Raypak 503-2003 manual Water Piping, Canadian Installations, General

Page 13

SECTION C: Installation

b.Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in.2 per 2,000 BTUH (1,100 mm2 per kW) of total input rat- ing of all equipment in the enclosure.

2.One permanent opening, commencing within 12 in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out- doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:

a.1 in.2 per 3,000 BTUH (740 mm2 per kW) of the total input rating of all equipment located in the enclosure, and

b.Not less than the sum of the areas of all vent connectors in the confined space.

WARNING: Do not use the “one permanent opening” method if the equipment room may be under negative pressure conditions.

Canadian Installations

CAUTION: All combustion air must be drawn from the air outside of the building; the mechanical equip- ment room must communicate directly with the outdoors.

1.Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in.2 (65 cm2).

2.For heaters using a barometric damper in the vent system there shall be a permanent air supply open- ing(s) having a cross section area of not less than 1 in.2 per 7,000 BTUH (320 mm2 per kW) up to and including 1 million BTUH, plus 1 in.2 per 14,000 BTUH (160 mm2 per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and ter-

minated 18 in. (450 mm) from the floor, but not near piping. This air supply opening requirement shall be in addition to the air opening for ventila- tion air required in 1. (above).

WARNING: Care must be taken to ensure that the equipment room is not under negative pressure conditions.

3.For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air re- quired in 1., there shall be a permanent air supply opening(s) having a total cross-sectional area of not less than 1 in.2 for each 30,000 BTUH (74 mm2 per kW) of total rated input of the burner(s), and the location of the opening(s) shall not inter- fere with the intended purpose of the opening(s) for ventilation air referred to in 1. This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.

4.Refer to B149.1 for additional information.

Water Piping

General

The heater should be located so that any water leaks will not cause damage to the adjacent area or structures.

CAUTION: This heater requires forced water circula- tion when the burner is operating. See Table F for minimum and maximum flow rates for water pump selection. The pump should be interlocked with the heater to prevent heater operation without water circu- lation.

NOTICE: Minimum pipe size for in/out connections is 2 in. NPT for 503 and 753 models and 2-½ in NPT for 1003 – 2003 models. Verify proper flow rates and ∆T as instructed in this manual.

11

Image 13
Contents Installation Operating Instructions Page Table of Contents PAY Attention to These Terms Section a Before InstallationProduct Receipt Model IdentificationComponent Locations Installations at ElevationGeneral Information Water Gas Vent Size Model Conn InputSection B Hot Water Supply General SafetyWater Temp Time to Produce Serious Burn Time/Temperature Relationships in ScaldsInstallation Codes InstallationSection C Equipment BaseInstallations1 Canadian Installations2 Heater Min. Clearance Recommended From Combustible Service Outdoor InstallationsCombustion and Ventilation Air Indoor UnitsOptional Construction Air Filter InstallationsDirect Vent TruSeal Combustion AirWater Piping Canadian InstallationsGeneral Cold Water Operation Relief Valve Piping Hydrostatic TestCold Water Starts Cold Water Run Temperature & Pressure GaugeModel 20F∆T 30F∆T 40F∆T Min. Flow Max Flow Gpm ∆P ft ∆P ft GpmDomestic Hot Water Hydronic HeatingPool Heating Potable Water and Space HeatingWinterizing Your Heater Automatic Chlorinators and Chemical FeedersPool/Spa Water Chemistry Gas SupplyWater Hardness PH of WaterGas Supply Pressure Gas Supply ConnectionModel NPT 4 NPT 2 NPT Check the Power Source Electrical Power ConnectionsField-Connected Controllers Making the Electrical Connections Field Wiring ConnectionAppliance Categories VentingSupport of Vent Stack Inlet MaterialVent Terminal Location Canada InstallationsVenting Configurations Venting Installation TipsInstallation Vertical Venting CategoryTermination Vent Size Volume Model Pressure Flue Products In. WCCommon Venting Typical Common Venting Horizontal Through-the-Wall Direct Venting CategoryHorizontal Through-the-Wall Direct Venting Direct Vent Vertical Direct Vent VerticalControls Outdoor InstallationFreeze Protection Definitions Operating ModesOperation Modulating Temperature Control User Interface Modes Default RangeModel 503 Heater Sequence of OperationModel 1753 Section C Installation Ignition Module High Limit Auto Reset Optional High Limit Manual ResetFlow Switch Code ConditionHigh and Low Gas Pressure Switches Optional Modulating Temperature ControlAir Pressure Switch Low Water Cut-Off OptionalUDB Diagnostic Board Blocked Vent SwitchModels Wiring DiagramsModels Section C Installation Start-up Section DPre Start-up Start-Up Blower AdjustmentPre Start-up Check Initial Start-upManifold Adjustment Leak Test Procedure Dual-Seat Gas Valve Safety InspectionFollow-Up Post Start-Up Check Leak Test ProcedureSection D Start up Operation Section ELighting Instructions To Turn Off Gas To ApplianceSection E Operation Section F TroubleshootingUDB Fault History Suggested Minimum Maintenance Schedule MaintenanceSection G Preventive Maintenance Schedule Appendix Section HInside Air Contamination Limited Parts Warranty MVB Types H and WH
Related manuals
Manual 56 pages 27.2 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.