Lochinvar 151 Prepare wall penetrations Alternate Field Supplied Option, Termination and fittings

Page 27

Installation & Operation Manual

4 Sidewall direct venting (continued)

Prepare wall penetrations (Alternate - Field Supplied Option)

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

4½ inch hole for 3 inch vent pipe

5½ inch hole for 4 inch vent pipe

7½ inch hole (191 mm) hole for 6 inch (152 mm) vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole as shown in FIG. 4-5B.

3.Use a sidewall termination plate as a template for correct location of hole centers.

4.Follow all local codes for isolation of vent pipe when passing through floors or walls.

5.Seal exterior openings thoroughly with exterior caulk.

Figure 4-5BA Typical Sidewall Termination Assembly - Models 151 - 801 PVC/CPVC or Stainless Steel

6.Stainless steel terminations are designed to penetrate walls with a thickness up to 9.25 inches of standard construction.

Multiple vent/air terminations

1. When terminating multiple Armor water heaters terminate each vent/air connection as described in this manual (FIG. 4-6A).

￿WARNING All vent pipes and air inlets must terminate at the same height to avoid possibility of

severe personal injury, death, or substantial property damage.

2.Place wall penetrations to obtain minimum clearance of 12 inches between edge of air inlet and adjacent vent outlet, as shown in FIG. 4-6A for U.S. installations. For Canadian installations, provide clearances required by CSA B149.1 Installation Code.

3.The air inlet of a Armor water heater is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent water heater vents.

Figure 4-6AMultiple Vent Terminations (must also comply with Figure 4-1A)

12" MIN. BETWEEN EDGE OF AIR INLET AND ADJACENT VENT OUTLET

VENT

SIDEWALL

TERMINATION PLATE

VENT

PIPING

BIRD SCREEN

ELBOW BIRD SCREEN

GALVANIZED

THIMBLE (WHEN REQUIRED BY LOCAL CODES)

ELBOW

AIR PIPING

AIR

VENT / AIR

Termination and fittings

TERMINATION

1.Prepare the vent termination elbow and the air termination elbow (FIG. 4-5B) by inserting bird screens. Bird screens can be obtained locally.

2.When completed, the air termination coupling must be oriented at least 12 inches (305 mm) below the vent termination and at least 12 inches (305 mm) above grade or snow line as shown in FIG. 4-1A, page 24.

3.Maintain the required dimensions of the finished termination piping as shown in FIG. 4-1A, page 24.

4.Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.

5.PVC/CPVC terminations are designed to accommodate any wall thickness of standard constructions per the directions found in this manual.

Figure 4-6BAlternate Multiple Vent Terminations w/Field Supplied Fittings (must also comply with Figure 4-1B)

27

Image 27
Contents What to do if YOU Smell GAS Installation&OperationManual Models 151Contents Please read before proceeding When servicing the water heaterStainless steel heat exchanger Armor Water Heater How it worksModels 151 Models 601 Models 400CSA RatingsBefore locating the water heater, check Installation must comply withCloset and alcove installations Determine water heater location1Closet Installation Minimum Required Clearances Flooring and foundation Residential garage installationProvide air openings to room Vent and air pipingAreas likely to have contaminants Products to avoidDetermine water heater location Models 151 Prepare water heaterGas conversions Remove water heater from wood palletModel 3Installing Propane Orifice ModelLeveling the water heater Models 601Direct venting options Sidewall Vent General ventingDirect venting options Vertical Vent, Sidewall Air Direct venting options Vertical VentPVC/CPVC Vent piping materials Install vent and combustion air pipingRequirements for installation in Canada Installing vent or air pipingVent Pipe, and Fittings PVC/CPVC Air intake/vent connectionsStainless steel vent Air inlet pipe materialsModel Kit Number Stainlesssteelairintake/ventconnectionsFlue Flue Intake Air Adapter TerminationRemoving from existing vent Model Air Intake VentVent and air system Air contamination Optional room airVent, air piping and termination Model Kit Number DescriptionDetermine location If using the alternate sidewall terminationSidewall direct venting Vent/air termination sidewall3AClearance to Gravity Air Inlets Seal all wall cavities Prepare wall penetrationsPrepare wall penetrations Alternate Field Supplied Option Multiple vent/air terminationsTermination and fittings Sidewall termination installation Sidewall termination optional concentric vent Models 151Description and usage 11 Concentric Multiventing sidewall terminations 13Concentric Vent Sidewall AttachmentVent/air termination vertical Vertical direct ventingMultiple vent/air terminations Prepare roof penetrationsVertical termination optional concentric vent Models 151 Vertical termination installationMinimum Combustion AIR Typical Multiventing vertical terminationsConcentric Venting Arrangement Alternate vertical concentric venting10Existing Vent as a Chase Existing vent as a chaseSystem water piping methods Flow switch and relief valve installationFlow switch adjustment System pipingScalding Piping componentsWater chemistry 4Single Heater Single Tank 2 Temperature Cold Water Supply Cold Water Supply Number of Units Model 8Double Heater Double Tank Gas connections Connecting gas supply pipingPropane gas Natural gasSingle Unit Natural Gas Pipe Capacity Chart Check inlet gas supplyLength of Pipe in Straight Feet for 1/2 PSI Gas pressure Gas valve replacementLow voltage connections Field wiringInstallation must comply with Line voltage connectionsFlow switch Tank thermostat Low gas pressure switchLouver proving switch High gas pressure switchAlarm contacts Wiring of the cascadeRuntime contacts 3Low Voltage Field Wiring Connections Condensate drain Condensate disposalInspect/check condensate lines and fittings Start-upCheck for gas leaks Inspect/fill condensate system Chlorine concentration less than 200 ppmCheck system and water heater Final checks before starting the water heaterStart the water heater If water heater does not start correctlyFor Your Safety Read Before Operating 3Operating Instructions Models 400 Natural Gas Propane Set tank set point temperatureVerify WHR circulator mode Set water heater operationSet clock Configuration of the cascadeGeneral Operating informationWater heater temperature regulation User InstallerCascade Sequence of the cascadeOperation Display Sequence of operation1Control Panel Armor water heater control moduleWater heater Information Dial Function Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check water system Check ignition ground wiringCheck all water heater wiring Check control settingsCheck burner flame Check flame signalCleaning heat exchanger Perform start-up and checksCheck Delta T Oiled bearing circulatorsModel Kit Part Component Number Description PC Interface Diagrams2Wiring Diagram Page Page AWII-I-O Rev C
Related manuals
Manual 16 pages 16.89 Kb

151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.