Desa CCL3930PR Ventilation Air From Inside Building, Ventilation Air From Outdoors, Continued

Page 6
Inside Building.

6

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location (Cont.) Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

The space in the example on page 5 is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the

extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

Inside Building.

Room,

Or

Option 2

B. Vent room directly to the outdoors. See Ventilation Air From Out-

Option 1

Remove

doors.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

doors. WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option VENTILATION AIR 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

Ventilation Air From Inside BuildingVentilation Air From OutdoorsFigure 2 - Ventilation Air from Inside BuildingFigure 3 - Ventilation Air from OutdoorsManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundvisitManual backgroundManual background.Manual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

111161-01A

Image 6
Contents WHAT TO DO IF YOU SMELL GAS UNVENTED VENT-FREE GAS LOG HEATERNot Used With Hand-HeldThermostat Remote Do not try to light any applianceTABLE OF CONTENTS SAFETY INFORMATIONWARNINGS PRODUCT IDENTIFICATION ContinuedSAFETY INFORMATION SAFETY PILOT PRODUCT FEATURESREMOTE CONTROL ACCESSORIES See Accessories, pageConfined Space and Unconfined Space DETERMINING FRESH-AIRFLOW FOR HEATER LOCATIONUnusually Tight Construction AIR FOR COMBUSTION AND VENTILATIONVentilation Air From Outdoors VENTILATION AIRVentilation Air From Inside Building AIR FOR COMBUSTION AND VENTILATIONMINIMUM FIREPLACE CLEARANCE TO INSTALLATIONCHECK GAS TYPE COMBUSTIBLE MATERIALSContinued Minimum Noncombustible Material ClearancesINSTALLATION Between 8 and 12, above. IfDetermining Minimum Mantel Clearances MANTEL CLEARANCESFLOOR CLEARANCES INSTALLATIONContinued INSTALLING HEATER BASE ASSEMBLYINSTALLATION ChimneyINSTALLATION CONNECTING TO GAS SUPPLYInstallation Items Needed Installation Items NeededINSTALLATION Pressure Testing gas Supply Piping systemCHECKING GAS CONNECTIONS ContinuedINSTALLATION INSTALLING REMOTE RECEIVER UNITPressure Testing Heater Gas Connections ContinuedINSTALLATION INSTALLING WIRELESS REMOTE CONTROL ACCESSORYInstalling 9-VoltBattery in Receiver ContinuedINSTALLATION INSTALLATIONContinued FOR YOUR SAFETY READ BEFORE LIGHTING OPERATING HEATERLIGHTING INSTRUCTIONS OPTIONAL REMOTE OPERATION MANUAL LIGHTING PROCEDURETO TURN OFF GAS TO APPLIANCE Shutting Off HeaterPILOT FLAME PATTERN WIRING DIAGRAMINSPECTING BURNERS MAIN BURNERCLEANING AND MAINTENANCE LOGSMAIN BURNER POSSIBLE CAUSE TROUBLESHOOTINGOBSERVED PROBLEM REMEDYTROUBLESHOOTING Maintenance, pageRefer to Air for Combustion and Venti OBSERVED PROBLEMOBSERVED PROBLEM ing Gas Connections, pages 12 andTROUBLESHOOTING Maintenance, pageTECHNICAL SERVICE SPECIFICATIONSSERVICE HINTS REPLACEMENT PARTSCCL3018NR, CCL3018NRA ILLUSTRATED PARTS BREAKDOWNMODELS CCL3018PR, CCL3018PRA ILLUSTRATED PARTS BREAKDOWNPART NUMBER PARTS LISTPARTS LIST CCL3018PRCCL3930PR, CCL3930PRA MODELSCCL3924PR, CCL3924PRA CCL3924NR, CCL3924NRA CCL3930NR, CCL3930NRAPARTS LIST PART NUMBEREQUIPMENT SHUTOFF VALVE GA5010 ACCESSORIESPARTS CENTRAL FIREPLACE HOODOWNERS REGISTRATION FORM Postage Required TAPETAPE Page NOT A UPC WARRANTY INFORMATIONLIMITED WARRANTY COMFORT GLOW VENT-FREEGAS LOG HEATERS