Lochinvar 151 Determine water heater location, Installation must comply with, Provide clearances

Page 8

Installation & Operation Manual

1 Determine water heater location

Installation must comply with:

Local, state, provincial, and national codes, laws, regulations, and ordinances.

National Fuel Gas Code, ANSI Z223.1 – latest edition.

National Electrical Code.

For Canada only: B149.1 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.

NOTICE

The Armor water heater gas manifold

and controls met safe lighting and other

 

 

performance under tests specified in ANSI

￿WARNING

This appliance requires a special venting system. If using PVC the vent connection to the appliance must be made with the starter CPVC pipe section provided with the appliance. The field provided vent fittings must be cemented to the CPVC pipe section. Use only the vent materials, primer and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.

Z21.10.3 – latest edition.

Before locating the water heater, check:

1. Check for nearby connection to:

• Water piping

• Venting connections

• Gas supply piping

• Electrical power

2. Locate the appliance so that if water connections should

leak, water damage will not occur. When such locations

cannot be avoided, it is recommended that a suitable

drain pan, adequately drained, be installed under the

appliance. The pan must not restrict combustion air

Closet and alcove installations

A closet is any room the water heater is installed in which is less than 86 cubic feet for AWN151 models, 106 cubic feet for AWN200models, 120 cubic feet for AWN286 models, 165 cubic feet for AWN400 models, 191 cubic feet for AWN501 models, 223 cubic feet for AWN601 models, 247 cubic feet for AWN701 models and 278 cubic feet for AWN801 models.

An alcove is any room which meets the criteria for a closet with the exception that it does not have a door.

Example: Room dimensions = 4 feet long, 5 feet wide, and 9 foot ceiling = 4 x 5 x 9 = 180 cubic feet.

flow. Under no circumstances is the manufacturer to be

held responsible for water damage in connection with

this appliance, or any of its components.

￿WARNING

For closet and alcove installations as shown in FIG.’s 1-1 and 1-2, CPVC vent material must be used inside the structure. The ventilating air openings

3.Check area combustible liquids.

￿WARNING

around the water heater. Remove any materials, gasoline and other flammable

Failure to keep water heater area clear and free of combustible materials, gasoline, and other flammable liquids and vapors can result in severe personal injury, death, or substantial property damage.

shown in FIG.’s 1-1 and 1-2 are required for this arrangement. Failure to follow this warning could result in fire, personal injury, or death.

Provide clearances:

Clearances from combustible materials

1. Hot water pipes—at least 1/4" from combustible materials.

4.The Armor water heater must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.

5.If a new water heater will replace an existing water heater, check for and correct system problems, such as:

System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.

2.

Vent pipe – at least 1" from combustible materials.

3.

See FIG.’s 1-1 and 1-2 on page 9 for other clearance

 

minimums.

Clearances for service access

1. See FIG.’s 1-1 and 1-2 on page 9 for recommended

service clearances. If you do not provide the minimum

clearances shown, it may not be possible to service the

water heater without removing it from the space.

￿WARNING

8

This appliance is certified as an indoor appliance. Do not install the appliance outdoors or locate where the appliance will be exposed to freezing temperatures or to temperatures that exceed 100°F.

Failure to install the appliance indoors could result in severe personal injury, death, or substantial property damage.

Image 8
Contents Installation&OperationManual Models 151 What to do if YOU Smell GASContents When servicing the water heater Please read before proceedingArmor Water Heater How it works Stainless steel heat exchangerModels 151 Models 400 Models 601Ratings CSAInstallation must comply with Closet and alcove installationsDetermine water heater location Before locating the water heater, check1Closet Installation Minimum Required Clearances Residential garage installation Provide air openings to roomVent and air piping Flooring and foundationProducts to avoid Areas likely to have contaminantsDetermine water heater location Prepare water heater Gas conversionsRemove water heater from wood pallet Models 1513Installing Propane Orifice Model ModelModels 601 Leveling the water heaterGeneral venting Direct venting options Sidewall VentDirect venting options Vertical Vent Direct venting options Vertical Vent, Sidewall AirInstall vent and combustion air piping Requirements for installation in CanadaInstalling vent or air piping PVC/CPVC Vent piping materialsPVC/CPVC Air intake/vent connections Vent Pipe, and FittingsAir inlet pipe materials Stainless steel ventStainlesssteelairintake/ventconnections FlueFlue Intake Air Adapter Termination Model Kit NumberVent and air system Removing from existing ventModel Air Intake Vent Optional room air Vent, air piping and terminationModel Kit Number Description Air contaminationIf using the alternate sidewall termination Sidewall direct ventingVent/air termination sidewall Determine location3AClearance to Gravity Air Inlets Prepare wall penetrations Seal all wall cavitiesTermination and fittings Prepare wall penetrations Alternate Field Supplied OptionMultiple vent/air terminations Description and usage Sidewall termination installationSidewall termination optional concentric vent Models 151 11 Concentric 13Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations Multiple vent/air terminationsVertical termination installation Vertical termination optional concentric vent Models 151Multiventing vertical terminations Minimum Combustion AIR TypicalAlternate vertical concentric venting Concentric Venting ArrangementExisting vent as a chase 10Existing Vent as a ChaseFlow switch and relief valve installation Flow switch adjustmentSystem piping System water piping methodsWater chemistry ScaldingPiping components 4Single Heater Single Tank 2 Temperature Cold Water Supply Cold Water Supply Number of Units Model 8Double Heater Double Tank Connecting gas supply piping Gas connectionsNatural gas Propane gasLength of Pipe in Straight Feet for 1/2 PSI Single Unit Natural Gas Pipe Capacity ChartCheck inlet gas supply Gas valve replacement Gas pressureField wiring Installation must comply withLine voltage connections Low voltage connectionsTank thermostat Low gas pressure switch Louver proving switchHigh gas pressure switch Flow switchRuntime contacts Alarm contactsWiring of the cascade 3Low Voltage Field Wiring Connections Condensate disposal Condensate drainStart-up Check for gas leaks Inspect/fill condensate systemChlorine concentration less than 200 ppm Inspect/check condensate lines and fittingsFinal checks before starting the water heater Start the water heaterIf water heater does not start correctly Check system and water heaterFor Your Safety Read Before Operating 3Operating Instructions Models 400 Set tank set point temperature Verify WHR circulator modeSet water heater operation Natural Gas PropaneConfiguration of the cascade Set clockOperating information GeneralWater heater temperature regulation Installer CascadeSequence of the cascade UserSequence of operation Operation DisplayArmor water heater control module 1Control PanelWater heater Information Dial Function Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check ignition ground wiring Check all water heater wiringCheck control settings Check water systemCheck flame signal Cleaning heat exchangerPerform start-up and checks Check burner flameModel Kit Part Component Number Description Check Delta TOiled bearing circulators Diagrams PC Interface2Wiring Diagram Page Page AWII-I-O Rev C
Related manuals
Manual 16 pages 16.89 Kb

151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.