SECTION C: Installation

Fig. 5: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations

 

 

U.S. Installations1

Canadian Installations2

A

Clearance above grade, veranda, porch, deck, or

1 ft (30 cm)

1 ft (30 cm)

balcony

 

 

 

 

 

4 ft (1.2m) below or to side

 

B

Clearance to window or door that may be opened

of opening; 1 foot (30 cm)

3 ft (91 cm)

 

 

above opening

 

C

Clearance to permanently closed window

*

*

 

 

 

 

 

Vertical clearance to ventilated soffit located

 

*

D

above the terminal within a horizontal distance of

5 ft (1.5m)

 

2 ft (61cm) from the centerline of the terminal

 

 

E

Clearance to unventilated soffit

*

*

 

 

 

 

F

Clearance to outside corner

*

*

G

Clearance to inside corner

6 ft (1.83m)

*

 

Clearance to each side of center line extended

*

3 ft (91 cm) within a height

H

15 ft above the me-

above meter/regulator assembly

 

 

ter/regulator assembly

 

 

 

I

Clearance to service regulator vent outlet

*

6 ft (1.83m)

 

Clearance to non-mechanical air supply inlet to

4 ft (1.2m) below or to side

 

J

building or the combustion air inlet to any other

of opening; 1 ft (30 cm)

3 ft (91 cm)

 

appliance

above opening

 

K

Clearance to mechanical air supply inlet

3 ft (91 cm) above if within

6 ft (1.83m)

10 ft (3m) horizontally

 

 

 

L

Clearance above paved sidewalk or paved

7 ft (2.13m)

7 ft (2.13m) t

driveway located on public property

 

 

 

M

Clearance under veranda, porch, deck or balcony

*

12 in. (30 cm) TT

1In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code

2In accordance with the current CAN/CGA-B149 Installation Codes

tVent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves both dwellings TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and underside of

veranda, porch, deck or balcony is greater than 1 ft (30cm)

* Clearances in accordance with local installation codes and the requirements of the gas supplier

Table D: Vent/Air Inlet Termination Clearances

8

Image 10
Contents Installation Operating Instructions Page Table of Contents PAY Attention to These Terms Product Receipt Before InstallationSection a Model IdentificationGeneral Information Installations at ElevationComponent Locations Water Gas Vent Size Model Conn InputHot Water Supply General Safety Section BTime/Temperature Relationships in Scalds Water Temp Time to Produce Serious BurnSection C InstallationInstallation Codes Equipment BaseInstallations1 Canadian Installations2 Combustion and Ventilation Air Outdoor InstallationsHeater Min. Clearance Recommended From Combustible Service Indoor UnitsDirect Vent InstallationsOptional Construction Air Filter TruSeal Combustion AirWater Piping Canadian InstallationsGeneral Cold Water Operation Relief Valve Piping Hydrostatic TestCold Water Starts Model 20F∆T 30F∆T 40F∆T Min. Flow Max Flow Gpm ∆P ft Temperature & Pressure GaugeCold Water Run ∆P ft GpmHydronic Heating Domestic Hot WaterPotable Water and Space Heating Pool HeatingAutomatic Chlorinators and Chemical Feeders Winterizing Your HeaterWater Hardness Gas SupplyPool/Spa Water Chemistry PH of WaterGas Supply Pressure Gas Supply ConnectionModel NPT 4 NPT 2 NPT Check the Power Source Electrical Power ConnectionsField-Connected Controllers Field Wiring Connection Making the Electrical ConnectionsSupport of Vent Stack VentingAppliance Categories Inlet MaterialCanada Installations Vent Terminal LocationInstallation Venting Installation TipsVenting Configurations Vertical Venting CategoryTermination Vent Size Volume Model Pressure Flue Products In. WCCommon Venting Horizontal Through-the-Wall Direct Venting Category Typical Common VentingHorizontal Through-the-Wall Direct Venting Direct Vent Vertical Direct Vent VerticalControls Outdoor InstallationFreeze Protection Definitions Operating ModesOperation Modes Default Range Modulating Temperature Control User InterfaceHeater Sequence of Operation Model 503Model 1753 Section C Installation Ignition Module Flow Switch High Limit Manual ResetHigh Limit Auto Reset Optional Code ConditionAir Pressure Switch Modulating Temperature ControlHigh and Low Gas Pressure Switches Optional Low Water Cut-Off OptionalBlocked Vent Switch UDB Diagnostic BoardWiring Diagrams ModelsModels Section C Installation Start-up Section DPre Start-up Pre Start-up Check Blower AdjustmentStart-Up Initial Start-upManifold Adjustment Leak Test Procedure Dual-Seat Gas Valve Safety InspectionFollow-Up Leak Test Procedure Post Start-Up CheckSection D Start up Lighting Instructions Section EOperation To Turn Off Gas To ApplianceSection E Operation Troubleshooting Section FUDB Fault History Suggested Minimum Maintenance Schedule MaintenanceSection G Preventive Maintenance Schedule Appendix Section HInside Air Contamination Limited Parts Warranty MVB Types H and WH
Related manuals
Manual 56 pages 27.2 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.