8 ACTUATOR CONTROL

MUZ-FD09NA

MUZ-FD12NA

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds

15 seconds

ON

Compressor

OFF

ON

Outdoor fan motor

OFF

8-2. R.V. COIL CONTROL

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF

Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<COOL><HEAT>

 

 

5 seconds

 

 

5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

Compressor OFF

 

 

 

 

 

 

 

R.V.coil

ON

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan ON

 

 

 

 

 

 

 

motor

OFF

 

 

 

 

 

 

 

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

 

 

 

 

 

 

Sensor

 

Purpose

 

 

Actuator

 

 

 

Compressor

LEV

Outdoor

R.V. coil

Indoor fan

 

 

 

 

 

fan motor

motor

 

 

 

 

 

 

 

 

Discharge temperature thermistor

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil temperature thermistor

 

Cooling : Coil frost prevention

 

 

 

 

 

 

 

Heating : High pressure protection

 

 

 

 

 

 

 

 

 

 

 

 

Defrost thermistor

 

Cooling : High pressure protection

 

 

 

 

 

 

Heating : Defrosting

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin temperature thermistor

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor heat exchanger temperature thermistor

 

High pressure protection

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature thermistor

 

Low ambient temperature operation

 

 

 

15

Image 15
Contents MUZ-FD09NA MUZ-FD09NA- U1 MUZ-FD12NA MUZ-FD12NA- U1 Page Part Names and Functions Technical ChangesMUZ-FD09NA MUZ-FD12NA SpecificationOperating Range Test conditionRequired Space Outlines and DimensionsWiring Diagram MAX. Refrigerant Piping Length and MAX. Height Difference Refrigerant System DiagramData MUZ-FD09NA Performance Curve CoolingMUZ-FD09NA MUZ-FD12NA HeatingCondensing pressure Condensing Pressure Cooling65 70F MSZ-FD09NA MSZ-FD12NA Standard Operation DataCorrection of Heating capacity Test RUN Operation How to operate fixed-frequency operationRelation Between Main Sensor and Actuator Actuator ControlOutdoor FAN Motor Control R.V. Coil ControlPRE-HEAT Control Setting Service FunctionsTroubleshooting Change in Defrost SettingOFF Failure Mode Recall FunctionOperational procedure Outdoor unit failure mode table Troubleshooting Check Table Page WHT RED Trouble Criterion of Main Parts MUZ-FD09NAMUZ-FD12NACheck of compressor How to check inverter/ compressorCheck of open phase Troubleshooting FlowCheck of compressor winding Check of compressor operation timeCheck of compressor start failure Check of R.V. coil Unit operates Cool mode even if it is set to Heat modeUnit operates Heat mode even if it is set to Cool mode Check of outdoor thermistorsCheck of outdoor fan motor Check of power supplyCheck of LEV Expansion valve Emergency Operation Check of inverter P.C. boardPage Outdoor unit Electromagnetic noise enters into TV sets or radiosInverter P.C. board Test Point Diagram and VoltageRemoving the cabinet Photo Disassembly InstructionsRemoving R.V. coil Removing the inverter assembly, inverter P.C. board PhotoPhoto 4 inverter assembly Photo Removing the discharge temperature thermistorRemoving the compressor and 4-way valve Removing outdoor fan motor PhotoPage New publication, effective Jan