Toxic chemicals, such as those used for boiler treatment shall not be introduced into this system.
Water supply systems may, because of such events as high line pressure, frequent
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater’s
Customer Service at
can be accomplished by insulating the hot water lines from the water heater.
FIGURE16.
Temperature-Pressure Relief Valve
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that
Figure 16 shows the typical attachment of the water piping to the water heater. The water heater is equipped with 1” NPT water connections for 75 gallon models.
NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the water connections. Do not solder the water lines directly to the water connections on the tank. It will harm the dip tube and damage the tank.
•Look at the top cover of the water heater. The water outlet is marked “HOT”. Put two or three turns of teflon tape around the exposed end of the 1” NPT threaded nipple. Connect the hot water pipe to the hot water outlet on the water heater.
•Look at the top of the water heater. The cold water inlet is marked “COLD”. Put two or three turns of teflon tape around the exposed end of the 1” NPT threaded nipple. Connect the cold water pipe to the cold water inlet of the water heater.
NOTE: This water heater is super insulated to minimize heat loss from the tank. Further reduction in heat loss
This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves Hot Water Supply Systems, ANSI Z21.22- CSA 4.4 and the code requirements of ASME.
14