Samsung AR18JRFSBWKXMG, AR12JQFNBWK/MG manual English-49, Please fill in with indelible ink, 1975

Page 49

Evacuating the connected pipes

Important information regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Do not vent gases into the atmosphere.

1. Please fill in with indelible ink,

the factory refrigerant charge of the product,

the additional refrigerant amount charged in the field and

+the total refrigerant charge. on the refrigerant charge label supplied with the product.

a. Factory refrigerant charge of the product: see unit name plate

b.Additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)

c.Total refrigerant charge

d.Refrigerant cylinder and manifold for charging

Refrigerant type

GWP value

R-410A

1975

GWP=Global Warming Potential

Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

= (

 

 

) kg

 

 

 

 

 

 

= (

 

 

) kg += (

 

) kg

 

 

 

 

b

 

 

 

 

c

07stIn llan atio

• The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

Charging the refrigerant under conditions of liquid by using a liquid pipe

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.

1.Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant.

Cylinder with siphon

Cylinder without siphon

Siphon

Charge the refrigerant standing the

Charge the refrigerant turning the cylinder

cylinder upright.

upside down.

• If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the

characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use electronic scales.

If cylinder doesn’t have syphon, upset it.

English-49

MG_GOOD_R-410A_A3050_IB&IM_EN_DB68-04540A.indd 49

9/1/2014 5:12:08 PM

Image 49
Contents Air Conditioner Features of your new air conditioner Contents English-4 Safety precautions01epPr aration English-5English-6 For UsingEnglish-7 English-8 Do not place objects or devices under the indoor unitEnglish-9 For CleaningOperation ranges Checking before useEnglish-10 English-11 Technical SpecificationsMain parts Checking the name of the partsDisplay English-12Remote controller buttons Checking the remote controllerEnglish-13 Low Battery warning Remote controller displayStoring the remote controller Inserting the batteriesBasic function Press the button to set the desired fan speed Press the button to adjust the temperatureEnglish-16 Vertical air flow Adjusting the air flow directionHorizontal air flow English-17Setting the On timer Setting the On/Off timerPress the SET button FfPress the Power button English-18English-19 Setting the Off timerEnglish-20 ModeAdditional options available English-21 Step cooling functionUsing the Comfort function Using the Fast functionEnglish-22 Press the Single user button on the remote controller Using the Single User functionEnglish-23 Setting the Beep sound Using the Auto Clean functionLighting in Auto clean mode English-24Cleaning the outdoor unit heat exchanger Cleaning the air conditionerEnglish-25 Heat exchangerRemoving the Air filter Cleaning the air filterEnglish-26 Remove the air filter from the main bodyEnglish-27 Reassembling the Air filterTop of the Air filter into the main body.. ➀ English-28 Maintaining the air conditionerAir conditioner TroubleshootingEnglish-29 Take the cover off and takePress the Power Error is indicatedOdors permeate Water is droppingEnglish-31 General information07stIn llan atio Installing the unit Choosing the installation locationPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit Where sulfide gas existsEnglish-33 When the air outlet is towards the wall When installing more than 1 outdoor unitEnglish-34  Figure DescriptionAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case English-35Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsEnglish-37 Assembling the hanger screwRemoving the screws This QR code for detail video of indoor unit installationRemoving the Cover panel Before mounting the indoor unit English-38English-39 Assembling the Cover panel After mounting the indoor unitCable specification Connecting the assembly cableConnecting the cable English-40Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryEnglish-41 Smooth the cut edges English-42Cut off the remaining foam insulation TorqueCutting or extending the pipe Evacuating the indoor unitEnglish-43 Unscrew the caps at the end of each pipeCorrect Inclined English-44Cracked English-45 Drain hose installationEnglish-46 Change the direction only when it is necessaryShield Downwards as seen in the pictureEnglish-47 Evacuating the connected pipesConnect a drain hose to the drain plug Drain hole Drain plugEnglish-48 Adding RefrigerantOuter Torque Please fill in with indelible ink English-491975 English-50 Performing the gas leak testsFixing the outdoor unit in place Outdoor unit installed on the wall by rackEnglish-51 English-52 Smart Install modeOff / Blinking / On English-53English-54 Final check and trial operationEnglish-55 Packing and unpacking guideEnglish-56 How to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-57 0211 Questions or COMMENTS?