Lochinvar 151 operation manual Air inlet pipe materials, Stainless steel vent

Page 20

3 General venting

Figure 3-11Near Water Heater PVC/CPVC Venting Models 701 - 801

VENT

AIR

6” COUPLING (FIELD SUPPLIED)

6” CPVC

STARTER

PIECE

(FACTORY SUPPLIED)

THE 6” STAINLESS STEEL ADAPTER SUPPLIED

WITH THE BOILER MUST BE USED FOR VENT

CONNECTION TO PVC/CPVC. THE 6” CPVC

STARTER PIECE MUST BE USED FOR PVC ONLY.

Air inlet pipe materials:

The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list:

PVC, CPVC or ABS

Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet)

Galvanized steel vent pipe with joints and seams sealed as specified in this section.

Type “B” double-wall vent with joints and seams sealed as specified in this section.

AL29-4C, stainless steel material to be sealed to specification of its manufacturer.

Installation & Operation Manual

c.Secure all joints with a minimum of three sheet metal screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.

d.Ensure that the air inlet pipes are properly supported.

The PVC, CPVC, or ABS air inlet pipe should be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used. The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe should use a silicone sealant to ensure a proper seal at the appliance connection and the air inlet cap connection. Dryer vent or flex duct should use a screw type clamp to seal the vent to the appliance air inlet and the air inlet cap. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.

When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.

￿ DANGER

Failure to properly seal all joints and seams

as required in the air inlet piping may result

 

 

in flue gas recirculation, spillage of flue

 

products and carbon monoxide emissions

 

causing severe personal injury or death.

Stainless steel vent

This product has been approved for use with stainless steel using the manufacturers listed in Table 3A.

*Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the appliance and the plastic air inlet pipe.

￿WARNING

Use only the materials, vent systems, and terminations listed in Table 3B. DO NOT mix vent systems of different types

￿WARNING

Using vent or air intake materials other than those specified, failure to properly seal all seams and joints or failure to follow vent pipe manufacturer’s instructions can result in personal injury, death or property damage. Mixing of venting materials will void the warranty and certification of the appliance.

or manufacturers, unless listed in this manual. Failure to comply could result in severe personal injury, death, or substantial property damage.

NOTICE

Installations must comply with applicable

national, state, and local codes. Stainless

 

steel vent systems

must

be

listed as a

 

UL-1738 approved

system

for

the United

NOTICE

The use of double-wall vent or insulated

material for the combustion air inlet pipe is

 

recommended in cold climates to prevent

 

the condensation of airborne moisture in

 

the incoming combustion air.

Sealing of Type “B” double-wall vent material or galvanized vent pipe material used for air inlet piping on a sidewall or vertical rooftop Combustion Air Supply System:

a.Seal all joints and seams of the air inlet pipe using either Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant such as those manufactured by Dow Corning or General Electric.

b.Do not install seams of vent pipe on the bottom of horizontal runs.

 

States and a ULC-S636 approved system for

 

Canada.

 

Installation of a stainless steel vent system

NOTICE

should adhere to the stainless steel vent

 

manufacturer’s installation instructions

 

supplied with the vent system.

 

The installer must use a specific vent starter

NOTICE

adapter at the flue collar connection,

 

supplied by the vent manufacturer to adapt

 

to its vent system. See Table 3B for approved

 

vent adapters. Discard CPVC starter piece.

20

Image 20
Contents Installation&OperationManual Models 151 What to do if YOU Smell GASContents When servicing the water heater Please read before proceedingArmor Water Heater How it works Stainless steel heat exchangerModels 151 Models 400 Models 601Ratings CSAInstallation must comply with Closet and alcove installationsDetermine water heater location Before locating the water heater, check1Closet Installation Minimum Required Clearances Residential garage installation Provide air openings to roomVent and air piping Flooring and foundationProducts to avoid Areas likely to have contaminantsDetermine water heater location Prepare water heater Gas conversionsRemove water heater from wood pallet Models 1513Installing Propane Orifice Model ModelModels 601 Leveling the water heaterGeneral venting Direct venting options Sidewall VentDirect venting options Vertical Vent Direct venting options Vertical Vent, Sidewall AirInstall vent and combustion air piping Requirements for installation in CanadaInstalling vent or air piping PVC/CPVC Vent piping materialsPVC/CPVC Air intake/vent connections Vent Pipe, and FittingsAir inlet pipe materials Stainless steel ventStainlesssteelairintake/ventconnections FlueFlue Intake Air Adapter Termination Model Kit NumberVent and air system Removing from existing ventModel Air Intake Vent Optional room air Vent, air piping and terminationModel Kit Number Description Air contaminationIf using the alternate sidewall termination Sidewall direct ventingVent/air termination sidewall Determine location3AClearance to Gravity Air Inlets Prepare wall penetrations Seal all wall cavitiesTermination and fittings Prepare wall penetrations Alternate Field Supplied OptionMultiple vent/air terminations Description and usage Sidewall termination installationSidewall termination optional concentric vent Models 151 11 Concentric 13Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations Multiple vent/air terminationsVertical termination installation Vertical termination optional concentric vent Models 151Multiventing vertical terminations Minimum Combustion AIR TypicalAlternate vertical concentric venting Concentric Venting ArrangementExisting vent as a chase 10Existing Vent as a ChaseFlow switch and relief valve installation Flow switch adjustmentSystem piping System water piping methodsWater chemistry ScaldingPiping components 4Single Heater Single Tank 2 Temperature Cold Water Supply Cold Water Supply Number of Units Model 8Double Heater Double Tank Connecting gas supply piping Gas connectionsNatural gas Propane gasLength of Pipe in Straight Feet for 1/2 PSI Single Unit Natural Gas Pipe Capacity ChartCheck inlet gas supply Gas valve replacement Gas pressureField wiring Installation must comply withLine voltage connections Low voltage connectionsTank thermostat Low gas pressure switch Louver proving switchHigh gas pressure switch Flow switchRuntime contacts Alarm contactsWiring of the cascade 3Low Voltage Field Wiring Connections Condensate disposal Condensate drainStart-up Check for gas leaks Inspect/fill condensate systemChlorine concentration less than 200 ppm Inspect/check condensate lines and fittingsFinal checks before starting the water heater Start the water heaterIf water heater does not start correctly Check system and water heaterFor Your Safety Read Before Operating 3Operating Instructions Models 400 Set tank set point temperature Verify WHR circulator modeSet water heater operation Natural Gas PropaneConfiguration of the cascade Set clockOperating information GeneralWater heater temperature regulation Installer CascadeSequence of the cascade UserSequence of operation Operation DisplayArmor water heater control module 1Control PanelWater heater Information Dial Function Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check ignition ground wiring Check all water heater wiringCheck control settings Check water systemCheck flame signal Cleaning heat exchangerPerform start-up and checks Check burner flameModel Kit Part Component Number Description Check Delta TOiled bearing circulators Diagrams PC Interface2Wiring Diagram Page Page AWII-I-O Rev C
Related manuals
Manual 16 pages 16.89 Kb

151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.