Desa CGB3924NRA, CGD3924NRA, CGB3930NRA Troubleshooting, Observed Problem Possible Cause Remedy

Page 19

OWNER’S MANUAL

TROUBLESHOOTING

Note: For additional help, visit DESA International’s Technical Service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode not connected to igni-

1.

Reconnect ignitor cable

spark at ODS/pilot

 

tor cable

 

 

 

2.

Ignitor cable pinched or wet

2.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

3.

Piezo ignitor nut is loose

3.

Tighten nut holding piezo ignitor to base

 

 

 

 

panel of log set. Nut is located behind

 

 

 

 

base panel

 

4.

Broken ignitor cable

4.

Replace ignitor cable

 

5.

Bad piezo ignitor

5.

Replace piezo ignitor

 

6.

Ignitor electrode broken

6.

Replace piezo ignitor

 

7.

Ignitor electrode positioned wrong

7.

Replace piezo ignitor

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or manual shutoff

1.

Turn on gas supply or open manual

spark at ODS/pilot but no ignition

 

valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob. Re-

 

 

 

 

peat igniting operation until air is removed

 

5.

ODS/pilot is clogged

5.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 18) or replace ODS/

 

 

 

 

pilot assembly

 

6.

Gas regulator setting is not correct

6.

Replace gas control

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3.

Manual shutoff valve not fully open

3.

Fully open manual shutoff valve

 

4.

Pilot flame not touching thermocouple,

4.

A) Contact local natural gas company

 

 

which allows thermocouple to cool,

 

 

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

lem could be caused by one or both of

 

Maintenance, page 18) or replace ODS/

 

 

the following:

 

pilot assembly

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

5.

Thermocouple connection loose at con-

5.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

6.

Thermocouple damaged

6.

Replace thermocouple

 

7.

Control valve damaged

7.

Replace control valve

www.desatech.com

Continued

105677

19

Image 19
Contents What to do if YOU Smell GAS Remote ReadyUnvented Natural GAS LOG Heater Safety Information Local Codes Product FeaturesRemote Control Accessories Product IdentificationUnusually Tight Construction Providing Adequate VentilationConfined Space and Unconfined Space Determining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors LOG Sizing Requirements InstallationCheck GAS Type Minimum Fireplace Clearance to Combustible MaterialsMinimum Noncombustible Material Clearances Unvented Natural GAS LOG Heater InstallationDetermining Minimum Mantel Clearances Determining Minimum Mantel Clearances When Using a HoodMantel Clearances Floor ClearancesInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Attaching Flexible Gas Hose to Heater Connecting to GAS SupplyChecking GAS Connections Installing Remote RE- Ceiver UnitInstalling Logs CGD3924NRA Installing Wireless Remote Control AccessoryInstalling 9-Volt Battery in Receiver Tered over the burner U bend Installing Logs on Models CGB3924PRA and CGB3930PRAOperating Heater For Your Safety Read Before LightingLighting Instructions Optional Remote Operation Manual Lighting ProcedureUnvented Natural GAS LOG Heater Operating To Turn OFF GAS To AppliancePilot Flame Pattern Inspecting BurnersMain Burner Cleaning Burner Injector Holder and Pilot AIR Inlet Hole Unvented Natural GAS LOG Heater Cleaning and MaintenanceService Hints Technical ServiceObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Unvented Natural GAS LOG Heater TroubleshootingGas leak. See Warning statement at CGD3924NRA Unvented Natural GAS LOG Heater Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListCGB3924NRA CGB3930NRA KEY CGB3924NRA CGB3930NRA Part Number Description QTY Parts Central Unvented Natural GAS LOG Heater Replacement PartsParts Under Warranty Parts not Under WarrantySpecifications AccessoriesWiring Diagram Warranty Information