Black & Decker MUZ-FD12NA- U1, MUZ-FD09NA- U1 service manual

Page 29

Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.

POWER lamp flashes ON and OFF in every 0.5 seconds. Outdoor unit doesn’t operate.

M How to check miswiring and serial signal error (outdoor unit does not work)

Turn OFF the power supply.

 

 

 

 

 

 

 

 

Is there rated voltage in the

 

 

 

 

 

Check the power supply.

power supply?

No

 

 

 

Yes

Turn ON the power supply.

Is there rated voltage between outdoor terminal block S1 and

S2?No

Yes

Press EMERGENCY OPERATION switch once.

Does AREA-L lamp light up? <Confirmation of the power to the indoor unit>

Yes

Is serial signal error indicated 6 minutes later?

Yes

Check the wiring.

No

Is there any miswiring, poor contact, or wire

No disconnection of the Yes Correct them. indoor/outdoor connect-

ing wire?

No

A

Turn OFF the power supply.

Check once more if the indoor/outdoor B connecting wire is not miswiring.

Short-circuit outdoor terminal block S2 and S3. 1

Turn ON the power supply.

1. Miswiring may damage indoor electronic control P.C. board during the operation.

Be sure to confirm the wiring is correct before the opera- tion starts.

3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.

A

Turn OFF inverter-controlled lighting equipment.

Turn OFF the power supply and then turn ON again.

Press EMERGENCY OPERATION switch.

Does the LED on the inverter P.C. board or

 

 

 

 

 

Replace the inverter P.C. board or the out-

the outdoor electronic control P.C. board

 

 

 

 

door electronic control P.C. board.

repeat "3.6-second-OFF and 0.8-second-

No

 

 

2

ON quick blinking"? 3

(Lighted

 

 

 

 

Yes

or not

 

2. Be careful to the residual

 

 

 

lighted)

 

voltage of smoothing capacitor.

 

 

Turn OFF the power supply.

 

Is there any error of the in-

 

 

 

 

Remove the short-circuit between

 

 

 

 

 

outdoor terminal block S2 and S3.

 

door/outdoor connecting wire,

 

 

 

Replace the indoor/

Turn ON the power supply.

 

such as the damage of the wire,

 

 

 

outdoor connecting

No

Yes

Is there amplitude of 10 to 20 VDC

 

intermediate connection, poor

 

 

 

wire.

between outdoor terminal block S2 and

 

contact to the terminal block?

 

 

 

 

 

 

 

 

 

S3? <Confirmation of serial signal>

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

Is there any error of the in-

 

 

 

 

Is there rated voltage between

 

 

 

 

 

 

 

 

 

 

 

door/outdoor connecting wire,

 

 

 

Replace the indoor/

Is serial signal error indicated 6 minutes later?

Yes

B

No

Reinstall either the unit or the light each other away.

Attach a filter on remote control receiv- ing section of the indoor unit.

indoor terminal block S1 and S2?

No

such as the damage of the wire,

 

 

outdoor connecting

Yes

<Confirmation of power voltage>

 

intermediate connection, poor

 

 

wire.

 

Yes

 

contact to the terminal block?

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the indoor electronic control P.C. board.

Be sure to release the failure-mode recall function after checking.

29

Image 29
Contents MUZ-FD09NA MUZ-FD09NA- U1 MUZ-FD12NA MUZ-FD12NA- U1 Page Part Names and Functions Technical ChangesMUZ-FD09NA MUZ-FD12NA SpecificationOperating Range Test conditionRequired Space Outlines and DimensionsWiring Diagram MAX. Refrigerant Piping Length and MAX. Height Difference Refrigerant System DiagramData MUZ-FD09NA MUZ-FD12NA Performance Curve CoolingHeating MUZ-FD09NACondensing pressure Condensing Pressure Cooling65 70F MSZ-FD09NA MSZ-FD12NA Standard Operation DataCorrection of Heating capacity Test RUN Operation How to operate fixed-frequency operationOutdoor FAN Motor Control Actuator ControlR.V. Coil Control Relation Between Main Sensor and ActuatorTroubleshooting Service FunctionsChange in Defrost Setting PRE-HEAT Control SettingOFF Failure Mode Recall FunctionOperational procedure Outdoor unit failure mode table Troubleshooting Check Table Page WHT RED Trouble Criterion of Main Parts MUZ-FD09NAMUZ-FD12NACheck of open phase How to check inverter/ compressorTroubleshooting Flow Check of compressorCheck of compressor start failure Check of compressor windingCheck of compressor operation time Unit operates Heat mode even if it is set to Cool mode Unit operates Cool mode even if it is set to Heat modeCheck of outdoor thermistors Check of R.V. coilCheck of outdoor fan motor Check of power supplyCheck of LEV Expansion valve Emergency Operation Check of inverter P.C. boardPage Outdoor unit Electromagnetic noise enters into TV sets or radiosInverter P.C. board Test Point Diagram and VoltageRemoving the cabinet Photo Disassembly InstructionsPhoto 4 inverter assembly Removing the inverter assembly, inverter P.C. board PhotoPhoto Removing the discharge temperature thermistor Removing R.V. coilRemoving the compressor and 4-way valve Removing outdoor fan motor PhotoPage New publication, effective Jan