Lennox International Inc WING manual Specifications Cooling only, Model, Outdoor Unit, Indoor Unit

Page 8

SPECIFICATIONS COOLING ONLY

OUTDOOR UNIT WITH AXIAL FAN

R-407C

MODEL

 

 

 

WING

WING

WING

WING

 

 

 

2,8TFK

3TFK

4TFK

5TFK

Cooling capacity

(*)

W

 

7.350

9.500

11.600

13.500

 

 

 

OUTDOOR UNIT

 

 

KJF 2,8K

KJF 3K

KJF 4K

KJF 5K

COMPRESSOR

Nª / Type

 

 

1 / ALT.

1 / ALT.

1 / ALT.

1 / ALT.

FAN

 

 

 

 

5.100

5.400

5.400

Air flow outdoor unit

m3/h.

 

3.100

REFRIGERANT

Type / R-407C

gr.

(1)

1650

2500

2600

2600

EXPANSIÓN

 

 

 

Capillary

Capillary

Capillary

Capillary

WEIGHT

 

Kg

 

78

85

96

98

DIMENSIONS

 

mm.

 

781

1035

1035

1035

Height

 

 

 

 

 

 

 

973

973

Width

 

mm.

 

973

973

Depth

 

mm.

 

333

333

333

333

PACKING DIMENSIONS

mm.

 

845 x 1060 x 385

 

1085 x 1275 x 385

 

REFRIGERANT COUPLING

 

 

3/8"

3/8"

3/8"

1/2"

Liquid pipe

 

 

 

 

 

 

 

 

Gas pipe

 

 

 

5/8"

3/4"

3/4"

3/4"

INDOOR UNIT

 

LTX 3

LTX 3

LTX 5

LTX 5

FAN

Max.

1.300

1.300

2.100

2.100

Air flow indoor unit

m3/h.

1.100

1.100

1.800

1.800

 

Min.

 

 

 

 

 

WEIGHT

Kg

40

40

57

57

DIMENSIONS

 

267

267

312

312

Height

mm.

Width

mm.

1.409

1.409

1.719

1.719

Depth

mm.

656

656

756

756

PACKING DIMENSIONS

mm.

310 x 1430 x 680

352 x 1749 x 776

REFRIGERANT COUPLING

3/8"

 

 

1/2"

Liquid pipe

 

3/8"

1/2" (2)

Gas pipe

 

3/4"

3/4" (2)

3/4"

3/4"

(*)Air entry temperature into the indoor unit 27°C DB/19 °C WB

(*)Air entry temperature into the outdoor unit 35ºC DB

(1)Charge of refrigerant, factory charged on outdoor unit. See page 22, to calculate model refrigerant charge.

(2)Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit.

DB.- Dry Bulb

WB.- Wet Bulb

6

Image 8
Contents Application Page Contents Páge LTX Indoor Unit in COMBINATION, with Axial FAN Outdoor Unit Cooling only R-407CProduct Range Heat Pump R-22C Product Range Heat PumpSystem Configuration Indoor Unit SwitchOn OFF Model Cooling only OFF Heat PumpGeneral Description Indoor Unit LTX Outdoor Unit KJF/KJBOutdoor Unit Outdoor Unit Type KJF/KJBSpecifications Cooling only ModelOutdoor Unit Indoor UnitWeight Outdoor Unit with Centrifugal FANSpecifications Heat Pump 3CB 4CB 5CB Sound Level SET with Axial FAN Outdoor UnitSound Level SET with Centrifugal FAN Outdoor UnitElectric Wiring Diagram Number of Wires X SectionElectrical Connections and System Configuration Cooling only Heat PumpLTX Outdoor Unit LTXOutdoor Unit MOTOR-FAN Characteristics KCF 3K / KCB 3SAIR Flow KCF 4K / KCB 4S KCF 5K / KCB 5SOperating Limits Heat Pump Units Operating Limits Cooling only UnitsStandard YES Outdoor UnitIndoor Distances Between Units Outdoor U Indoor U Indoor Unit ModelOutdoor Units Type KJF-K/ KJB ModelOutdoor Units Tipo KCF-K/ KCB ExampleSetting UP Maximum DimensionsKCF-K KCB-S AIR OUT Standard OptionalAIR Standard Access to Electrical BOXDescription Outdoor Unit KCF-K / KCB 2,8-3 810 Description Outdoor Unit KCF / KCB-S 4Entrance STANDARD/ Optional Outdoor Unit KCF-K / KCB Dimensions and Setting Templates of Indoor Unit LTX KJF-K KJBKJF-K LTXInstallation Indoor Unit Installation UnitAIR-SWEEP Opening in Flase CeilingIndoor Unit Optionals Electrical Heater Outdoor Unit Optionals Main Switch Winter ControlMaintenance of the Unit Possible Problems Solution Standard Guidelines to Lennox Refac equipment Page Page W. L e n n oxe u ro p e . c o m