Lennox International Inc WING manual Distances Between Units, Outdoor U Indoor U Indoor Unit Model

Page 20

REFRIGERANT CONNECTIONS

DISTANCES BETWEEN UNITS

To locate the outdoor and the indoor units, refer to the following information.

L: Distance length between both units. 1 = Refrigerant vapour line.

2 = Liquid aspiration line.

OUTDOOR U.

INDOOR U.

2

L

2

1

L

INDOOR UNIT

OUTDOOR U.

OUTDOOR U.

1

1

2

L

INDOOR U.

MODEL

 

2,8

3

4

5

 

 

 

 

 

 

Tube size

Liquid

3/8"

3/8"

3/8"(1)

1/2"

 

Vapour

5/8"(1)

3/4"

3/4"

3/4"

 

 

 

 

 

 

Refrigerant lines sizes

Máx.Vertical

15

15

15

15

Refrigerant lines sizes L

Total vertical

20

25

20

20

+

 

Horizontal

 

 

 

 

Max. number of bends

 

8

12

8

8

If the height length is greater than 5 meters, a siphon suction must be installed on the suction line every 5 meters to ensure that oil return to the compressor.

(1) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..

NOTE: THE REFRIGERANT LINES GAS AND LIQUID, MUST BE INSULATED

For other positions and longer lengths, consult the Lennox Technical Support Department for application

assistance.

The following data will be obtained from that estimation:

Pipe dimensions, Siphon suction, Insulation, Refrigerant charge

18

Image 20
Contents Application Page Contents Páge LTX Indoor Unit in COMBINATION, with Axial FAN Outdoor Unit Cooling only R-407CProduct Range Heat Pump R-22C Product Range Heat PumpSystem Configuration Indoor Unit SwitchOn OFF Model Cooling only OFF Heat PumpGeneral Description Indoor Unit LTX Outdoor Unit KJF/KJBOutdoor Unit Outdoor Unit Type KJF/KJBSpecifications Cooling only ModelOutdoor Unit Indoor UnitWeight Outdoor Unit with Centrifugal FANSpecifications Heat Pump 3CB 4CB 5CB Sound Level SET with Axial FAN Outdoor UnitSound Level SET with Centrifugal FAN Outdoor UnitElectric Wiring Diagram Number of Wires X SectionElectrical Connections and System Configuration Cooling only Heat PumpLTX Outdoor Unit LTXOutdoor Unit MOTOR-FAN Characteristics KCF 3K / KCB 3SAIR Flow KCF 4K / KCB 4S KCF 5K / KCB 5SOperating Limits Heat Pump Units Operating Limits Cooling only UnitsStandard YES Outdoor UnitIndoor Distances Between Units Outdoor U Indoor U Indoor Unit ModelOutdoor Units Type KJF-K/ KJB ModelOutdoor Units Tipo KCF-K/ KCB ExampleSetting UP Maximum DimensionsKCF-K KCB-S AIR OUT Standard OptionalAIR Standard Access to Electrical BOXDescription Outdoor Unit KCF-K / KCB 2,8-3 810 Description Outdoor Unit KCF / KCB-S 4Entrance STANDARD/ Optional Outdoor Unit KCF-K / KCB Dimensions and Setting Templates of Indoor Unit LTX KJF-K KJBKJF-K LTXInstallation Indoor Unit Installation UnitAIR-SWEEP Opening in Flase CeilingIndoor Unit Optionals Electrical Heater Outdoor Unit Optionals Main Switch Winter ControlMaintenance of the Unit Possible Problems Solution Standard Guidelines to Lennox Refac equipment Page Page W. L e n n oxe u ro p e . c o m