Black & Decker MUZ-FD09NA- U1 Electromagnetic noise enters into TV sets or radios, Outdoor unit

Page 30

N Electromagnetic noise enters into TV sets or radios

Is the unit grounded?

Yes

Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?

No

Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?

No

Are the antennas damaged? Is the coaxial cable damaged?

Is there any poor contact in the anten- na wiring?

No

Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?

No

No

Yes

Yes

Yes

Yes

Ground the unit.

Extend the distance between the antennas and the indoor unit, and/or the antennas and the

outdoor unit.

Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or

radios and the outdoor unit.

Replace or repair the antenna.

Replace or repair the coaxial cable.

Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir-

ing of the antennas.

Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring).

Check the followings before asking for service.

1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)

2.Channel, frequency, broadcast station affected by the electromagnetic noise

3.Channel, frequency, broadcast station unaffected by the electromagnetic noise

4.Layout of ;

indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver

5.Electric field intensity of the broadcast station affected by the electromagnetic noise

6.Presence or absence of amplifier such as booster

7.Operation condition of air conditioner when the electromagnetic noise enters in

1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.

2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.

3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec- tromagnetic noise.

4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.

30

Image 30
Contents MUZ-FD09NA MUZ-FD09NA- U1 MUZ-FD12NA MUZ-FD12NA- U1 Page Technical Changes Part Names and FunctionsSpecification MUZ-FD09NA MUZ-FD12NATest condition Operating RangeOutlines and Dimensions Required SpaceWiring Diagram Refrigerant System Diagram MAX. Refrigerant Piping Length and MAX. Height DifferenceData Heating Performance Curve CoolingMUZ-FD09NA MUZ-FD12NA MUZ-FD09NACondensing Pressure Cooling Condensing pressure65 70F Standard Operation Data MSZ-FD09NA MSZ-FD12NATest RUN Operation How to operate fixed-frequency operation Correction of Heating capacityR.V. Coil Control Actuator ControlOutdoor FAN Motor Control Relation Between Main Sensor and ActuatorChange in Defrost Setting Service FunctionsTroubleshooting PRE-HEAT Control SettingFailure Mode Recall Function OFFOperational procedure Outdoor unit failure mode table Troubleshooting Check Table Page Trouble Criterion of Main Parts MUZ-FD09NAMUZ-FD12NA WHT REDTroubleshooting Flow How to check inverter/ compressorCheck of open phase Check of compressorCheck of compressor winding Check of compressor operation timeCheck of compressor start failure Check of outdoor thermistors Unit operates Cool mode even if it is set to Heat modeUnit operates Heat mode even if it is set to Cool mode Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of LEV Expansion valve Check of inverter P.C. board Emergency OperationPage Electromagnetic noise enters into TV sets or radios Outdoor unitTest Point Diagram and Voltage Inverter P.C. boardDisassembly Instructions Removing the cabinet PhotoPhoto Removing the discharge temperature thermistor Removing the inverter assembly, inverter P.C. board PhotoPhoto 4 inverter assembly Removing R.V. coilRemoving outdoor fan motor Photo Removing the compressor and 4-way valvePage New publication, effective Jan