Samsung AR24HSFSEWKNMG manual Performing final check and trial operation, Pumping down refrigerant

Page 53

Installation

Step 4.3 Performing final check and trial operation

1Check the following:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (Take the following steps.)

2Press the (Power) button on the remote control to check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

3Press the (Mode) button to select Cool or Heat mode. Then take the following sub-steps:

In Cool mode, use the Temperature button to set the set temperature to 16 °C.

In Heat mode, use the Temperature button to set the set temperature to 30 °C.

Check whether, approximately 3 to 5 minutes later, the outdoor unit starts, and a cool or warm air blows out.

After 12 minutes of stationary condition, check the indoor unit air treatment.

4Press the (Air swing) button to check whether the airflow blades work properly.

5Press the (Power) button to stop the trial operation.

Pumping down refrigerant

Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit. This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

1Shut off the liquid valve with the Allen wrench.

2Turn on the air conditioner in cooling with fan operating at high velocity. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop.)

3After 2 minutes of operation, shut the suction valve with the same wrench.

52English

4Turn off the air conditioner and switch mains supply off.

5Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

CAUTION

Compressor damage may occur if the compressor is run at a negative suction pressure.

Pumping down for removing the product

1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.

2Let the compressor run for more than 5 minutes.

3Release the valve caps on High and Low pressure side.

4Use L-wrench to close the valve on the high pressure side.

5After approximately 1 minute, close the valve on the low pressure side.

6Stop operation of the air conditioner by pressing the (Power) button on the indoor unit or remote control.

7Disconnect the pipes.

 

1

 

1 minute

Liquid service port

Gas service port

<High pressure>

<Low pressure>

2

Off

DB68-06043A-00.indd 52

4/1/2016 5:44:52 PM

Image 53
Contents Samsung Air conditionergioner Contents Safety Information on Installation Preparation InstallationFor Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning 2016 54325 PM Display Indoor Unit OverviewInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes To 24 CControlling air flow direction Controlling fan speedStep cooling function Cool modeCooling Operation Dehumidifying Operation Dry modeHeating Operation Heat modeFan mode Quick Smart FeaturesAuto mode Fast function Quiet function Comfort functionBeep sound function Single user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Running Auto clean Cleaning at a GlanceCleaning the filter Troubleshooting Cleaning and Maintenance 11.85 Btu/hr/W 55 Btu/hr/W 12.10 Btu/hr/W 70 Btu/hr/W Technical Specifications16.0 kg 55.2 kg95 W/W 12.00 Btu/hr/W 75 Btu/hr/W 11.95 Btu/hr/W 65 Btu/hr/W20 ˚C 15 ˚CInstallation Safety Information on InstallationPower supply line, fuse, or circuit breaker Overview of installation location requirements Choosing the installation locationPreparation Minimum clearances for the outdoor unitOutdoor unit Packing and UnpackingIndoor unit Accessories Checking and preparing accessories and toolsTools Drilling a hole through the wallTaping the pipes, cables, and drain hose Disassembling the cover panel Indoor Unit InstallationDisassembling the installation plate Connecting the power and communication cables assembly cable Prepare a compressor and the following tools Optional Extending the power cableOptional Extending the drain hose Installing and connecting the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plate12 Assembling the cover PanelOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationFixing the outdoor unit in place Evacuating the air Adding refrigerant Performing the gas leak tests Installation InspectionRunning the Smart Install mode LED Pumping down for removing the product Performing final check and trial operationPumping down refrigerant