Raypak Y-200 manual Control Screens, Screen Description Factory Default

Page 13

Control Screens

To access programming mode: Press and hold the "MODE" button for 4 seconds. When in Program mode, cursor is blinking on first settable parameter. UP/DOWN arrows change parameter. LEFT/RIGHT arrows move to next selectable parameter.

NOTE: Once programming is finished, go to Screen 28 to program the USER DEFAULT SET_UP. Then open the front panel and press the SW3 reset button on the motherboard to save the new programming.

SCREEN

DESCRIPTION

FACTORY DEFAULT

Initial Screen

01

Displays the product identification and version of software.

 

Calendar, Time, Initial

 

The present month, day, year and time in a 24-hour clock

 

Setpoint

02

format; setpoint temperature.

 

 

 

 

Temperature can be displayed in degrees Fahrenheit or

 

°F or °C

02

 

Celcius

 

Default value = ° F

 

 

40 to 220 °F (4.4 to 104.4 °C); the system output

 

 

 

temperature desired when the outdoor temperature is 70 °F

 

 

 

(21.1°C); or in domestic hot water applications, the desired

Default = 140 °F

Setpoint

02

 

water temperature.

 

(60°C)

 

 

1 to 10°F; the temperature above and below the Target

 

 

 

Temperature at which the boiler turns off and on. NOTE: The

 

 

 

Control Band is disabled in PID operation. If the Control

 

 

 

Band is adjusted during PID operation, it disables the PID

Default = 3° F. No

Control Band

03

 

function.

 

value when in PID

 

 

Degrees of offset added to or subtracted from the initial set

 

Offset

04

point at the date and time selected.

 

Default = OFF

Setting Holiday

05

Data from screen 04 is combined with these screen settings.

Default = 00-00-RH

 

 

None (for Domestic Hot Water Application ONLY) or 0.01:1 to

 

 

 

8:1; determines how much the internally-calculated Target

Default value =

 

 

Temperature will change for a given outdoor temperature

200°F@10°F

Reset Ratio

06

 

change.

 

(93.3°C@-12.2°C)

System Status

07

Shows the status of the system.

 

 

 

 

 

 

 

Max default value=

 

 

 

 

 

180°F / 82.2°C

 

 

Maximum "USER" water temperatures 235°F (112.7°C) and

Min default value=

Water Temperature

 

Minimum water temperatures 40°F (4.4°C)

Display

105°F / 40.5 °C

Limits

08

 

Only.

 

Changes: Screen 23.

 

 

32 to 200°F (0 to 93.3°C), a warm-weather shutdown feature.

 

Outdoor Cut-off

 

When the outdoor temperature exceeds this setting, the

Default value = 75 °F

Temperature

09

boiler will not fire unless placed in manual override mode.

(23.8°C)

 

 

-01 to -10°F; the number of degrees below the Outdoor Cut-

 

Outdoor Cut-off

 

off Temperature which causes the Outdoor Cut-off

 

Deadband

10

 

Temperature to reset.

 

Default value = -3°F

 

 

Displays the Pump, Boiler, Stage and Auxiliary contact

This screen is

System/Network Monitor

11

status. If flashing, contacts are closed (ON).

DISPLAY only.

 

 

Displays the current Outdoor Air, System Water and Target

 

Outdoor Water TAR

12

Temperature in degrees °F or °C.

 

Default = °F

 

 

000 to 600 seconds; determines when the pump shuts off

 

AUX Delay

13

after entering Outdoor Cut-off mode.

 

Default = 180 seconds.

 

 

0 to 600 seconds; sets the time interval between sequential

 

 

 

boiler start-ups.

0 to 600 seconds;

Default = 10 seconds.

Boiler/Stage On Delay

14

sets time interval between stages turning on.

Disabled in PID.

Table E: Control Screens

13

Image 13
Contents Series Is a registered trademark of Underwriters Laboratories Inc Contents Concept of Operation Please RegisterOptions Controller ConfigurationsElectrical Installation Mechanical InstallationCheck Your Power Source Power to the Controller Controller Field WiringFor Single-Stage ON/OFF Boilers For Multiple-Stage BoilersWiring Diagram Slave Cable Installation from System Control Module Air Temperature Sensor InstallationHydronic Heating Applications Water Temperature Sensor InstallationCheck Power Power TestDomestic Hot Water Supply Applications Installation Verification Procedure Control Screens Screen Description Factory DefaultInlet / Outlet Manual OverrideCircuit Board Layout Circuit Board LayoutProgram Mode Normal ModeKeypad Initial Screen Control Screen Displays & ProgrammingPrimary Parameters M MControl Band Proportional Only Control BandN T R O L F S E T OffsetF S E F S E T F UReset Ratio Reset ParameterHoliday T T I N GRadiation System to Outdoor TemperatureSystem Status Advanced Programming FeatureMessage Meaning Outdoor Cut-Off Temperature Water TemperatureOutdoor Cut-Off Deadband T O F FSystem Monitor System TemperaturesSystem Pump no Screen O R S B S a a aBoiler/Stage on Delay Auxiliary DelayBoiler Turn-On Delay Stage Turn-On DelayBoiler Turn-Off Delay Boiler/Stage Off DelayStage Turn-Off Delay Proportional Integral Derivative PIDFor Manual Only Lead Change TimeFor Auto Only A DSetup PasswordTo enter the password S S W O R DWater Temperature Limits Set PasswordTo change the default password AAA to a new password System TestStage/Sensor Connections for Y-200 Master/Slave Systems Master UnitSlave Unit Factory DefaultsLonWorks Optional Modem Password User DefaultsAlarm Call ID Alarm Call TelephoneAlarm Call Retry Alarm Call EventsPID Interval Master Unit with SlavesA V E S N E C T E D T W O R KX X X X X X X XA V E S C O N N E C T E D V E X X X X X XMaster/Slave Diagram Temperature F Resistance K Ohms Sensor Resistance at Various TemperaturesIllustrated Parts List Limited Warranty
Related manuals
Manual 7 pages 24.2 Kb

Y-200 specifications

The Raypak Y-200 is a sophisticated and robust swimming pool heater that is designed for efficiency, durability, and optimal performance. Ideal for both residential and commercial pools, the Y-200 is equipped with advanced technology to ensure a seamless heating experience, catering to pool owners who prioritize quality and reliability.

One of the main features of the Raypak Y-200 is its impressive heating capacity. With a powerful heater that can efficiently raise the temperature of water in larger pools, users can enjoy comfortable swimming conditions year-round. The heater is designed to be easy to install and maintain, allowing for hassle-free integration into existing pool systems.

The Y-200 utilizes innovative digital controls, which give users precise measurement and adjustment capabilities. This includes a user-friendly display that provides real-time feedback on temperature settings and operational status. The digital interface makes it simple to program the heater according to individual preferences, ensuring that water is always at the desired temperature.

In terms of energy efficiency, the Raypak Y-200 boasts advanced technology that reduces energy consumption while maximizing heat output. The heater is designed with a reliable and robust heat exchanger that utilizes copper fin technology, providing excellent thermal conductivity and corrosion resistance. This ensures longevity and reduces the need for frequent maintenance.

Additionally, the Y-200 incorporates environmentally friendly technologies, including low-NOx emissions, aligning with modern standards for sustainability. This feature not only minimizes the environmental impact but also assists in meeting local regulations concerning emissions.

Durability is a hallmark of the Raypak Y-200. Constructed with high-quality materials designed to withstand the rigors of outdoor conditions, it provides users with peace of mind knowing that their investment is protected. The heater is also equipped with a weather-resistant cabinet, ensuring reliable operation regardless of climate.

In conclusion, the Raypak Y-200 stands out in the market due to its powerful heating capacity, advanced digital controls, energy-efficient technologies, and durable construction. It is an excellent choice for pool owners seeking a dependable and efficient heating solution to enhance their swimming experience. With its combination of high performance and user-friendly features, the Y-200 represents a valuable addition to any pool setting.