustible surfaces and 36" clearance to the rear of the unit for outdoor installations. To avoid a blocked air inlet or blocked flue condition, keep the air inlet, flue outlet and drain slot clear of snow, ice, leaves, debris, etc.

CAUTION

Do not install outdoor models directly on

the ground. You must install the outdoor

 

 

unit on a concrete, brick, block, or other

 

non-combustible pad.

 

 

Do not locate unit so that high winds

CAUTION

can deflect off of adjacent walls, buildings

 

 

or shrubbery causing

recirculation.

 

Recirculation of flue products may cause

 

operational problems, bad combustion or

 

damage to controls. Locate

unit at least

 

3 feet (0.91m) from any wall or vertical

 

surface to prevent wind conditions from

 

affecting performance.

 

Installation & Service Manual

NOTICE

Multiple outdoor unit installations require

48'' (1.22m) clearance between each vent

 

 

cap. Locate the outdoor cap at least 48''

 

(1.22m) below and 48'' (1.22m) horizontally

 

from any window, door, walkway or gravity

 

air intake.

 

Locate the unit at least 10 feet (3.05m) away

 

from any forced air inlet.

 

Locate the unit at least 3 feet (0.91m)

 

outside any overhang.

 

Clearances around outdoor installations can

 

change with time. Do not allow the growth

 

of trees, shrubs or other plants to obstruct

 

the proper operation of the outdoor vent

 

system.

 

A minimum of 3 feet must be maintained

CAUTION

at all times from outdoor air vent cap

 

surfaces to combustible construction and/or

 

materials.

 

Do not install in locations where rain from

CAUTION

building runoff drains will spill onto the

 

unit.

20

Image 20
Contents What to do if YOU Smell GAS Save this manual for future referenceContents Warranty Please read before proceedingSpecial instructions Checking equipmentSafety information Owner warningPrevention of freezing CodesCopper-fin How it works Copper-fin How it works Models 987 2067 Front View Models 987 2067 Rear View Ratings Copper-fin =B=R RatingCopper-fin Specifications Installation Determine unit locationLocating the unit Indoor clearances from combustible constructionOutdoor boiler installation Shut-down and drainingFreeze protection Pump operationFreeze Protection for a Heating Boiler System if required Combustion and Ventilation AirMinimum Recommended Combustion AIR Supply to Equipment Room Number3Combustion air filter Models 497 Combustion air filterOutside Combustion Air, No Ducts Outside Combustion Air, Using DuctsCombustion Air Options Exhaust Fans Combustion Air from an Interior SpaceVenting General informationVenting support Vertical vent termination clearances and locationFlue Pipe Sizes Model Flue Size Vent system optionsBarometric damper location Conventional negative draft venting Negative draftFlue outlet piping Common venting systemsMasonry chimney installation Inspection of a masonry chimneyOutdoor installation venting Outdoor vent/air inlet locationOutdoor vent kit Outdoor Vent Kits Model Pump Cover Without Pump CoverConnecting to gas supply Gas piping Gas connectionsGas pressure test Inlet GAS Pressure Natural ModelSuggested GAS Pipe Size for Single Unit Installations Gas connectionGas train and controls Fittings to Equivalent Straight PipeGAS Piping Size Chart Combination gas valvesVenting of combination gas valves Checking gas supply pressureGas manifold pressure adjustment 3Measuring gas supply pressure at combination gas valve4Measuring manifold gas pressure Nat. GasWater connections Boiler circulator requirements Pressure Drop ChartWater connections heating boilers only Run Cycle Output Minimum System Load Temp. Rise 8.33 60 Min Minimum boiler water temperaturesLow system water volume Low temperature return water systems System Temperature Rise ChartRadiant floor and snow melt heating systems LTV Valve Kits Model LTV Valve KITCommon Manifold Size Min Models 497 Number of Units GPMDiameter Common Manifold Size Min Models 987 Number of Units6Primary/secondary piping of multiple boilers 7Boiler with low temperature bypass 8Primary/secondary piping with buffer tank Installation with a chilled water system Typical heating boiler installationsBoiler flow rate General plumbing rulesTemperature / pressure gauge Boiler bypass requirementsFilling the system Water treatmentConnecting to electrical supply Electrical connectionsAMP Draw Data VACBurners Terminal strip connection optionsTemperature adjustment Locating the temperature controlTemperature control settings OJ1 OJ2Outdoor reset option Temperature control sensors Remote sensor for pump delayPlacement of sensors Boiler applicationRemote Wire Connection Wire Gauge Max. Allowable Length Hot surface ignition systemRemote mounting of a sensor Hot surface igniter and ignition control moduleDiagnostic Status Indication Ignition and control timingsOperation and diagnostic lights Sequence Constant IgnitionStage 2 on SixStartup OFFFreeze protection when used Check/control water chemistryFill and test water system Purge air from water systemCheck for gas leaks Check thermostat circuitsCheck vent and air piping Start the boilerDomestic water heaters Water velocity controlInitial set-up of maximum water flow Maximum Water Flow1Typical water heater piping with storage tank 2Single water heater piping with two storage tanks Common Manifold Size Min Models 497 Number of Units4Multiple water heater piping with multiple storage tanks Required temperature rise Pipe Sizing Chart 497 987Pipe size requirements Water chemistryPotable hot water temperature control settings Domestic water temperatureMinimum pump performance Heat exchangerLocation of cold water supply piping connections High water temperature limit control Optional relief valveThermal expansion Cathodic protectionMaintenance Combustion and ventilation air Adjustment procedure Models 497 Sequence of operation Servicing a hot surface igniter and ignition moduleIgnition system checkout OverviewHeat transfer process End of sequenceGlossary Pump Delay Electronic Thermostat Function Trial for Ignition Ignition Module FunctionIgniter Controlled by Ignition Module Hi-Lo Fire RelayDiagrams Ladder diagramDiagrams Connection diagram Connection diagram

497 - 2067 specifications

Lochinvar 497 - 2067 is a highly efficient and versatile condensing boiler that is designed to meet the diverse heating needs of residential and commercial applications. Known for its impressive performance and advanced technology, the Lochinvar 497 - 2067 has garnered a reputation as a reliable choice among heating professionals.

One of the standout features of the Lochinvar 497 - 2067 is its impressive thermal efficiency. The boiler boasts an efficiency rating of up to 95% AFUE (Annual Fuel Utilization Efficiency), allowing users to significantly reduce their energy costs while minimizing environmental impact. This efficiency is facilitated by its innovative condensing technology, which captures and reuses heat from exhaust gases for optimal performance.

The Lochinvar 497 - 2067 is equipped with a robust stainless steel heat exchanger designed to handle high temperatures and ensure long-lasting performance. The heat exchanger’s design maximizes heat transfer, while its corrosion-resistant properties guarantee durability over time. This contributes to the boiler's overall longevity and serviceability, reducing the need for frequent replacements.

Control is another critical feature of the Lochinvar 497 - 2067. The boiler comes with an advanced control system that enables easy management of system operations. Users can take advantage of features such as outdoor reset control, which adjusts the temperature of the boiler based on external weather conditions, enhancing system efficiency and comfort.

In terms of safety, the Lochinvar 497 - 2067 incorporates several cutting-edge safety features, including a flame detection system and multiple safety shut-off devices. These safeguards help to ensure the safe operation of the boiler, providing peace of mind to users and heating professionals alike.

Another important characteristic is the compact design of the Lochinvar 497 - 2067, which allows for flexible installation in various settings, including tight spaces. Its lightweight structure further simplifies the installation process, making it a practical choice for contractors.

In summary, the Lochinvar 497 - 2067 is an exceptional high-efficiency condensing boiler that combines advanced technology, durability, and ease of use. With its impressive thermal efficiency, superior heat exchanger design, advanced control systems, and enhanced safety measures, it stands out as a top choice for those seeking reliable heating solutions. This boiler not only meets but exceeds modern demands for energy efficiency and performance, solidifying its position in the market.