Final check and trial operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

1. Press the Power button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2. Press the Mode button to select Cool or Heat (ARJQ) mode.

In Cool mode, use Temp hr. + or button and set the temperature at 16 °C.

In Heat mode, use Temp hr. + or button and set the temperature at 30 °C (ARJQ).

• Approximately 3~5 minutes later, outdoor unit will start to operate and the

Cool or Warm (ARJQ) air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment.

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp: From 10 °C to 12 °C (indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp: From 11 °C to 14 °C (indicative delta T) (ARJQ)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space. (ARJQ)

3. Press the Air swing button and check the following:

The airflow blades work properly.

4.Press the Power button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Turn on the air conditioner and select Fast Cool mode. Please let the compressor run for more than 5 minutes. If the compressor does not operate for more than 5 minutes due to protection control, wait about 2 minutes, and then carry out the next procedure.

2 . Release the valve caps on High and Low pressure side.

3 . Use L wrench to close the valve on the high pressure side.

4 . After approximately 2 minutes, close the valve on the low pressure side.

5 . Stop operation of the air conditioner by pressing the Power button on the indoor unit or remote controller.

6 . Disconnect the pipes.

English-54

MG_GOOD_R-410A_A3050_IB&IM_EN_DB68-04540A.indd 54

9/1/2014 5:12:18 PM

Image 54
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epPr arationFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Checking before use Operation rangesEnglish-10 Technical Specifications English-11Display Checking the name of the partsMain parts English-12Checking the remote controller Remote controller buttonsEnglish-13 Storing the remote controller Remote controller displayLow Battery warning Inserting the batteriesBasic function Press the button to adjust the temperature Press the button to set the desired fan speedEnglish-16 Horizontal air flow Adjusting the air flow directionVertical air flow English-17Press the SET button FfPress the Power button Setting the On/Off timerSetting the On timer English-18Setting the Off timer English-19Mode English-20Additional options available Step cooling function English-21Using the Fast function Using the Comfort functionEnglish-22 Using the Single User function Press the Single user button on the remote controllerEnglish-23 Lighting in Auto clean mode Using the Auto Clean functionSetting the Beep sound English-24English-25 Cleaning the air conditionerCleaning the outdoor unit heat exchanger Heat exchangerEnglish-26 Cleaning the air filterRemoving the Air filter Remove the air filter from the main bodyReassembling the Air filter English-27Top of the Air filter into the main body.. ➀ Maintaining the air conditioner English-28English-29 TroubleshootingAir conditioner Take the cover off and takeOdors permeate Error is indicatedPress the Power Water is droppingGeneral information English-3107stIn llan atio Power supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-33 English-34 When installing more than 1 outdoor unitWhen the air outlet is towards the wall  Figure DescriptionAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case English-35Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsAssembling the hanger screw English-37Removing the Cover panel Before mounting the indoor unit This QR code for detail video of indoor unit installationRemoving the screws English-38Assembling the Cover panel After mounting the indoor unit English-39Connecting the cable Connecting the assembly cableCable specification English-40Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberEnglish-41 Cut off the remaining foam insulation English-42Smooth the cut edges TorqueEnglish-43 Evacuating the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeEnglish-44 Correct InclinedCracked Drain hose installation English-45Shield Change the direction only when it is necessaryEnglish-46 Downwards as seen in the pictureConnect a drain hose to the drain plug Evacuating the connected pipesEnglish-47 Drain hole Drain plugAdding Refrigerant English-48Outer Torque English-49 Please fill in with indelible ink1975 Performing the gas leak tests English-50 Outdoor unit installed on the wall by rack Fixing the outdoor unit in place English-51 Smart Install mode English-52English-53 Off / Blinking / OnFinal check and trial operation English-54Packing and unpacking guide English-55Apply heat to the contraction tube to contract it How to connect your extended power cablesEnglish-56 After tube contraction work is completed, wrap it withEnglish-57 Questions or COMMENTS? 0211