D Check of compressor winding
●Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>> at 3 points
<<Judgement>> Refer to
0[Ω] ················Abnormal [short] Infinite[Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
E Check of compressor operation time
●Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit.
(TEST RUN OPERATION : Refer to
Measure the time from the start of compressor to the stop of compressor due to overcurrent.
F Check of compressor start failure
<<Judgement>>
0 second
1 second
2 seconds
10 seconds
10 minutes
Compressor starts
Abnormal (IPM failure)
(Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,)
(Outdoor P.C. board defect) (Disconnected connector)
Abnormal
(Refrigerant circuit defect) (Closed valve)
Normal
Confirm that 1~4 is normal.
• Electrical circuit check
1.Contact of the compressor connector (including CN61)
2.Output voltage of inverter P.C. board and balance of them (See
3.Direct current voltage between DB61(+) and
4.Voltage between outdoor terminal block
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start? 1
Yes
|
| Check the refrigerant circuit. | |
Yes |
| Check the stop valve. | |
|
|
| |
|
| Replace the compressor. | |
No | |||
|
1
Compressor start failure. Activate
Heat the compressor with
a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
24