Lochinvar 497 - 2067 service manual Pressure Drop Chart, Water connections heating boilers only

Page 28

4 Water connections

Water connections (heating boilers only)

Inlet and outlet water connections on Models 497 - 747 have 2'' NPT and on Models 987 - 2067 the inlet and outlet connections are 2 1/2'' NPT.

CAUTION

Field installed reducing bushings must not

be used to reduce below the pipe diameters

 

of the models listed above.

Any reduction in pipe size may decrease flow resulting in high water temperatures, boiler noise, flashing to steam, and non- warrantable heat exchanger damage.

The boiler may be installed with a primary/secondary piping system provided to the boiler. It is important to guarantee that adequate flow is provided to properly dissipate heat from the boiler and also ensure that flow through the boiler does not exceed the maximum recommended flow rate of 55 GPM for Models 497 - 747 and 90 GPM for Models 987 - 2067 for a boiler equipped with a copper heat exchanger.

Installation & Service Manual

Circulator pump specifications

1.Maximum operating pressure for the pump must exceed system operating pressure.

2.Maximum water temperature should not exceed the nameplate rating.

3.Cast iron circulators may be used for closed loop systems.

4.A properly sized expansion tank must be installed near the boiler and on the suction side of the pump.

Circulator pump operation (heating boilers only)

The boiler pump must run when the boiler is firing. Separate supply circuits can be provided or the two circuits (pump and controls) can be combined for connection to one circuit, properly sized for both.

Pump delay operation

Boiler circulator requirements

This is a low mass, high efficiency hot water boiler which must have adequate flow for quiet, efficient operation. Pump selection is critical to achieve proper operation. A pump should be selected to achieve proper system design water temperature rise. Pipe diameter and length are critical to ensure proper flow through the boiler. A System Temperature Rise Chart (Table 4B on page 30) is provided to assist in proper pump selection. This table provides GPM and boiler head-loss at various temperature rises for each model based on Btu/hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing at full rate.

Example: The boiler inlet temperature is 160°F (71.1°C) and the boiler outlet temperature is 180°F (82.2°C). This means that there is a 20°F (11.1°C) temperature rise across the boiler. The boiler temperature rise is visible in the Operator Interface on the boiler’s front control panel.

A pump delay operation feature is provided. The boiler’s circulating pump will cycle on at each call for heat, before the burner fires. The pump will continue to operate while the burner is firing. The pump will run for a minimum 30 second period after the temperature set point is satisfied. This timing will remove any of the residual heat from the combustion chamber before turning the pump off. See the wiring diagram in Section 10 of this manual.

Figure 4-3_Heat exchanger pressure drop chart_ Models 497- 747

Pressure Drop Chart

Models 497 - 747

HEAD

12

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

FEETIN

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DROP

6

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

20

30

40

45

50

55

60

65

70

75

80

10

 

2

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

FLOW IN GALLONS PER MINUTE

Figure 4-4_Heat exchanger pressure drop chart_ Models 987 - 2067

MODELS 987 - 2067

28

Image 28
Contents What to do if YOU Smell GAS Save this manual for future referenceContents Warranty Please read before proceedingSpecial instructions Checking equipmentSafety information Owner warningPrevention of freezing CodesCopper-fin How it works Copper-fin How it works Models 987 2067 Front View Models 987 2067 Rear View Ratings Copper-fin =B=R RatingCopper-fin Specifications Installation Determine unit locationLocating the unit Indoor clearances from combustible constructionOutdoor boiler installation Shut-down and drainingFreeze protection Pump operationFreeze Protection for a Heating Boiler System if required Combustion and Ventilation AirMinimum Recommended Combustion AIR Supply to Equipment Room Number3Combustion air filter Models 497 Combustion air filterCombustion Air Options Outside Combustion Air, Using DuctsOutside Combustion Air, No Ducts Exhaust Fans Combustion Air from an Interior SpaceVenting General informationVenting support Vertical vent termination clearances and locationBarometric damper location Vent system optionsFlue Pipe Sizes Model Flue Size Conventional negative draft venting Negative draftFlue outlet piping Common venting systemsMasonry chimney installation Inspection of a masonry chimneyOutdoor installation venting Outdoor vent/air inlet locationOutdoor vent kit Outdoor Vent Kits Model Pump Cover Without Pump CoverConnecting to gas supply Gas piping Gas connectionsGas pressure test Inlet GAS Pressure Natural ModelSuggested GAS Pipe Size for Single Unit Installations Gas connectionGas train and controls Fittings to Equivalent Straight PipeGAS Piping Size Chart Combination gas valvesVenting of combination gas valves Checking gas supply pressureGas manifold pressure adjustment 3Measuring gas supply pressure at combination gas valve4Measuring manifold gas pressure Nat. GasWater connections Water connections heating boilers only Pressure Drop ChartBoiler circulator requirements Low system water volume Minimum boiler water temperaturesRun Cycle Output Minimum System Load Temp. Rise 8.33 60 Min Low temperature return water systems System Temperature Rise ChartRadiant floor and snow melt heating systems LTV Valve Kits Model LTV Valve KITCommon Manifold Size Min Models 497 Number of Units GPMDiameter Common Manifold Size Min Models 987 Number of Units6Primary/secondary piping of multiple boilers 7Boiler with low temperature bypass 8Primary/secondary piping with buffer tank Installation with a chilled water system Typical heating boiler installationsBoiler flow rate General plumbing rulesTemperature / pressure gauge Boiler bypass requirementsFilling the system Water treatmentConnecting to electrical supply Electrical connectionsAMP Draw Data VACBurners Terminal strip connection optionsTemperature adjustment Locating the temperature controlTemperature control settings OJ1 OJ2Outdoor reset option Temperature control sensors Remote sensor for pump delayPlacement of sensors Boiler applicationRemote Wire Connection Wire Gauge Max. Allowable Length Hot surface ignition systemRemote mounting of a sensor Hot surface igniter and ignition control moduleDiagnostic Status Indication Ignition and control timingsOperation and diagnostic lights Sequence Constant IgnitionStage 2 on SixStartup OFFFreeze protection when used Check/control water chemistryFill and test water system Purge air from water systemCheck for gas leaks Check thermostat circuitsCheck vent and air piping Start the boilerDomestic water heaters Water velocity controlInitial set-up of maximum water flow Maximum Water Flow1Typical water heater piping with storage tank 2Single water heater piping with two storage tanks Common Manifold Size Min Models 497 Number of Units4Multiple water heater piping with multiple storage tanks Required temperature rise Pipe Sizing Chart 497 987Pipe size requirements Water chemistryPotable hot water temperature control settings Domestic water temperatureMinimum pump performance Heat exchangerLocation of cold water supply piping connections High water temperature limit control Optional relief valveThermal expansion Cathodic protectionMaintenance Combustion and ventilation air Adjustment procedure Models 497 Sequence of operation Servicing a hot surface igniter and ignition moduleIgnition system checkout OverviewHeat transfer process End of sequenceGlossary Pump Delay Electronic Thermostat Function Trial for Ignition Ignition Module FunctionIgniter Controlled by Ignition Module Hi-Lo Fire RelayDiagrams Ladder diagramDiagrams Connection diagram Connection diagram

497 - 2067 specifications

Lochinvar 497 - 2067 is a highly efficient and versatile condensing boiler that is designed to meet the diverse heating needs of residential and commercial applications. Known for its impressive performance and advanced technology, the Lochinvar 497 - 2067 has garnered a reputation as a reliable choice among heating professionals.

One of the standout features of the Lochinvar 497 - 2067 is its impressive thermal efficiency. The boiler boasts an efficiency rating of up to 95% AFUE (Annual Fuel Utilization Efficiency), allowing users to significantly reduce their energy costs while minimizing environmental impact. This efficiency is facilitated by its innovative condensing technology, which captures and reuses heat from exhaust gases for optimal performance.

The Lochinvar 497 - 2067 is equipped with a robust stainless steel heat exchanger designed to handle high temperatures and ensure long-lasting performance. The heat exchanger’s design maximizes heat transfer, while its corrosion-resistant properties guarantee durability over time. This contributes to the boiler's overall longevity and serviceability, reducing the need for frequent replacements.

Control is another critical feature of the Lochinvar 497 - 2067. The boiler comes with an advanced control system that enables easy management of system operations. Users can take advantage of features such as outdoor reset control, which adjusts the temperature of the boiler based on external weather conditions, enhancing system efficiency and comfort.

In terms of safety, the Lochinvar 497 - 2067 incorporates several cutting-edge safety features, including a flame detection system and multiple safety shut-off devices. These safeguards help to ensure the safe operation of the boiler, providing peace of mind to users and heating professionals alike.

Another important characteristic is the compact design of the Lochinvar 497 - 2067, which allows for flexible installation in various settings, including tight spaces. Its lightweight structure further simplifies the installation process, making it a practical choice for contractors.

In summary, the Lochinvar 497 - 2067 is an exceptional high-efficiency condensing boiler that combines advanced technology, durability, and ease of use. With its impressive thermal efficiency, superior heat exchanger design, advanced control systems, and enhanced safety measures, it stands out as a top choice for those seeking reliable heating solutions. This boiler not only meets but exceeds modern demands for energy efficiency and performance, solidifying its position in the market.