2General venting

Air intake/vent connections

1.Combustion Air Intake Connector (FIG.’s 2-5 and 2-6) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.

2.Vent Connector (FIG.’s 2-5 and 2-6) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.

Figure 2-5Near Water Heater Venting Models SNR150-100 - SNR200-100

Figure 2-6Near Water Heater Venting Models SNA285-125 - SNA500-125

AIR

VENT

4" CPVC PIPE INSTALLED IN THE WATER HEATER MUST BE USED FOR VENT CONNECTION

AIR

VENT

3" CPVC PIPE INSTALLED IN THE WATER HEATER MUST BE USED FOR VENT CONNECTION

NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN CLOSET AND ALCOVE INSTALLATIONS.

NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN CLOSET AND ALCOVE INSTALLATIONS.

Air inlet pipe materials:

The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list:

PVC, CPVC or ABS

Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet)

Galvanized steel vent pipe with joints and seams sealed as specified in this section.

Type “B” double-wall vent with joints and seams sealed as specified in this section.

*Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the appliance and the plastic air inlet pipe.

The Shield water heater uses model specific combustion air intake and vent piping sizes as detailed in Table 2B below.

Table 2B Air Intake/Vent Piping Sizes

Model

Air Intake

Vent

 

 

 

SNR150-100 -- SNR200-100

3 inches

3 inches

 

 

 

SNA285-125 -- SNA500-125

4 inches

4 inches

 

 

 

NOTICE

Increasing or decreasing combustion air or vent piping is not authorized.

Models SNA400-125 and SNA500-125 will de-rate 1.75% per 25 feet of vent when installed as direct vent or 0.75% per 25 feet of vent when drawing combustion air from the room.

Models SNR150-100 through SNA285-125 will de-rate up to 1% per 25 feet of vent pipe when installed as direct vent, but will not de-rate when drawing combustion air from the room.

16

Image 16
Contents Installation & Service Manual What to do if YOU Smell GASContents Please read before proceeding Hazard definitionsShield How it works BlowerModels SNR150-100 -- SNA285-125 Model SNA400-125 Model SNA500-125Ratings CSAInstallation must comply with Closet and alcove installationsDetermine water heater location Before locating the water heater, check1Closet Installation Minimum Required Clearances Remove water heater from wood pallet Flooring and foundationPrevent combustion air contamination Do not install the Shield water heater into 3Combustion Air Direct from Outside Minimum Recommended Combustion AIR Supply to Equipment Room General venting Direct venting optionsCanada Venting and combustion airVent pipe and fittings Air intake/vent connections Air inlet pipe materialsRemoving from existing vent Vent LengthVent and air piping If using the alternate sidewall termination Sidewall direct ventingVent/air termination sidewall Vent Size2Clearance to Gravity Air Inlets Prepare wall penetrations Alternate Field Supplied Option Prepare wall penetrationsTermination and fittings Multiple vent/air terminations 5AMultiple Vent Terminations must also comply with -1ASidewall termination optional concentric vent Sidewall termination installationDescription and usage 9Concentric Vent Dimensional Drawing 12Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations 2Vertical Terminations with Multiple Water HeatersVertical termination installation Vertical termination optional concentric vent6Concentric Vent Roof Installation Multiventing vertical terminationsConventional and sidewall venting 1Vertical Direct Venting w/Room AirSystem piping System water piping methodsScalding General piping informationWater chemistry Piping componentsDelta T Single Unit 3Multiple Units Water Tank Supply Connecting gas supply piping Gas connectionsNatural gas Propane gasCheck inlet gas supply Natural Gas Pipe Capacity ChartLength of Pipe in Straight Feet for 1/2 PSI Gas valve replacement Gas pressureField wiring 3Low Voltage Field Wiring Connections Inputs Condensate disposal Condensate drainCheck for gas leaks Inspect/fill condensate system Start-upFinal checks before starting the water heater Start the water heater If water heater does not start correctlyCheck system and water heater Check flame and combustion2Operating Instructions Models SNR150-100 -- SNA285-125 3Operating Instructions Models SNA400-125 -- SNA500-125 Temperature control Protection featuresOperating information GeneralAdjustable control parameters Water heater temperature regulationSaving parameters Sequence of operation HTR IgnitionShield control module 1Control PanelStatus display screens Status Display ScreensStatus Display Screens cont’d Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check water heater relief valveCheck ignition ground wiring Check burner flame Check all water heater wiringCheck control settings Check flame signalCleaning heat exchanger Handling ceramic fiber materialsOiled bearing circulators Niosh stated First AidTroubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No Burner OperationUnit Does Not Modulate Above 50%Checking temperature sensors Temperature F Resistance ΩTroubleshooting Sequence FlameNo Flame Ign No Flame RunningGV/Relay FailManual Reset High LimitFan Low Fan Speed LowSwitch Fan HighFan Speed High Sensor OpenParameters ProgrService Blk Watch Dog ErrorLow 24 VAC Write EEPromCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureGas valve adjustment procedure Models SNR150-100 -- SNA285-125Model SNA400-125 Model SNA500-125Diagrams 120 VACLOW Voltage

SNA400-125, SNR150-100, SNA285-125, SNR200-100, SNA500-125 specifications

Lochinvar has established itself as a leader in the realm of high-efficiency heating solutions, and its line of condensing boilers, including the SNA500-125, SNR200-100, SNA400-125, SNA285-125, and SNR150-100, exemplifies the brand’s commitment to innovation, efficiency, and reliability.

The SNA500-125 model stands out with its impressive heating capacity, designed for larger commercial applications. Featuring advanced modulating burners, it can precisely adjust its output based on real-time demand, significantly enhancing energy efficiency. The stainless steel heat exchanger ensures robust durability and improved thermal performance, while the integrated controls offer advanced diagnostic capabilities and user-friendly operation.

Next in the lineup, the SNR200-100 serves as a versatile option for mid-sized applications. Its compact design allows for flexible installation, making it a valuable choice for facilities with limited space. The boiler incorporates a high-efficiency combustion system that maximizes fuel utilization, while its low NOx emissions technology aligns with environmental standards, reducing the carbon footprint of users.

The SNA400-125 delivers a robust solution for diverse heating needs, equipped with state-of-the-art modulation technology that not only optimizes efficiency but also offers quiet operation – a crucial feature for facilities where noise reduction is paramount. This model also includes built-in redundancy options, enhancing reliability during peak operational periods.

The SNA285-125 provides a balance of performance and efficiency for smaller commercial settings. Its innovative control system offers precise temperature management and easy integration with existing systems. Energy Star certified, this model is not only cost-effective but supports sustainability efforts in various industries.

Lastly, the SNR150-100 is ideally suited for light commercial applications, featuring a compact footprint and excellent heat transfer capabilities. The user-friendly interface and robust safety features make it an excellent choice for operators prioritizing both ease of use and reliability.

All these models incorporate Lochinvar's commitment to superior design and advanced technologies, setting a benchmark in the high-efficiency heating market. With a focus on long-term performance and compliance with modern environmental standards, Lochinvar continues to deliver top-tier solutions tailored to meet diverse customer needs. Whether for large-scale operations or smaller settings, these boilers represent a significant advancement in commercial heating technology.