Lochinvar 151 Removing from existing vent, Model Air Intake Vent, Vent and air system

Page 22

3 General venting

Figure 3-13Near Water Heater Stainless Steel Venting Models 286 - 601

VENT

4" S.S. ADAPTER

4" S.S. INTERMEDIATE (FOR SAF-T VENT ONLY)

Figure 3-14Near Water Heater Stainless Steel Venting Models 701 - 801

The Armor water heater uses model specific combustion air intake and vent piping sizes as detailed in Table 3D below.

Table 3D Air Intake/Vent Piping Sizes

Model

Air Intake

Vent

Installation & Operation Manual

Minimum / Maximum allowable combustion air and vent piping lengths are as follows:

Combustion Air = 12 equivalent feet minimum / 100 equivalent feet maximum

Vent = 12 equivalent feet minimum / 100 equivalent feet maximum

When determining equivalent combustion air and vent length, add 5 feet for each 90° elbow and 3 feet for each 45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45° elbows + (1) concentric vent kit (CVK3003) = 49 equivalent feet of piping.

NOTICE

The appliance output rating will reduce by

up to 1.5% for each 25 feet of vent length.

 

Table 3E Concentric Vent Kit Equivalent Vent Lengths

Model

Kit Number

Equivalent Vent

Length

 

 

151 - 200

CVK3003

3 feet

286

CVK3007

3 feet

400

CVK3007

5 feet

501 - 601

CVK3007

30 feet

Removing from existing vent

Follow the instructions in Section 1, page 12 of this manual when removing a water heater from an existing vent system.

Vent and air piping

Vent and air system:

Installation must comply with local NOTICE requirements and with the National Fuel

Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

You must also install air piping from outside to the water heater air intake adapter. The resultant installation is direct vent (sealed combustion).

You may use any of the vent/air piping methods covered in this manual. Do not attempt to install the Armor water heater using any other means.

151 - 200

3 inches

3 inches

286 - 601

4 inches

4 inches

701 - 801

4 inches

6 inches

 

Increasing or decreasing combustion air

NOTICE

or vent piping is not authorized.

 

￿WARNING

DO NOT mix components from different systems. The vent system could fail, causing leakage of flue products into the living space. Use only approved stainless steel, PVC or CPVC pipe and fittings. For PVC/CPVC use with primer and cement specifically designed for the material used.

22

Image 22
Contents Installation&OperationManual Models 151 What to do if YOU Smell GASContents When servicing the water heater Please read before proceedingArmor Water Heater How it works Stainless steel heat exchangerModels 151 Models 400 Models 601Ratings CSADetermine water heater location Installation must comply withCloset and alcove installations Before locating the water heater, check1Closet Installation Minimum Required Clearances Vent and air piping Residential garage installationProvide air openings to room Flooring and foundationProducts to avoid Areas likely to have contaminantsDetermine water heater location Remove water heater from wood pallet Prepare water heaterGas conversions Models 1513Installing Propane Orifice Model ModelModels 601 Leveling the water heaterGeneral venting Direct venting options Sidewall VentDirect venting options Vertical Vent Direct venting options Vertical Vent, Sidewall AirInstalling vent or air piping Install vent and combustion air pipingRequirements for installation in Canada PVC/CPVC Vent piping materialsPVC/CPVC Air intake/vent connections Vent Pipe, and FittingsAir inlet pipe materials Stainless steel ventFlue Intake Air Adapter Termination Stainlesssteelairintake/ventconnectionsFlue Model Kit NumberModel Air Intake Vent Removing from existing ventVent and air system Model Kit Number Description Optional room airVent, air piping and termination Air contaminationVent/air termination sidewall If using the alternate sidewall terminationSidewall direct venting Determine location3AClearance to Gravity Air Inlets Prepare wall penetrations Seal all wall cavitiesMultiple vent/air terminations Prepare wall penetrations Alternate Field Supplied OptionTermination and fittings Sidewall termination optional concentric vent Models 151 Sidewall termination installationDescription and usage 11 Concentric 13Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations Multiple vent/air terminationsVertical termination installation Vertical termination optional concentric vent Models 151Multiventing vertical terminations Minimum Combustion AIR TypicalAlternate vertical concentric venting Concentric Venting ArrangementExisting vent as a chase 10Existing Vent as a ChaseSystem piping Flow switch and relief valve installationFlow switch adjustment System water piping methodsPiping components ScaldingWater chemistry 4Single Heater Single Tank 2 Temperature Cold Water Supply Cold Water Supply Number of Units Model 8Double Heater Double Tank Connecting gas supply piping Gas connectionsNatural gas Propane gasCheck inlet gas supply Single Unit Natural Gas Pipe Capacity ChartLength of Pipe in Straight Feet for 1/2 PSI Gas valve replacement Gas pressureLine voltage connections Field wiringInstallation must comply with Low voltage connectionsHigh gas pressure switch Tank thermostat Low gas pressure switchLouver proving switch Flow switchWiring of the cascade Alarm contactsRuntime contacts 3Low Voltage Field Wiring Connections Condensate disposal Condensate drainChlorine concentration less than 200 ppm Start-upCheck for gas leaks Inspect/fill condensate system Inspect/check condensate lines and fittingsIf water heater does not start correctly Final checks before starting the water heaterStart the water heater Check system and water heaterFor Your Safety Read Before Operating 3Operating Instructions Models 400 Set water heater operation Set tank set point temperatureVerify WHR circulator mode Natural Gas PropaneConfiguration of the cascade Set clockOperating information GeneralWater heater temperature regulation Sequence of the cascade InstallerCascade UserSequence of operation Operation DisplayArmor water heater control module 1Control PanelWater heater Information Dial Function Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check control settings Check ignition ground wiringCheck all water heater wiring Check water systemPerform start-up and checks Check flame signalCleaning heat exchanger Check burner flameOiled bearing circulators Check Delta TModel Kit Part Component Number Description Diagrams PC Interface2Wiring Diagram Page Page AWII-I-O Rev C
Related manuals
Manual 16 pages 16.89 Kb

151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.