Lochinvar 151 Final checks before starting the water heater, Start the water heater

Page 54

10 Start-up

Final checks before starting the water heater

Read the Armor Water Heater Service Manual to familiarize yourself with SMART SYSTEM control module operation. Read this manual, pages 55 and 56 for proper steps to start the water heater.

Verify the water heater and system are full of water and all system components are correctly set for operation.

Verify the preparation procedures of Section 10, pages 53 and 54 have been completed.

Fill the vent condensate trap with water (removing the retaining screw in order to remove the 2 inch PVC cap with the switch located at the top of the trap). Replace the cap. Press the cap onto the trap until the cap makes contact with the drain. Replace the retaining screw.

Verify electrical connections are correct and securely attached.

Inspect vent piping and air piping for signs of deterioration from corrosion, physical damage or sagging. Verify air piping and vent piping are intact and correctly installed per this manual.

Start the water heater

1.Read and follow the Operating instructions in FIG.’s 10-2 and 10-3, pages 55 and 56.

If water heater does not start correctly

1.Check for loose connections, blown fuse or service switch off?

2.Is water heater water temperature above 200°F?

3.Is tank thermostat or tank set point set below room temperature?

4.Is gas turned on at meter or water heater?

5.Is incoming gas pressure less than 4 inches w.c.?

If none of the above corrects the problem, refer to the Troubleshooting Section of the Armor Water Heater Service Manual.

Check system and water heater

Check water piping

1.Check system piping for leaks. If found, shut down the water heater and repair immediately. (See WARNINGS on pages 53 and 54 (startup) regarding failure to repair leaks.)

2.Check Delta T. Reference Section 6 - System Piping on page 38 for more information regarding Delta T.

3.Vent any remaining air from the system using manual vents. Air in the system will interfere with circulation and cause heat distribution problems and noise.

Installation & Operation Manual

Check vent piping and air piping

1.Check for gastight seal at every connection, seam of air piping, and vent piping.

￿WARNING Venting system must be sealed gastight to prevent flue gas spillage and carbon

monoxide emissions, which will result in severe personal injury or death.

Check gas piping

1.Check around the water heater for gas odor following the procedure on page 44 of this manual (Connecting Gas Supply Piping).

￿WARNING If you discover evidence of any gas leak, shut down the water heater at once. Find

the leak source with a bubble test and repair immediately. Do not start the water heater again until corrected. Failure to comply could result in severe personal injury, death, or substantial property damage.

Propane water heaters – verify conversion

1.Verify propane conversion has been completed per the Propane Conversion instructions.

￿WARNING DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is

factory-set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

￿WARNING Armor water heaters are typically shipped ready to fire on natural gas. Check water

heater rating plate to determine which fuel the water heater is set for. If set to natural gas, it may be converted to LP by installing an orifice or by making a gas valve adjustment (see pages 13 thru 15). In order to operate on LP gas, an orifice MUST BE installed or a gas valve adjustment MUST BE made. Failure to comply could result in severe personal injury, death, or substantial property damage.

Check flame and combustion

1.Turn the main power off to the water heater by placing the “On/Off” switch in the OFF position.

2.Remove the flue temperature sensor from the flue pipe connection. Note: Combustion measurements will be made at this point.

3.Turn the main power on to the water heater by placing the “On/Off” switch in the ON position.

54

Image 54
Contents Installation&OperationManual Models 151 What to do if YOU Smell GASContents When servicing the water heater Please read before proceedingArmor Water Heater How it works Stainless steel heat exchangerModels 151 Models 400 Models 601Ratings CSADetermine water heater location Installation must comply withCloset and alcove installations Before locating the water heater, check1Closet Installation Minimum Required Clearances Vent and air piping Residential garage installationProvide air openings to room Flooring and foundationProducts to avoid Areas likely to have contaminantsDetermine water heater location Remove water heater from wood pallet Prepare water heaterGas conversions Models 1513Installing Propane Orifice Model ModelModels 601 Leveling the water heaterGeneral venting Direct venting options Sidewall VentDirect venting options Vertical Vent Direct venting options Vertical Vent, Sidewall AirInstalling vent or air piping Install vent and combustion air pipingRequirements for installation in Canada PVC/CPVC Vent piping materialsPVC/CPVC Air intake/vent connections Vent Pipe, and FittingsAir inlet pipe materials Stainless steel ventFlue Intake Air Adapter Termination Stainlesssteelairintake/ventconnectionsFlue Model Kit NumberRemoving from existing vent Model Air Intake VentVent and air system Model Kit Number Description Optional room airVent, air piping and termination Air contaminationVent/air termination sidewall If using the alternate sidewall terminationSidewall direct venting Determine location3AClearance to Gravity Air Inlets Prepare wall penetrations Seal all wall cavitiesPrepare wall penetrations Alternate Field Supplied Option Multiple vent/air terminationsTermination and fittings Sidewall termination installation Sidewall termination optional concentric vent Models 151Description and usage 11 Concentric 13Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations Multiple vent/air terminationsVertical termination installation Vertical termination optional concentric vent Models 151Multiventing vertical terminations Minimum Combustion AIR TypicalAlternate vertical concentric venting Concentric Venting ArrangementExisting vent as a chase 10Existing Vent as a ChaseSystem piping Flow switch and relief valve installationFlow switch adjustment System water piping methodsScalding Piping componentsWater chemistry 4Single Heater Single Tank 2 Temperature Cold Water Supply Cold Water Supply Number of Units Model 8Double Heater Double Tank Connecting gas supply piping Gas connectionsNatural gas Propane gasSingle Unit Natural Gas Pipe Capacity Chart Check inlet gas supplyLength of Pipe in Straight Feet for 1/2 PSI Gas valve replacement Gas pressureLine voltage connections Field wiringInstallation must comply with Low voltage connectionsHigh gas pressure switch Tank thermostat Low gas pressure switchLouver proving switch Flow switchAlarm contacts Wiring of the cascadeRuntime contacts 3Low Voltage Field Wiring Connections Condensate disposal Condensate drainChlorine concentration less than 200 ppm Start-upCheck for gas leaks Inspect/fill condensate system Inspect/check condensate lines and fittingsIf water heater does not start correctly Final checks before starting the water heaterStart the water heater Check system and water heaterFor Your Safety Read Before Operating 3Operating Instructions Models 400 Set water heater operation Set tank set point temperatureVerify WHR circulator mode Natural Gas PropaneConfiguration of the cascade Set clockOperating information GeneralWater heater temperature regulation Sequence of the cascade InstallerCascade UserSequence of operation Operation DisplayArmor water heater control module 1Control PanelWater heater Information Dial Function Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check control settings Check ignition ground wiringCheck all water heater wiring Check water systemPerform start-up and checks Check flame signalCleaning heat exchanger Check burner flameCheck Delta T Oiled bearing circulatorsModel Kit Part Component Number Description Diagrams PC Interface2Wiring Diagram Page Page AWII-I-O Rev C
Related manuals
Manual 16 pages 16.89 Kb

151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.