INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
TIMBER FRAMED BUILDINGS
1.5It will be necessary to provide additional clearance when the flue passes through a wall containing any combustible materials so as to prevent a fire hazard.
1.6The hole through which the flue will pass, must have a steel sleeve which is positioned so that an air gap of at least 25mm is maintained between the outer surface of the flue, and any part of the sleeve.
1.7For further guidance on the installation of gas appliances in timber framed buildings, contact your local buildings control authority.
2.GAS SUPPLY
2.1Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible.
2.2Ensure that the gas supply is capable of delivering the required amount of gas and is in accordance with the rules in force.
2.3Soft copper tubing can be used to install the appliance. Soft soldered joints can be used externally of the appliance.
2.4This appliance is supplied complete with a factory fitted isolation device incorporated into the inlet connection, no further isolation device is required.
2.5All supply gas pipes must be purged of any debris that may have entered, prior to connection to the appliance.
2.6The gas inlet is located centrally at the bottom of the appliance. The supply pipe may be installed using one of three alternatives.
1)By drilling a hole straight through the outside wall. There is a cutout in the back panel of the Linea and the fixing bracket to allow the pipe to be concealed within the appliance.
2)Surface mounting the pipe. For this option there is a pipe cover kit 8654. This consists of
a)1.4 Metre Cover
b)2 Brackets
c)Screws and Rawlplugs
To fit the cover, measure the length required and cut down accordingly. Fix the two brackets to the wall as required. The magnets should be vertical. Fix pipe clips to the wall and install the gas pipe. The cover can now be attached to the magnets to cover the gas supply.
NOTE: There are three options of cover finishes. Black, Metallic Alloy and primed finish which allows the customer to finish any chosen colour.
3)The gas pipe can be concealed by cutting a channel in the wall. All current regulations must be adhered to and no pipe joint must be concealed in the wall.
3.VENTILATION
3.1This appliance requires no additional ventilation.
4.APPLIANCE LOCATION
IMPORTANT: DO NOT OBSTRUCT THE TOP AND BOTTOM SLOTS IN THE LINEA OUTER CASE, THESE MUST BE UNOBSTRUCTED. DO NOT RECESS THIS APPLIANCE INTO A WALL, IT MUST BE SURFACE MOUNTED ON A FLAT WALL USING THE WALL MOUNTING BRACKET SUPPLIED.
4.1This appliance does not require a hearth. It can only be fitted on an outside wall with suitable clearances for the flue terminal and guard (if required). As detailed in diagram 1.
4.2All minimum clearances must be complied with. See diagram 3. These clearances are to the outside edge of the decorative frame and are therefore dependant on the frame chosen.
3
AR1325
4.3The outer dimensions of the frames and their position relative to the flue centre and Linea are detailed in diagrams 4 and 5.
4 DESIGNO
AR1326
10