Outdoor fan motor does not operate.
I Check of outdoor fan motor
Disconnect CN932 from the inverter P.C. board, and measure the resistance of the outdoor fan motor.
Is the outdoor fan motor normal? |
|
|
| ||
|
| Replace the outdoor fan motor. | |||
(Refer to | No | ||||
| |||||
| Yes |
|
|
| |
|
|
|
|
|
Replace the inverter P.C. board.
Inverter does not operate.
J Check of power supply
Disconnect the connector (CN61) between compressor and intelligent power module.
Turn ON power supply and press EMERGENCY OPERATION switch.
Does POWER lamp on the indoor |
| |
unit light up? | No | |
| Yes |
|
|
| |
|
|
|
Is there voltage 280 ~ 370 VDC between DB61 (+) and DB61
the inverter P.C. board?Yes (Refer to
No
Check the electric parts in main circuit.
Rectify indoor/ outdoor connecting wire.
Yes
Is there voltage 208 / 230 VAC between the indoor terminal block S1 and S2?
Dose LED on the inverter P.C. board light up or flash? (Refer to
Yes
If light up, OK.
If flash, refer to
Replace the indoor No electronic control P.C.
board.
Replace the inverter No P.C. board.
280 ~ 370 VDC
DB61
Inverter P.C. board (Solder side)
26