Connecting the assembly cable

Cable specification

Model

Power cable

Interconnection cable

Type GL

 

 

 

 

18/24HC

3G x 2.5 mm², H05VV-F

3G x 2.5 mm², H07RN-F

 

 

 

 

25 A

18/24HP

3G x 2.5 mm², H05VV-F

3G x 2.5 mm², H07RN-F

 

2 x 0.75 mm², H05RN-F

 

 

 

 

 

 

 

 

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3 mm.

• Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Connecting the cable

Electrical work

(1)For electrical and earth works, comply with the‘technical standards of electrical installations’and the the‘wiring regulations’of the Local wiring regulations.

(2)Tighten the terminal block screw to under 1.2 N•m (12 kgf•cm).

(3)Precautions when connecting terminal blocks of the indoor unit

Before connecting, make sure the connecting part of the terminal socket is facing upwards.

Upside down

The terminal

There is no ring

socketis damaged.

terminalto cover the wire.

 

There must be no space between the terminal and the screw when connected.

- Any remaining space may become a fire hazard due to overheating of the electrical contact.

 

 

Either the screw is not fitted

The terminal socket

properly or there is a space between

is upside down.

the screw and the ring terminal.

• For the terminal block wiring, use a wire with a ring terminal socket only.

Regular wires without a ring terminal socket may become a fire hazard due to overheating of the electrical contact during a wiring work.

English-40

MG_BETTER_A3050_IB&IM_EN_DB68-04070A-00.indd 40

17/09/2013 11:23:35

Image 40
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epaPr n atioFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Operation ranges Checking before useEnglish-10 Checking the usage time English-11Technical Specifications English-12Checking the name of the parts Main partsDisplay English-13Remote controller buttons Checking the remote controllerEnglish-14 Remote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Press the button to adjust the temperature Press the button to set the desired fan speedEnglish-17 Basic fun n iotAdjusting the air flow direction Vertical air flowHorizontal air flow English-18Using the Fast function Using the Comfort functionEnglish-19 F03undAdvance n iotMode When the air conditioner is on and in cool/heat modeEnglish-20 Setting the On/Off timer Press the On Timer or Off Timer button to set the timePress the Set/Cancel button to activate it on English-21From the moment you have set the timer English-22If the air conditioner is on If the air conditioner is off Turn off automaticallyUsing the Single User function Using the Virus Doctor functionPress the button on the remote controller English-23Using the Auto Clean function Using the Filter resetWhen the air conditioner is turned on English-24Cleaning the air conditioner Cleaning the outdoor unit heat exchangerEnglish-25 Sre04 OthCleaning the Air filter Removing the Air filterEnglish-26 Remove the Air filter from the main bodyEnglish-27 Reassembling the Air filterTop of the Air filter into the main body.. ➀ Maintaining the air conditioner English-28Troubleshooting TemperatureAdjustment is not English-29Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normalEnglish-31 General informationT05s In llan atio Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit Where sulfide gas existsEnglish-33 When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-34  Figure DescriptionAccessories Accessories in the indoor unit caseEnglish-35 LlanAccessories in the outdoor unit case Optional accessoriesTools required for installation General Tools Tools for test operations Assembling the hanger screw Fixing the installation plate English-37 Removing the Cover panel Before mounting the indoor unit Removing the screwsEnglish-38 Assembling the Cover panel After mounting the indoor unit English-39Connecting the assembly cable Cable specificationConnecting the cable English-40Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryEnglish-41 English-42 Smooth the cut edgesCut off the remaining foam insulation TorqueEvacuating the indoor unit Cutting or extending the pipeEnglish-43 Unscrew the caps at the end of each pipePut a flare nut slightly into the pipe and modify the flare English-44Depth a Drain hose installation English-45Change the direction only when it is necessary English-46Shield Downwards as seen in the pictureEvacuating the connected pipes English-47Connect a drain hose to the drain plug Drain hole Drain plugAdding Refrigerant English-48Outer Torque If you use a pipe longer than 5 mPerforming the gas leak tests English-49Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-50 660 340Smart Install mode English-51English-52 Off BlinkingFinal check and trial operation English-53How to connect your extended power cables English-54Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withMGBETTERA3050IB&IMENDB68-04070A-00.indd 17/09/2013 Questions or COMMENTS? 0211