Installation
Step 4.3 Performing final check and trial operation
1Check the following:
•Strength of the installation site
•Tightness of pipe connection to detect gas leak
•Electric wiring connection
•
•Drainage
•Grounding conductor connection
•Correct operation (Take the following steps.)
2Press the (Power) button on the remote control to check the following:
•The indicator on the indoor unit lights up.
•The airflow blade opens and the fan gears up for operation.
3Press the (Mode) button to select Cool or Heat mode. Then take the following
•In Cool mode, use the Temperature button to set the set temperature to 16 °C.
•In Heat mode, use the Temperature button to set the set temperature to 30 °C.
•Check whether, approximately 3 to 5 minutes later, the outdoor unit starts, and a cool or warm air blows out.
•After 12 minutes of stationary condition, check the indoor unit air treatment.
4Press the (Air swing) button to check whether the airflow blades work properly.
5Press the (Power) button to stop the trial operation.
Pumping down refrigerant
1Shut off the liquid valve with the Allen wrench.
2Turn on the air conditioner in cooling with fan operating at high velocity. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop.)
3After 2 minutes of operation, shut the suction valve with the same wrench.
52English
4Turn off the air conditioner and switch mains supply off.
5Disconnect tubing. After disconnection, protect valves and tubing ends from dust.
CAUTION
•Compressor damage may occur if the compressor is run at a negative suction pressure.
Pumping down for removing the product
1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.
2Let the compressor run for more than 5 minutes.
3Release the valve caps on High and Low pressure side.
4Use
5After approximately 1 minute, close the valve on the low pressure side.
6Stop operation of the air conditioner by pressing the (Power) button on the indoor unit or remote control.
7Disconnect the pipes.
| 1 |
| 1 minute |
Liquid service port | Gas service port |
<High pressure> | <Low pressure> |
2
Off