Samsung AR24HSFSEWKNMG manual Shortening or extending the refrigerant pipes assembly pipe

Page 45

Installation

1Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2Smooth the cut edges.

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

 

 

 

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

NOTE

If you want to shorten or extend the pipes, see Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe) on page 44.

4Cut off the remaining foam insulation.

5If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6Pass the pipe through the hole in the wall.

NOTE

The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test. For further details. see Step 4.1 Performing the gas leak tests on page 50.

CAUTION

Tighten the flare nut with a torque wrench according to specified method. If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Do not box in or cover the pipe connection. All refrigerant pipe connection must be easily accessible and serviceable.

44English

Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe)

Pipe cutter

Pipe

90°

Oblique

Rough

Burr

D

 

90°±2°

 

 

 

A

45°±2°

 

 

 

 

L

 

 

R 0.4 to 0.8

Pipe

Flare

D

 

 

 

 

(Unit: mm)

Outer diameter (D)

Depth (A) Flare dimension (L)

ø 6.35

1.3

8.7 to 9.1

ø 9.52

1.8

12.8 to 13.2

ø 12.70

2.0

16.2 to 16.6

ø 15.88

2.2

19.3 to 19.7

Flare nut

Indoor outlet pipe

Connecting pipe

 

 

 

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

 

 

 

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

DB68-06043A-00.indd 44

4/1/2016 5:44:43 PM

Image 45
Contents Samsung Air conditionergioner Contents Safety Information on Installation Preparation InstallationFor Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning 2016 54325 PM Display Indoor Unit OverviewInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes To 24 CControlling air flow direction Controlling fan speedCool mode Cooling OperationStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeQuick Smart Features Auto modeFan mode Fast function Quiet function Comfort functionBeep sound function Single user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Running Auto clean Cleaning at a GlanceCleaning the filter Troubleshooting Cleaning and Maintenance 11.85 Btu/hr/W 55 Btu/hr/W 12.10 Btu/hr/W 70 Btu/hr/W Technical Specifications16.0 kg 55.2 kg95 W/W 12.00 Btu/hr/W 75 Btu/hr/W 11.95 Btu/hr/W 65 Btu/hr/W20 ˚C 15 ˚CInstallation Safety Information on InstallationPower supply line, fuse, or circuit breaker Overview of installation location requirements Choosing the installation locationPreparation Minimum clearances for the outdoor unitPacking and Unpacking Indoor unitOutdoor unit Accessories Checking and preparing accessories and toolsTools Drilling a hole through the wallTaping the pipes, cables, and drain hose Indoor Unit Installation Disassembling the installation plateDisassembling the cover panel Connecting the power and communication cables assembly cable Prepare a compressor and the following tools Optional Extending the power cableOptional Extending the drain hose Installing and connecting the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe 10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plate12 Assembling the cover PanelOutdoor Unit Installation Fixing the outdoor unit in placeOptional Fixing the outdoor unit to a wall with a rack Evacuating the air Adding refrigerant Installation Inspection Running the Smart Install modePerforming the gas leak tests LED Performing final check and trial operation Pumping down refrigerantPumping down for removing the product