Lochinvar SNR150-100 Sidewall direct venting, Vent/air termination sidewall, Vent Size

Page 18

3Sidewall direct venting

Vent/air termination – sidewall

 

TM

Installation & Service Manual

 

 

 

 

 

 

f.

Do not terminate above any door or window.

 

Condensate can freeze, causing ice formations.

g.

Locate or guard vent to prevent condensate damage

￿WARNING

￿WARNING

Follow instructions below when determining vent location to avoid possibility of severe personal injury, death, or substantial property damage.

A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.

to exterior finishes.

Figure 3-1ASidewall Termination of Air and Vent

 

TO BOILER

 

INTAKE AIR

 

CONNECTION

FROM BOILER

 

VENT PIPE

 

CONNECTION

 

POSSIBLE ORIENTATIONS

12"

MIN

 

TO

 

OVER-

 

HANG

 

VENT / AIR

 

TERMINATION

￿WARNING

NOTICE

Do not connect any other appliance to the vent pipe or multiple water heaters to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.

Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

 

 

12"

 

 

MIN

 

GRADE OR

 

 

SNOW LINE

 

Table 3A Sidewall Vent Kits

 

Model

Kit Number

Vent Size

SNR150-100 -- SNR200-100 KIT30045

3 inch vent

SNA285-125 -- SNA500-125

KIT30046

4 inch vent

Determine location

Locate the vent/air terminations using the following guidelines:

1.The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 17 of this manual.

2.You must consider the surroundings when terminating the vent and air:

a.Position the vent termination where vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable.

b.The flue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.

c.Prevailing winds could cause freezing of condensate and water/ice buildup where flue products impinge on building surfaces or plants.

d.Avoid possibility of accidental contact of flue products with people or pets.

e.Do not locate the terminations where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.

￿ WARNING Sidewall vent and air inlet terminations must terminate in the same pressure

zone.

18

If using the alternate sidewall termination:

3.The air piping must terminate in a down-turned elbow as shown in FIG. 3-1B. This arrangement avoids recirculation of flue products into the combustion air stream.

4.The vent piping must terminate in an elbow pointed outward or away from the air inlet, as shown in FIG. 3-1B.

￿WARNING Do not exceed the maximum lengths of the outside vent piping shown in FIG. 3-1B.

Excessive length exposed to the outside could cause freezing of condensate in the vent pipe, resulting in potential water heater shutdown.

Figure 3-1BAlternate Sidewall Termination of Air and Vent w/Field Supplied Fittings

Image 18
Contents Installation & Service Manual What to do if YOU Smell GASContents Please read before proceeding Hazard definitionsShield How it works BlowerModels SNR150-100 -- SNA285-125 Model SNA400-125 Model SNA500-125Ratings CSADetermine water heater location Installation must comply withCloset and alcove installations Before locating the water heater, check1Closet Installation Minimum Required Clearances Flooring and foundation Remove water heater from wood palletPrevent combustion air contamination Do not install the Shield water heater into 3Combustion Air Direct from Outside Minimum Recommended Combustion AIR Supply to Equipment Room General venting Direct venting optionsVenting and combustion air CanadaVent pipe and fittings Air intake/vent connections Air inlet pipe materialsVent Length Removing from existing ventVent and air piping Vent/air termination sidewall If using the alternate sidewall terminationSidewall direct venting Vent Size2Clearance to Gravity Air Inlets Prepare wall penetrations Prepare wall penetrations Alternate Field Supplied OptionTermination and fittings Multiple vent/air terminations 5AMultiple Vent Terminations must also comply with -1ASidewall termination installation Sidewall termination optional concentric ventDescription and usage 9Concentric Vent Dimensional Drawing 12Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations 2Vertical Terminations with Multiple Water HeatersVertical termination installation Vertical termination optional concentric vent6Concentric Vent Roof Installation Multiventing vertical terminationsConventional and sidewall venting 1Vertical Direct Venting w/Room AirScalding System pipingSystem water piping methods General piping informationPiping components Water chemistryDelta T Single Unit 3Multiple Units Water Tank Supply Connecting gas supply piping Gas connectionsNatural gas Propane gasNatural Gas Pipe Capacity Chart Check inlet gas supplyLength of Pipe in Straight Feet for 1/2 PSI Gas valve replacement Gas pressureField wiring 3Low Voltage Field Wiring Connections Inputs Condensate disposal Condensate drainStart-up Check for gas leaks Inspect/fill condensate systemFinal checks before starting the water heater Check system and water heater Start the water heaterIf water heater does not start correctly Check flame and combustion2Operating Instructions Models SNR150-100 -- SNA285-125 3Operating Instructions Models SNA400-125 -- SNA500-125 Operating information Temperature controlProtection features GeneralWater heater temperature regulation Adjustable control parametersSaving parameters Sequence of operation HTR IgnitionShield control module 1Control PanelStatus display screens Status Display ScreensStatus Display Screens cont’d Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check expansion tank Flue vent system and air pipingCheck water system Check water heater relief valveCheck control settings Check ignition ground wiring Check burner flameCheck all water heater wiring Check flame signalOiled bearing circulators Cleaning heat exchangerHandling ceramic fiber materials Niosh stated First AidCheck control module fuses TroubleshootingBefore troubleshooting Check the followingUnit Does Not Modulate No DisplayNo Burner Operation Above 50%Checking temperature sensors Temperature F Resistance ΩTroubleshooting Flame SequenceNo Flame Ign GV/Relay No FlameRunning FailFan Low Manual ResetHigh Limit Fan Speed LowFan Speed High SwitchFan High Sensor OpenParameters ProgrLow 24 VAC Service BlkWatch Dog Error Write EEPromOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModel SNA400-125 Gas valve adjustment procedureModels SNR150-100 -- SNA285-125 Model SNA500-125Diagrams 120 VACLOW Voltage

SNA400-125, SNR150-100, SNA285-125, SNR200-100, SNA500-125 specifications

Lochinvar has established itself as a leader in the realm of high-efficiency heating solutions, and its line of condensing boilers, including the SNA500-125, SNR200-100, SNA400-125, SNA285-125, and SNR150-100, exemplifies the brand’s commitment to innovation, efficiency, and reliability.

The SNA500-125 model stands out with its impressive heating capacity, designed for larger commercial applications. Featuring advanced modulating burners, it can precisely adjust its output based on real-time demand, significantly enhancing energy efficiency. The stainless steel heat exchanger ensures robust durability and improved thermal performance, while the integrated controls offer advanced diagnostic capabilities and user-friendly operation.

Next in the lineup, the SNR200-100 serves as a versatile option for mid-sized applications. Its compact design allows for flexible installation, making it a valuable choice for facilities with limited space. The boiler incorporates a high-efficiency combustion system that maximizes fuel utilization, while its low NOx emissions technology aligns with environmental standards, reducing the carbon footprint of users.

The SNA400-125 delivers a robust solution for diverse heating needs, equipped with state-of-the-art modulation technology that not only optimizes efficiency but also offers quiet operation – a crucial feature for facilities where noise reduction is paramount. This model also includes built-in redundancy options, enhancing reliability during peak operational periods.

The SNA285-125 provides a balance of performance and efficiency for smaller commercial settings. Its innovative control system offers precise temperature management and easy integration with existing systems. Energy Star certified, this model is not only cost-effective but supports sustainability efforts in various industries.

Lastly, the SNR150-100 is ideally suited for light commercial applications, featuring a compact footprint and excellent heat transfer capabilities. The user-friendly interface and robust safety features make it an excellent choice for operators prioritizing both ease of use and reliability.

All these models incorporate Lochinvar's commitment to superior design and advanced technologies, setting a benchmark in the high-efficiency heating market. With a focus on long-term performance and compliance with modern environmental standards, Lochinvar continues to deliver top-tier solutions tailored to meet diverse customer needs. Whether for large-scale operations or smaller settings, these boilers represent a significant advancement in commercial heating technology.