Lochinvar SNR150-100, SNA500-125 Minimum Recommended Combustion AIR Supply to Equipment Room

Page 13

TM

Installation & Service Manual

1Determine water heater location (continued)

TABLE - 1B

MINIMUM RECOMMENDED COMBUSTION

AIR SUPPLY TO EQUIPMENT ROOM

 

 

FIG. 1-3

FIG. 1-4

FIG. 1-5

FIG. 1-6

 

 

 

 

 

 

 

 

 

 

 

 

Model

*Outside Air from

*Outside Air from

**Inside Air from

 

 

 

2 Openings Directly from

2 Ducts Delivered from

2 Ducts Delivered from Interior

*Outside Air from

 

 

Number

 

 

Outdoors

Outdoors

Space

1 Opening Directly

 

 

 

 

 

 

Top

Bottom

Top

Bottom

Top

Bottom

from Outdoors, in2

 

 

 

Opening, in2

Opening, in2

Opening, in2

Opening, in2

Opening, in2

Opening, in2

 

 

 

SNR150-100

38

38

75

75

150

150

50

 

 

(246 cm2)

(246 cm2)

(484 cm2)

(484 cm2)

(968 cm2)

(968 cm2)

(323 cm2)

 

 

 

 

 

SNR200-100

50

50

100

100

200

200

67

 

 

(323 cm2)

(323 cm2)

(646 cm2)

(646 cm2)

(1,291 cm2)

(1,291 cm2)

(433 cm2)

 

 

 

 

 

SNA285-125

72

72

143

143

285

285

95

 

 

(465 cm2)

(465 cm2)

(923 cm2)

(923 cm2)

(1,839 cm2)

(1,839 cm2)

(613 cm2)

 

 

 

 

 

SNA400-125

100

100

200

200

400

400

134

 

 

(646 cm2)

(646 cm2)

(1,291 cm2)

(1,291 cm2)

(2,581 cm2)

(2,581 cm2)

(865 cm2)

 

 

 

 

 

SNA500-125

125

125

250

250

500

500

167

 

 

(807 cm2)

(807 cm2)

(1,613 cm2)

(1,613 cm2)

(3,226 cm2)

(3,226 cm2)

(1,078 cm2)

 

 

 

 

*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the water heater only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.

**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.

*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.

*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).

Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN B149.1. Check all local code requirements for combustion air.

All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30cm) of the ceiling and one must be within 12" (30cm) of the floor of the equipment room. Each opening must have net free area as specified in the chart above (Table 1B). Single openings shall commence within 12" (30cm) of the ceiling.

￿Under no circumstances should the CAUTION equipment room ever be under negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may

take away air from the unit.

The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system.

The result is improper combustion and a non-warrantable, premature appliance failure.

EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the equipment room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.

13

Image 13
Contents What to do if YOU Smell GAS Installation & Service ManualContents Hazard definitions Please read before proceedingBlower Shield How it worksModels SNR150-100 -- SNA285-125 Model SNA500-125 Model SNA400-125CSA RatingsCloset and alcove installations Installation must comply withDetermine water heater location Before locating the water heater, check1Closet Installation Minimum Required Clearances Remove water heater from wood pallet Flooring and foundationPrevent combustion air contamination Do not install the Shield water heater into 3Combustion Air Direct from Outside Minimum Recommended Combustion AIR Supply to Equipment Room Direct venting options General ventingCanada Venting and combustion airVent pipe and fittings Air inlet pipe materials Air intake/vent connectionsRemoving from existing vent Vent LengthVent and air piping Sidewall direct venting If using the alternate sidewall terminationVent/air termination sidewall Vent Size2Clearance to Gravity Air Inlets Prepare wall penetrations Alternate Field Supplied Option Prepare wall penetrationsTermination and fittings 5AMultiple Vent Terminations must also comply with -1A Multiple vent/air terminationsSidewall termination optional concentric vent Sidewall termination installationDescription and usage 9Concentric Vent Dimensional Drawing Multiventing sidewall terminations 12Concentric Vent Sidewall AttachmentVent/air termination vertical Vertical direct venting2Vertical Terminations with Multiple Water Heaters Prepare roof penetrationsVertical termination optional concentric vent Vertical termination installationMultiventing vertical terminations 6Concentric Vent Roof Installation1Vertical Direct Venting w/Room Air Conventional and sidewall ventingSystem water piping methods System pipingScalding General piping informationWater chemistry Piping componentsDelta T Single Unit 3Multiple Units Water Tank Supply Gas connections Connecting gas supply pipingPropane gas Natural gasCheck inlet gas supply Natural Gas Pipe Capacity ChartLength of Pipe in Straight Feet for 1/2 PSI Gas pressure Gas valve replacementField wiring 3Low Voltage Field Wiring Connections Inputs Condensate drain Condensate disposalCheck for gas leaks Inspect/fill condensate system Start-upFinal checks before starting the water heater If water heater does not start correctly Start the water heaterCheck system and water heater Check flame and combustion2Operating Instructions Models SNR150-100 -- SNA285-125 3Operating Instructions Models SNA400-125 -- SNA500-125 Protection features Temperature controlOperating information GeneralAdjustable control parameters Water heater temperature regulationSaving parameters HTR Ignition Sequence of operation1Control Panel Shield control moduleStatus Display Screens Status display screensStatus Display Screens cont’d Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check water heater relief valveCheck all water heater wiring Check ignition ground wiring Check burner flameCheck control settings Check flame signalHandling ceramic fiber materials Cleaning heat exchangerOiled bearing circulators Niosh stated First AidBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner Operation No DisplayUnit Does Not Modulate Above 50%Temperature F Resistance Ω Checking temperature sensorsTroubleshooting Sequence FlameNo Flame Ign Running No FlameGV/Relay FailHigh Limit Manual ResetFan Low Fan Speed LowFan High SwitchFan Speed High Sensor OpenProgr ParametersWatch Dog Error Service BlkLow 24 VAC Write EEPromGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureModels SNR150-100 -- SNA285-125 Gas valve adjustment procedureModel SNA400-125 Model SNA500-125120 VAC DiagramsLOW Voltage

SNA400-125, SNR150-100, SNA285-125, SNR200-100, SNA500-125 specifications

Lochinvar has established itself as a leader in the realm of high-efficiency heating solutions, and its line of condensing boilers, including the SNA500-125, SNR200-100, SNA400-125, SNA285-125, and SNR150-100, exemplifies the brand’s commitment to innovation, efficiency, and reliability.

The SNA500-125 model stands out with its impressive heating capacity, designed for larger commercial applications. Featuring advanced modulating burners, it can precisely adjust its output based on real-time demand, significantly enhancing energy efficiency. The stainless steel heat exchanger ensures robust durability and improved thermal performance, while the integrated controls offer advanced diagnostic capabilities and user-friendly operation.

Next in the lineup, the SNR200-100 serves as a versatile option for mid-sized applications. Its compact design allows for flexible installation, making it a valuable choice for facilities with limited space. The boiler incorporates a high-efficiency combustion system that maximizes fuel utilization, while its low NOx emissions technology aligns with environmental standards, reducing the carbon footprint of users.

The SNA400-125 delivers a robust solution for diverse heating needs, equipped with state-of-the-art modulation technology that not only optimizes efficiency but also offers quiet operation – a crucial feature for facilities where noise reduction is paramount. This model also includes built-in redundancy options, enhancing reliability during peak operational periods.

The SNA285-125 provides a balance of performance and efficiency for smaller commercial settings. Its innovative control system offers precise temperature management and easy integration with existing systems. Energy Star certified, this model is not only cost-effective but supports sustainability efforts in various industries.

Lastly, the SNR150-100 is ideally suited for light commercial applications, featuring a compact footprint and excellent heat transfer capabilities. The user-friendly interface and robust safety features make it an excellent choice for operators prioritizing both ease of use and reliability.

All these models incorporate Lochinvar's commitment to superior design and advanced technologies, setting a benchmark in the high-efficiency heating market. With a focus on long-term performance and compliance with modern environmental standards, Lochinvar continues to deliver top-tier solutions tailored to meet diverse customer needs. Whether for large-scale operations or smaller settings, these boilers represent a significant advancement in commercial heating technology.